Kozy-World KWN215 Owner'S Operation And Installation Manual Download Page 5

5

       WARNING:   Rework  worksheet, add-
ing  the  space  of  the  adjoining
unconfined  space. The  combined  spaces
must  have  enough  fresh air to supply  all
appliances  in  both  spaces.

VENTILATION  AIR
Ventilation  Air  From  Inside Building
This  fresh  air  would  come  from  an
adjoining  unconfined  space.  When
ventilating   to  an  adjoining  unconfined
space, you  must provide  two permanent
openings: one  within  12

"

  of  the  ceiling

and  one  within  12

"

  of  the  floor  on  the

wall  connecting  the  two  spaces  (see
options 1 and 2,  Figure  2). You  can  also
remove  door  into  adjoining  room (see
option 3, Figure 2). 

Follow  the  National

Fuel  Gas  Code  NFPA 54/ANS Z223.1.
Section  5.3,  Air  for  Combustion  and
Ve n t i l a t i o n

    f o r     r e q u i r e d   s i z e   o f

ventilation  grills  or  ducts

 Example:
 Gas  water  heater          40,000        Btu/Hr
 Vent  free  heater    +      20,000        Btu/Hr
 Total                         =      60,000        Btu/Hr

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add the Btu/Hr of all fuel burning appliances in the space.
     Vent-free heater                                                      Btu/Hr
     Gas water heater*                                                    Btu/Hr
    Gas furnace                                                               Btu/Hr
     Vented gas heater                                                    Btu/Hr
     Gas Fireplace logs                                                   Btu/Hr
     Other gas appliances* +                                         Btu/Hr
    Total                                =                                            Btu/Hr
    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                          Btu/Hr (maximum the space can support)
                         Btu/Hr (actual amount of Btu/Hr used)
         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           60,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. See

  Ventilation  Air  from

Inside  Building

, page 5.

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  from  Outdoors

, page 6 .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

AIR  FOR  COMBUSTION  AND  VENTILATION

Continued

Summary of Contents for KWN215

Page 1: ...or use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer Save...

Page 2: ...face of heater becomes very hot when running heater Keep children and adults away from hot surface to avoid burns or clothing ignition Heater will remain hot for a time after shut down Allow surface t...

Page 3: ...the greatest heater comfort and may result in lower gas bills LOCAL CODES Install and use heater with care Follow all local codes In the absence of local codes use the latest edition of National Fuel...

Page 4: ...ation air by one of the methods described in the National Fuel Gas Coda ANS Z223 1 Section 5 3 or applicable local codes Unusually Tight Construction The air that leaks around doors and windows may pr...

Page 5: ...n the space Vent free heater Btu Hr Gas water heater Btu Hr Gas furnace Btu Hr Vented gas heater Btu Hr Gas Fireplace logs Btu Hr Other gas appliances Btu Hr Total Btu Hr Do not include direct vent ga...

Page 6: ...t union l test gauge connection l sediment trap l tee joint l pipe wrench A CSA AGA design certified equip ment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur...

Page 7: ...en down see Figure 7 Methods For Attaching Mounting Bracket To Wall Only use last hole on each end of mounting bracket to attach bracket to wall These two holes are 16 inches apart from their c e n t...

Page 8: ...ace mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten screws until mounting bracket is firm...

Page 9: ...1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 13 A CSA AGA design certified equipment shutoff valve with 1 8 NPT tap is an acceptable a...

Page 10: ...r 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 15 Apply mixture of liquid soap and water to gas joints Bubbles...

Page 11: ...ting pilot again 8 Turn control knob counterclockwise to desired heating Level The main burner should light Set control knob to any heat level between HI and LO n THERMOSTATn CONTROL OPERATION The the...

Page 12: ...ightly press in control turn control knob clockwise to the PILOT position Figure 18 Control Knob In The OFF Position Figure 19 Pilot 1 STOP Read the safety information on the side of heater 2 Make sur...

Page 13: ...pilot flame comes out of the pilot assembly see Figure 24 With the unit off lightly blow air through the air inlet hole You may blow through a drinking straw if com pressed air is not available Figur...

Page 14: ...nt shutoff valve is not fully open 4 Thermocouple connection loose at control valve 5 Pilot flame is not touching thermo couple This allows thermocouple to cool causing pilot flame to go out This prob...

Page 15: ...expanding while heating or contracting while cooling 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner orifice see Cleaning an...

Page 16: ...pors from paint hair spray glues etc See IMPORTANT statement above 2 G a s l e a k S e e W a r n i n g statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is p...

Page 17: ...number 814 643 2299 ACCESSORIES Purchase these heater accesso ries from your local dealer If they can not supply these accessories contact KOZY WORLD for information You can also write to the address...

Page 18: ...1 8 ILLUSTRATED PARTS BREAKDOWN THERMOSTAT MODELS KWN217 KWN317 ODS Pilot Assembly...

Page 19: ...er Glass Retainer Self Tapping Screw Thermostat Valve Assembly Screws Thermosstat Valve Base Assembly Ignitor Assembly Ignitor Line Pressure Regulator Washer Self Locking Screw Main Inlet Tube Assembl...

Page 20: ...2 0 ILLUSTRATED PARTS BREAKDOWN NON THERMOSTAT MODELS KWN215 KWN315 ODS Pllot Assembly...

Page 21: ...ew Control valve Ignitor Line Control Knob Assembly Control Valve Fixed Nut Pressure Regulator Washer Self Locking Screw Main Inlet Tube Assembly ODS Line Assembly Lower Gas Outline Tube Assembly Medi...

Reviews: