52
The gas control system used in the LEO series meets the requirements for appliances burning gase-
ous fuels in Directives 2009/142/EEc and DIN EN 298, DIN EN 126, DIN EN 13611. The system can be
supplied with a gaseous fuel, second and third family according to EN- 437. first, make sure that the
connected device is intended to be supplied with the type of gas contained in the gas installation. All
the necessary information about the required parameters of the gas can be found on the nameplate
of the fireplace. Before connecting the gas supply pipes, it is necessary to purge them to remove me-
tal filings and other contaminants from their interior. The automatic gas control should be protected
from moisture and dust. These factors may cause irreparable damage to individual components. Gas
supply pipes to the fireplace should be equipped with a ball valve of 1⁄2 inch in diameter. Individual
elements of gas installation cannot be sealed using a Teflon tape or pTfE tape (please use the sealing
elements supplied with the unit). If the gas installation needs to be connected to a settler, install it
according to fig. 10. The settler protects the controller from gas contaminants.
pRESSuRE DROp/cAp AcITY
2009/142/EEc oraz DIN EN 298, DIN EN 126, DIN EN
13611
fuEL
Gaseous fuels of the first, second and third family,
according to EN-437
pRESSuRE DROp/cAp AcITY
2,5 mbar for 1,2 m
3
/h
ADJuSTMENT RANGE
class c, according to EN 88
ADJuSTING THE REGuLATOR
5 to 40 mbar (50 do 400 kpa)
MOuNTING pOSITION
the module cannot be mounted with the breaker block
downwards. The control position can be adjusted in the
range from 0° to 90° relative to its home position
MAXIMuM pRESSuRE Of INpuT GAS
50 mbar (5 kpa)
MAIN GAS INLET cONNEcTION
Reducing nipple 1/2‘‘ na 3/8‘‘
cONTROL BuRNER cONNEcTION
M10x1 for a pipe of 6 mm
DIScHARGE Of THE MAIN GAS INLET
AND OuTLET
from the side or bottom
MAXIMuM TIGHTENING TORQuE
nlet and outlet connection
3
/
8
“: 35 Nm control burner
connection:15 Nm
THERMOcOupLE /BREAKER BLOcK
M10x1, M9x1, M8x1
IGNITION
piezoelectric ignition
ALLOWABLE TEMpERATuRE LIMIT
controller: 0 °c to 80 °c
Receiver without batteries: 80 °c
Odbiornik z bateriami: 55 °c
pilot: 60 °c
przewód zapłonowy: 150 °c
Technical specifications of the gas control system used in the LEO
Summary of Contents for LEO SERIES
Page 3: ...3 LEO LP 100 LEO L 100 LEO 100 LEO 200 LEO P 100 LEO L 200 ...
Page 5: ...5 LEO L 100 LEO P 100 LEO LP 100 ...
Page 6: ...6 LEO P 200 LEO 200 LEO L 200 ...
Page 41: ...41 LEO LP 100 LEO L 100 LEO 100 LEO 200 LEO P 100 LEO L 200 ...
Page 43: ...43 LEO L 100 LEO P 100 LEO LP 100 ...
Page 44: ...44 LEO P 200 LEO 200 LEO L 200 ...
Page 79: ...79 LEO LP 100 LEO L 100 LEO 100 LEO 200 LEO P 100 LEO L 200 ...
Page 81: ...81 LEO L 100 LEO P 100 LEO LP 100 ...
Page 82: ...82 LEO P 200 LEO 200 LEO L 200 ...
Page 121: ...121 ...
Page 122: ...122 ...
Page 123: ...123 ...