background image

Supplementary documentation BM 100 A with PROFIBUS-PA

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 

R

 D-47058 Duisburg

2/7

Tel.: 0203-301 309 

R

 Fax: 0203-301389 · e-mail: [email protected]

Contents:

GENERAL.................................................................................................................................................................3

ITEMS INCLUDED WITH SUPPLY ...........................................................................................................................3

SOFTWARE HISTORY .............................................................................................................................................3

1. PROFIBUS-PA......................................................................................................................................................3

1.1 PROFIBUS-PA - S

ERVICES

...............................................................................................................................4

1.2 N

ETWORK 

C

ONFIGURATION

.................................................................................................................................4

1.2.1 GSD file .....................................................................................................................................................4
1.2.2 Cyclic data exchange .................................................................................................................................4

1.3 M

EANING OF MEASUREMENT AND STATUS INFORMATION

.........................................................................................5

2. ELECTRICAL CONNECTION ...............................................................................................................................6

2.1 I

NTERCONNECTION OF DEVICES IN THE HAZARDOUS LOCATION

................................................................................6

2.2 B

US CABLE

........................................................................................................................................................6

2.3 S

HIELDING AND GROUNDING

................................................................................................................................6

2.4 PROFIBUS-PA 

CONNECTION

.............................................................................................................................7

3. MENU SETTINGS FOR PROFIBUS-PA................................................................................................................7

4. TECHNICAL DATA, PROFIBUS IDENT-NO. EE01 ...............................................................................................7

Summary of Contents for BM 100 A

Page 1: ...NE 07 2000 KROHNE Messtechnik GmbH Co KG Ludwig Krohne Str 5 R D 47058 Duisburg 1 7 Tel 0203 301 309 R Fax 0203 301389 e mail krohne krohne de Supplementary Installation and Operating Instructions BM...

Page 2: ...LY 3 SOFTWARE HISTORY 3 1 PROFIBUS PA 3 1 1 PROFIBUS PA SERVICES 4 1 2 NETWORK CONFIGURATION 4 1 2 1 GSD file 4 1 2 2 Cyclic data exchange 4 1 3 MEANING OF MEASUREMENT AND STATUS INFORMATION 5 2 ELECT...

Page 3: ...and connection to a PROFIBUS PA fieldbus Attention Please set the controller to manual mode before changing parameters of the BM 100 A Items included with supply In addition to the standard scope of s...

Page 4: ...can be placed in the project This will then enable the cyclic communication measured values and status 1 2 2 Cyclic data exchange During network configuration the user has to define which measurement...

Page 5: ...Exponent 127 1 Mantissa Value 1 0 2 129 127 1 2 1 2 2 2 3 Value 1 4 1 0 5 0 25 0 125 7 5 Status 1 Byte Quality Quality Substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 0 bad 0 1 unce...

Page 6: ...4 1mH km C 80 200nF km the approved input values of the field devices Uo Io Po are matchable with the output values of the power supply e g segmment coupler which menas UI Uo II Io und PI Po 2 2 Bus...

Page 7: ...e not PROFIBUS PA The value must not be changed 1 6 2 ADDRESS Input 0 126 Settings out of the range will be ignored If out of range 126 will be used as default value Address can be changed via local d...

Reviews: