background image

START-UP and PULL DOWN

A thorough leak test and evacuation must precede charging and start-up.  Refer to the condensing unit or sys-
tem installation instructions.  Check the compressor oil level before and during start-up.  Check fan blades for
correct rotation.  The control circuit should be energized at least 12 hours and preferably 24 hours before
charging and start-up to open the liquid line solenoid and turn on the crankcase heater.  This will assist with a
good, deep evacuation and provide added compressor protection during charging and start-up.

Do not leave equipment unattended during start-up.  Evaporator fan motors may require a jumper until the
room has cooled sufficiently to keep the fans from cycling.  High moisture levels in new rooms can cause rapid
frost build up on the evaporator coil.  It may be necessary to manually initiate a defrost.  Do not allow the coil
to become completely blocked with frost.

EXPANSION VALVE ADJUSTMENT - EVAPORATOR SUPERHEAT

Expansion valves will usually need adjustment.  Evaporator superheat should be approximately 6° to 12°F.
Low temperature evaporators will operate most efficiently with 6° to 8° superheat at design room temperature.
Obtain evaporator superheat by accurately measuring the suction line temperature at the expansion valve
bulb.  Obtain pressure at the Schrader fitting on the suction connection.  Convert the pressure to temperature
using a pressure-temperature chart.  Subtract the converted temperature from the measured temperature to
obtain superheat.  For close coupled systems with short line runs it may be necessary to slightly increase
superheat at the evaporator to insure the minimum desirable (25°F) superheat at the compressor.

The access panels on the evaporator must always be in place when the evaporator is operating.  Do not leave
the access panels off after valve adjustment or service.

DEFROST TIMER ADJUSTMENT

Usually, 2 to 4 defrost per day will be satisfactory.  In extreme cases 6 defrost per day may be necessary.
With a medium frost load, air circulation is still good and coils defrost best.  Defrosting with a very light frost
load can cause steaming.  Allowing a coil to become heavily frosted can reduce air circulation and reduces the
system capacity.   After the room has pulled down to temperature and the evaporator has gone through 6 or 8
defrost, it should be thoroughly checked after a defrost to make sure the coil and drain pan are clear of all
frost and ice.  Manually remove any ice accumulations.  Fan blades and guards should also be cleared of frost
or ice.  Defrost termination control adjustment may be necessary.  The timer fail safe should be set about 6 to
10 minutes beyond normal termination time.  The usual timer fail-safe setting for electric defrost evaporators is
30 to 40 minutes.  For optimum system performance and efficiency, set the timer pins to initiate a defrost when
the coil has a medium frost load.

EVAPORATOR MAINTENANCE

Disconnect electrical power to the evaporator when inspecting or cleaning.  Evaporators should be checked
occasionally and cleaned of all dirt or grease accumulation.  Fan blades and guards may require more fre-
quent cleaning.  DO NOT use ammonia or other cleaning chemicals that are corrosive to copper or aluminum.
The drain pan should be lowered and thoroughly cleaned to prevent any drain restriction.  The drain connec-
tion must be open and clean.  Coils must be power washed if they become dirty.  We recommend using the
System Operation Check List on page 10.  Using often can give indication of a problem before it becomes a
major issue.  The Check List can also assure the owners that their equipment is in good condition and is being
maintained properly.  The Check List should be retained as a permanent service record document for each
system.

REPLACEMENT PARTS

To order replacement parts always include the evaporator model number, serial number, and a complete
description of the part.  Provide component model numbers, markings, size, function, and state the quantity
you are ordering.  Providing complete information will insure prompt handling of your order.  See page 2 for
unit model number and serial number information.  See page 11 and 12 for replacement part numbers.

9

Summary of Contents for CED

Page 1: ...812 SEPTEMBER 1999 NEW KRAMER ELECTRIC DEFROST EVAPORATORS LPE LVE MSE CSE HSE CED KED INSTALLATION START UP AND MAINTENANCE INSTRUCTIONS 14230 Lochridge Blvd Covington Georgia 30014 770 778 5800 Fax...

Page 2: ...MSE models are recommended for room temperatures to 20 F model CED and KED to 30 F and model HSE to 10 F Model CED and KED are available with D type direct drive fans as standard or an optional PP typ...

Page 3: ...uld be selected from the valve manufacturers literature If liquid subcooling is present be sure to use the correction factor to determine the correct size valve Avoid oversizing the valve which can ca...

Page 4: ...ainst a wall or directly on the floor Always leave 1 or more inches of air space along side walls and each end wall space should be equivalent to the evaporator height or more Do not locate evaporator...

Page 5: ...not to scale No doors at side or back of evaporators Back wall H H 2 x H H Side Evaporator wall Air Air 5 x H Side Alternate wall Door location See Table above for H dimension Door Front wall 5 EVAPO...

Page 6: ...1 3 8 1 5 8 1 3 8 1 5 8 2 1 8 1 2 1 2 5 8 60000 75000 1 1 8 1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 1 2 5 8 5 8 75000 90000 1 3 8 1 3 8 1 5 8 1 3 8 1 5 8 1...

Page 7: ...1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 2 1 2 5 8 48000 60000 1 1 8 1 3 8 1 3 8 1 1 8 1 3 8 1 5 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 2 5 8 5 8 60000 75000 1 1 8 1 3 8 1 5 8 1 3 8 1 5 8 1...

Page 8: ...n shipment Spin each fan blade to be sure it turns freely FIELD WIRING Terminal Block H1 H2 H3 3 N X 4 M3 HEATER SAFETY DEFROST TERMINATION Brown Yellow MOTORS and CAPACITORS FAN DELAY Brown Use only...

Page 9: ...edium frost load air circulation is still good and coils defrost best Defrosting with a very light frost load can cause steaming Allowing a coil to become heavily frosted can reduce air circulation an...

Page 10: ...iver Pressure_________PSI Evaporator Frost Load Light o Medium o Heavy o ___________________ Time since last defrost_____hours Timer set ____ defrost per day _____ minute Fail Safe DEFROST Check Heate...

Page 11: ...006009 30 202136007 Defrost Termination Std 103079010 103079010 103079010 Adjustable DTFD is Fan Delay Std 103079009 103079009 103079009 standard on CED KED Adjustable DTFD Optional 204464037 20446403...

Page 12: ...510 3 206240 005 240 3538 3 206240 019 460 3249 CED 6 KED 4 450 620 400 550 12 113100 115 800 2 113095 230 725 850 1070 750 950 12 113101 115 1150 2 113096 230 660 1360 1200 26 113102 115 1070 4 1130...

Reviews: