SECTION 10

  OPERATING INSTRUCTIONS

Setup Komfort 8K1 Control Module–Additional Diagnostic Information 

#SFD-36

R.6  February 2022

#SFD-36

R.6  February 2022

47

HUSSONG MFG. CO., INC.

KOZY HEAT FIREPLACES

10.1  Setup Komfort 8K1 Control Module

1.  Set the main ON/OFF rocker switch in the OFF position.
2.  Remove the remote control components from packaging.
3.  Install (3) AAA batteries (included in the components packet) in 

the remote control battery bay. 

4.  Connect the transformer to an AC power supply.
5.  Connect the fan to the AUX 300 control module 

FIGURE 

9.1

 (page 45).

10.2  Initialize the Komfort 

8K1 Control System

1.  Verify the ON/OFF/REMOTE switch is in the REMOTE position. A 

green LED will illuminate and blink three times.

2.  Using a small item, such as a paper clip, press and release the 

LEARN button located near the ON/OFF/REMOTE switch.

3.  The control module will beep once and illuminate a green LED 

for 10 seconds. 

4.  While the green LED is blinking, press the POWER button on the 

remote control. The control module will emit a double beep to 

indicate that the remote is initialized to the control system.

10.3  Automatic Safety Turn-off

This system will execute an automatic turn OFF command after 8 

hours of continuous main burner operation. 

10.4  Backup Battery Operation

This appliance will operate on the backup battery pack in a power 

outage. The lifespan of the backup batteries depends on various 

factors, such as the quality of the batteries, number of ignitions, etc.

Only install backup batteries in power outages only. Do not leave 

batteries installed in the backup battery pack. 

10.5  Control System 7 Day Time-out

If your Komfort 8K1 control system is set to pilot-on-demand ignition 

with 

7

 consecutive days without ignition of the main burner, the 

pilot will turn off. This is a standard safety feature of the Komfort 8K1 

control system. 
Once you turn the pilot-on-demand on, the 

7

 day timer will start. If at 

any time during the following 

7

 days your main burner ignites, it will 

reset the timer back to 

7

 days. 

See section 

10.8.7

 on page 49 for more information about pilot 

ignition selection.

How to check if your system is set to pilot-on-demand:

• 

The remote control screen will display the snowflake with text 

PILOT icon.

To select the preferred pilot ignition:

1.  Press the MENU button to activate the menu.
2.  Using the UP and DOWN arrows, highlight the PILOT icon and 

press SELECT. 

3.  Use the UP and DOWN arrows to turn the pilot-on-demand ON 

or OFF, then press SELECT. 

• 

A single beep will be emitted from the control module indicating 

pilot-on-demand feature has been activated. 

• 

A double beep will be emitted from the control module 

indicating the pilot-on-demand feature has been deactivated.

10.6  Komfort 8K1 Control System 

Ignition Sequence

The Komfort 8K1 control module will attempt (1) time for ignition, for 

approximately 60 seconds.
If there is no flame ignition (rectification) within the (60) second time 

frame, the Komfort 8K1 system will go into a lockout. The control 

module will display an error code (see section 

10.7

), followed by a 

blinking red/green LED, indicating a system lockout. 

10.6.1  Reset Control Module after Lockout

10.6.1.1  Disconnect Power Supply

• 

Disconnect the power supply to the control module. After 

approximately (5) second, reconnect power supply.

10.6.1.2  ON/OFF/REMOTE Switch

• 

Turn the ON/OFF/REMOTE switch on the control module to OFF. 

Wait approximately (5) seconds, and turn the ON/OFF/REMOTE 

switch to REMOTE. The control module will illuminate a green 

LED (2) times and emit a beep. 

• 

Turn the ON/OFF/REMOTE switch on the control module to OFF. 

Wait approximately (5) seconds, and turn the ON/OFF/REMOTE 

switch to ON. The control module will illuminate a green LED (2) 

times and emit a beep. The ignition sequence will start again.

10.7  Additional Diagnostic Information

Diagnostic codes are outlined below and should be used as an 

additional troubleshooting tool.

Red LED will blink (1) time, then a red/green LED blink (lockout)

• 

Error caused by fuel-type selector switch is in incorrect position 

or fuel-type selector switch is damaged. Verify selector is in 

correct position. If condition persists, replace the control module.

Red LED will blink (2) times, then a red/green LED blink (lockout)

• 

Error caused by Insufficient voltage from ignition coil to 

pilot flame igniter. Clear the lockout (see section 

10.6.1 

above) and attempt ignition. If condition persists, replace the 

control module. 

Red LED will blink (3) times, then a red/green LED blink (lockout

)

• 

Error caused by inadequate gas supply. Verify proper inlet 

pressure to the gas line.

• 

Error caused by detection of false flame or short in sensor lead. 

Verify that pilot leads are correctly terminated to the control 

module, and that no shorted wires exist.

• 

Error caused by sense and/or igniter lead disconnected. Verify 

that the pilot sensor rod, igniter rod, and hood are clean. 

Summary of Contents for SPRINGFIELD 36

Page 1: ...rket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance...

Page 2: ......

Page 3: ...fety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong President Dudley Hussong Board Chairman Homeowner R...

Page 4: ......

Page 5: ...30 7 3 Vent Restriction 31 7 4 Vent Heat Shield Assembly Installation 32 7 5 Vent Installation 33 7 6 Class A Chimney Masonry Chimney Conversion 39 7 7 Coaxial to Co Linear Chimney Conversion 40 7 8...

Page 6: ......

Page 7: ...ing said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 1 3 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accorda...

Page 8: ...atural Gas and Propane Installation Code local authorities or codes having jurisdiction in you area regarding derate guidelines 2 1 1 1 US Installations Refer to the American Gas Association guideline...

Page 9: ...mensions 30 762mm 131 8 334mm 19 502mm 295 8 752mm 35 908mm 2113 16 554mm 337 16 849mm 313 16 96mm 119 16 293mm 2 58mm 145 16 364mm 255 16 643mm 8 203mm 36 933mm 21 553mm 2 50mm FRONT VIEW TOP VIEW LE...

Page 10: ...rs for this appliance Only doors certified with the appliance shall be used IMPORTANT Consider the height of hearth finish material when building a fireplace platform Proper installation of safety bar...

Page 11: ...ou are planning a corner installation with use of an exterior and or interior kit the requirements in section 3 7 2 HEAT TRANSFER KIT INSTALLATION REQUIREMENTS on page 21 must be followed If planning...

Page 12: ...e face to allow the fireplace front to be flush with typical 1 2 12mm non combustible facing material Follow instructions below 1 Locate the 2 screws on each side securing the top stand off brackets t...

Page 13: ...anges facing away from the fireplace 3 Secure the nailing flanges to the fireplace with screws provided through the slots in nailing flanges 4 Bend perforation on nailing flange until parallel with fi...

Page 14: ...9 1 4 743mm A 45 projection from appliance sides 0 0mm Appliance sides to an adjacent parallel sidewall 6 152mm Fireplace enclosure floor to 3 4 19mm trim 35 889mm Fireplace enclosure floor to combust...

Page 15: ...panel extending the full width and depth of the appliance This fireplace may be elevated off the floor provided it is properly supported by framing materials and maintains ceiling clearances If instal...

Page 16: ...may be insulated using unfaced insulation products listed as non combustible per ASTM E 136 3 5 3 3 Horizontal Terminations IMPORTANT Horizontal vent sections require 1 4 6mm rise for every 12 305mm o...

Page 17: ...5mm 1 25mm 1 25mm 21 533mm NATURAL GAS AND PROPANE MINIMUM HORIZONTAL TERMINATION FRAMING NATURAL GAS AND PROPANE 800 1 MINIMUM HORIZONTAL TERMINATION FRAMING 10 273mm 11 279mm 57 16 138mm REQUIRED WA...

Page 18: ...insulated building envelope and weatherproof membrane are not to be interrupted by fireplace installation See FIGURE 3 7 on the following page Fireplace operation is approved from 40 F to 110 F All wi...

Page 19: ...ed by fireplace installation Free standing structure weatherproof enclosure Minimum weatherproof overhang in front and sides M i n i m u m w e a t h e r p r o o f o v e r h a n g i n f r o n t a n d s...

