ELECTRIC DEFROST EVAPORATOR

RECOMMENDED LINE SIZE   

 

l

l

     

 

R-404A,  R-507

EVAPORATOR  +20°F SUCTION  +10°F SUCTION

 -10°F SUCTION

 -25°F SUCTION

 -40°F SUCTION

LIQUID  LINE

EVAPORATOR

BTUH

30'

60'

100'

30'

60'

100'

30'

60'

100'

30'

60'

100'

30'

60'

100'

30'

60'

100'

BTUH

3000

3/8

1/2

1/2

1/2

1/2

1/2

1/2

5/8

5/8

1/2

5/8

5/8

1/2

5/8

5/8

3/8

3/8

3/8

3000

4000

1/2

1/2

5/8

1/2

1/2

5/8

1/2

5/8

5/8

1/2

5/8

7/8

1/2

5/8

7/8

3/8

3/8

3/8

4000

6000

1/2

5/8

7/8

1/2

5/8

7/8

5/8

5/8

7/8

5/8

7/8

7/8

5/8

7/8

7/8

3/8

3/8

3/8

6000

9000

5/8

7/8

7/8

5/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

3/8

3/8

3/8

9000

12000

5/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8 1 1/8

7/8

7/8 1 1/8

3/8

3/8

3/8

12000

15000

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

1 1/8

7/8 1 1/8 1 1/8

7/8

1 1/8 1 1/8

3/8

3/8

1/2

15000

18000

7/8

7/8 1 1/8

7/8

7/8

1 1/8

7/8

1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

3/8

3/8

1/2

18000

24000

7/8

7/8 1 1/8

7/8

1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 1/8 1 1/8 1 3/8

3/8

1/2

1/2

24000

30000

7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 1/8 1 1/8 1 3/8 1 1/8 1 3/8 1 3/8

1/2

1/2

1/2

30000

36000

1 1/8 1 1/8 1 3/8 1 1/8 1 1/8 1 3/8 1 1/8 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8

1/2

1/2

1/2

36000

42000

1 1/8 1 1/8 1 3/8 1 1/8 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8

1/2

1/2

5/8

42000

48000

1 1/8 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8

1/2

1/2

5/8

48000

60000

1 1/8 1 3/8 1 3/8 1 1/8 1 3/8 1 5/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8

1/2

5/8

5/8

60000

75000

1 1/8 1 3/8 1 5/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8

5/8

5/8

5/8

75000

90000

1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 1 5/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8

5/8

5/8

7/8

90000

120000

1 3/8 1 5/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8

5/8

7/8

7/8

120000

150000

1 5/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 5/8 2 1/8 2 5/8 2 5/8

7/8

7/8

7/8

150000

180000

1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8

7/8

7/8 1 1/8

180000

210000

2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8

7/8

7/8 1 1/8

210000

240000

2 1/8 2 1/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8 2 5/8 2 5/8 3 1/8

7/8

1 1/8 1 1/8

240000

300000

2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8 2 5/8 2 5/8 3 1/8 2 5/8 3 1/8 3 5/8 1 1/8 1 1/8 1 3/8

300000

All Line Sizes are for O.D. Type L, ACR, or RS copper tube.  All Lengths are "Equivalent Feet."

Shading indicates Maximum Suction Riser Size.  Diameter of riser must not be larger than horizontal run.

All lines selected for 2°F equivalent pressure loss maximum.

Consider double suction risers if capacity control is used.

See page 6 for "equivalent feet" of valves and fittings.

Suction traps must be used for proper oil return.

Liquid line is from receiver to expansion valve.

7

Summary of Contents for CED

Page 1: ...812 SEPTEMBER 1999 NEW KRAMER ELECTRIC DEFROST EVAPORATORS LPE LVE MSE CSE HSE CED KED INSTALLATION START UP AND MAINTENANCE INSTRUCTIONS 14230 Lochridge Blvd Covington Georgia 30014 770 778 5800 Fax...

Page 2: ...MSE models are recommended for room temperatures to 20 F model CED and KED to 30 F and model HSE to 10 F Model CED and KED are available with D type direct drive fans as standard or an optional PP typ...

Page 3: ...uld be selected from the valve manufacturers literature If liquid subcooling is present be sure to use the correction factor to determine the correct size valve Avoid oversizing the valve which can ca...

Page 4: ...ainst a wall or directly on the floor Always leave 1 or more inches of air space along side walls and each end wall space should be equivalent to the evaporator height or more Do not locate evaporator...

Page 5: ...not to scale No doors at side or back of evaporators Back wall H H 2 x H H Side Evaporator wall Air Air 5 x H Side Alternate wall Door location See Table above for H dimension Door Front wall 5 EVAPO...

Page 6: ...1 3 8 1 5 8 1 3 8 1 5 8 2 1 8 1 2 1 2 5 8 60000 75000 1 1 8 1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 1 2 5 8 5 8 75000 90000 1 3 8 1 3 8 1 5 8 1 3 8 1 5 8 1...

Page 7: ...1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 2 1 2 5 8 48000 60000 1 1 8 1 3 8 1 3 8 1 1 8 1 3 8 1 5 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 2 5 8 5 8 60000 75000 1 1 8 1 3 8 1 5 8 1 3 8 1 5 8 1...

Page 8: ...n shipment Spin each fan blade to be sure it turns freely FIELD WIRING Terminal Block H1 H2 H3 3 N X 4 M3 HEATER SAFETY DEFROST TERMINATION Brown Yellow MOTORS and CAPACITORS FAN DELAY Brown Use only...

Page 9: ...edium frost load air circulation is still good and coils defrost best Defrosting with a very light frost load can cause steaming Allowing a coil to become heavily frosted can reduce air circulation an...

Page 10: ...iver Pressure_________PSI Evaporator Frost Load Light o Medium o Heavy o ___________________ Time since last defrost_____hours Timer set ____ defrost per day _____ minute Fail Safe DEFROST Check Heate...

Page 11: ...006009 30 202136007 Defrost Termination Std 103079010 103079010 103079010 Adjustable DTFD is Fan Delay Std 103079009 103079009 103079009 standard on CED KED Adjustable DTFD Optional 204464037 20446403...

Page 12: ...510 3 206240 005 240 3538 3 206240 019 460 3249 CED 6 KED 4 450 620 400 550 12 113100 115 800 2 113095 230 725 850 1070 750 950 12 113101 115 1150 2 113096 230 660 1360 1200 26 113102 115 1070 4 1130...

Reviews: