15
When refitting the terminal in the device, the pins are automatically clicked back into their position in the
device. Coding of the terminals is complete. We recommend coding each terminal as described above.
5.2
Parameterization
The KRIWAN INTspector app visualizes your system's operating data.
The aim of the following is to provide support when using the KRIWAN INTspector app. The following
examples are based on the KRIWAN Diagnose device INT69® YF 22A701P081, 20A701P081 and
app version 4.2.2.
To use the app, you need to download the INTspector app from the app store on your terminal device.
Then connect the protection device either via the Bluetooth gateway (02S377S021) or via the USB
gateway (02S365S21 – not compatible with Apple products) with your terminal device and open the
INTspector app.
More about the KRIWAN INTspector app in chapter 6.2.
5.2.1
Parameter table
Parameter name
Setting range
Unit
Min
Max
Motor temperature 1
– Sensor type
– Switch-off temperature
– Warning temperature
– Hysteresis
– Trip delay
– Restart delay
– Lead correction
Deactivated
-100
-100
0
0.1
0
0
PT100
300
300
300
3600
Locked
100
°C
°C
K
s
s
Ω
Temperature 1
– Sensor type
– Switch-off temperature
– Warning temperature
– Hysteresis
– Trip delay
– Restart delay
– Lead correction
Deactivated
-100
-100
0
0.1
0
0
PT1000
300
300
300
3600
Locked
100
°C
°C
K
s
s
Ω
Temperature 2
– Sensor type
– Switch-off temperature
– Warning temperature
– Hysteresis
– Trip delay
– Restart delay
– Lead correction
Deactivated
-100
-100
0
0.1
0
0
PT100
300
300
300
3600
Locked
100
°C
°C
K
s
s
Ω
Leakage 1
– Operating mode
– Switch-off value
– Warning value
– Hysteresis
– Trip delay
– Restart delay
Deactivated
10
10
1
0.1
0
Resistance undershoot
1000
1000
999
3600
Locked
kΩ
kΩ
kΩ
s
s
Leakage 2
– Operating mode
– Switch-off value
Deactivated
10
Resistance undershoot
1000
kΩ