KRIWAN INT280-60 Quick Start Manual Download Page 1

KRIWAN Industrie-Elektronik GmbH · Allmand 11 · D-74670 Forchtenberg · phone (+49) 7947 822 0 · fax (+49) 7947 1288 · e-mail: [email protected] · home: www.kriwan.com

Technical changes reserved

Pr

oduct gr

oup S

Edition: 710.00566.0

INT280-60

®

INT280-60

®

INT280-60

Wiring diagram

Dimensions in mm

PE

N

L3

L2

L1

F1

F2

Q1

H1

Alarm

1

2

3

4

5

INT280-60

M

3 AC

169

93.9

29.5

Ø50

Ø47.6

Ø6.7

Ø58.5

112°

90°

34°

45°

60

97

32

111.5

9

Application

The INT280-60 is a further development of the reliable KRIWAN oil level 
regulators.
The oil level regulator INT280-60 monitors and controls the oil level in 
the refrigerant compressors. The problem of poor oil distribution in 
multi-compressor packs has been overcome by actively supplying oil 
from the oil reservoir. This minimizes the risk of operating without 
enough oil in the compressor.

Functional description

If the oil level is too low, the intelligent filling algorithm controls the oil 
refill. To do this, the integrated solenoid valve is opened cyclically. 
The oil level regulator switches the compressor off through the internal 
relay if the oil level remains too low after an extended period of time. Oil 
refilling continues after this.
When the oil level is sufficient the relay tightens, the compressor can 
start again.
The reactions are time delayed, to prevent unnecessary switching in 
response to temporary fluctuations in the oil level.
The INT280-60 has its own monitoring system of the optical sensor. In 
the event of malfunctions or soiling, the relevant warning or error will be 
notified.
The integrated LED signals the current status.
For operation in the specified manner, the supply voltage has to be on 
permanently on the INT280-60.