TP-410 - Configuration and Distribution of Control Data
17
17
6.1.3
The Remote Mode
In the remote mode, the PC is connected to the RS-232 port on the transmitter (for
example,
TP-125EDID
). In this example, the PC controls machine # 1 and all its
outputs, as well as machine # 2 and its outputs.
Figure 10: RS-232 Remote Control
6.1.4
Connecting Multiple TP-410 Units via the RS-485 Bus
You can connect up to 15
TP-410
units via the RS-485 bus with control from a PC
or serial controller. To connect up to 15
TP-410
units via RS-485 (see
Figure 11
):
1. Connect the RS-485 terminal block of the first
TP-410
to the RS-485
terminal block of the second
TP-410
, and so on (see
Section 5.3
2. Set each
TP-410
address number to be a unique number (see
),
connecting all the
TP-410
units via the RS-485 terminal blocks.
Section 7.1
3. On the first and last
TP-410
physical devices on the RS-485 bus, set the
RS-485 termination DIP-switch ON (terminating the RS-485 line at 120
Ω
,
see
).
Section 7.3
4. On all other
TP-410
units, ensure that the RS-485 termination DIP-switch is
OFF.
).