4. OPERATION AND MAINTENANCE
©2014 Kraus Global Ltd.
34
Retail CNG Dispenser Manual
Connect manager’s
keypad to “Keypad 2”
(J301) terminals.
Figure 3.5: Manager Keypad Connector Location
4.2.3 Disabling Programming mode
1.
Disconnect power from the dispenser at the breaker /
distribution panel.
2.
Shut off gas to the dispenser and ensure that the area is free of
hazardous gas / vapour.
3. Open the dispenser door and remove the two sealing bolts from
the MICON
®
enclosure located in the centre of the dispenser. If
the dispenser has already been sealed by a weights and measures
inspector, it may be necessary to break the lead seals.
4. Toggle the programming switch located at the center of the
intrinsic safety module. Please see Figure 3.4. The switch should
be in the rightmost position.
5. Replace the sealing bolts and close the dispenser door.
Disconnect the Manager keypad from the primary display (see
Figure 3.5).
6. Restore power to the dispenser and allow it to boot. The
dispenser should now be in normal operating mode. The letters
“CFG” should
NOT
be displayed on the third line of the primary
displays.