Page 20: ...esthatarerequiredspecifically for your application or installation FIGURE 3 8 shows removal of the Heat Transfer Kit cover plates There are 2 square cover plates located on either side of the outer sh...

Page 21: ...using 1 heat transfer kit the vent termination must be on the opposite side of the heat transfer kit air chute See FIGURE 3 10 Corner installations have different minimum requirements to allow space...

Page 22: ...nimum clearance from a parallel adjacent sidewall to appliance sides is 6 152mm 4 1 3 Finishing Recommendations NOTE The surface area above the appliance may be affected by high temperatures emitted f...

Page 23: ...T FIREPLACES 59 1505mm 37 940mm 35 889mm TRIM 19mm 4 102mm 29 743mm 1 25mm COMBUSTIBLE FLOOR NON COMBUSTIBLE ZONE MANTEL PROJECTION 1 25mm UP FOR EVERY 1 25mm DEEPER COMBUSTIBLE MATERIAL 1 2 13mm Non...

Page 24: ...the nailing flanges from the sides of the fireplace Save screws 5 Install the bottom trim panel with the flange positioned as shown in FIGURE 4 3 Secure with 2 screws included in the fireplace compone...

Page 25: ...r the screen front until the notched tabs are firmly in position verifying the depth accommodates finish material To remove safety screen lift the screen up and out of slots 4 3 2 Overlap Fit Installa...

Page 26: ...over the control compartment as you see fit NOTE The position of the louver should match with the desired position of the notched tabs needed for your installation The louver in the first notch positi...

Page 27: ...iping system by closing its individual manual shut off valve A listed and Commonwealth of Massachusetts approved 1 2 13mm tee handle manual shut off valve and flexible gas connector are to be connecte...

Page 28: ...Feet Meters Flat to 6 12 1 0 0 30 Over 6 12 to 7 12 1 25 0 38 Over 7 12 to 8 12 1 5 0 46 Over 8 12 to 9 12 2 0 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1...

Page 29: ...12 30cm 9 23cm K Clearance to mechanical air supply inlet 6 1 83m 3 91cm above if within 10 3m horizontally Massachusetts 10 3m L Clearance above paved sidewalk or paved driveway located on public pro...

Page 30: ...educer when used in combination with an existing minimum 6 x 8 ID masonry or 7 ID Class A metal chimney See Section 7 7 on page 40 Refer to the vent manufacturer s installation manual for complete ins...

Page 31: ...er most ring knocked out will create the least amount of restriction Follow FIGURE 7 1 for restrictor plate installation before attaching venting or through the baffle restrictor if venting is already...

Page 32: ...gn the 2 slots on the vertical heat shield flanges with corresponding screw holes located in front of the flue outlet on the top of the fireplace 3 Secure the vertical vent heat shield to the fireplac...

Page 33: ...all venting installations Refer to Section 7 4 on page 32 IMPORTANT Horizontal vent sections require 6mm rise for every 12 305mm of travel 7 5 1 1 5 x 8 Vertical Terminations i Minimum Maximum Vertica...

Page 34: ...e 6mm rise for every 12 305mm of travel i Minimum 6 Vertical Rise Minimum Maximum Horizontal Termination 6 152mm minimum vertical rise 90 elbow 6 152mm minimum horizontal run 24 610mm maximum horizont...

Page 35: ...t be within the shaded area in FIGURE 7 5 25 7 6m maximum vertical rise 25 7 6m maximum horizontal run 50 15 2m of total length Maximum of 5 90 elbows For each additional 90 elbow used after the first...

Page 36: ...exible pipe may be used for approved venting configurations by vent manufacturers listed in section 7 1 APPROVED VENT SYSTEMS on page 30 7 5 2 1 4 x 6 5 8 Vertical Terminations i Minimum Maximum Verti...

Page 37: ...90 elbow for 4 x 6 5 8 pipe 24 610mm max 4 x 6 5 8 horizontal length termination cap ii Maximum Vertical and Maximum Horizontal Venting 24 610mm min 5 x 8 vertical length 4 x 6 5 8 reducer 23 7m max...

Page 38: ...4 610mm min 5 x 8 vertical length 4 x 6 5 8 reducer 23 7m max 4 x 6 5 8 vertical length 90 elbow for 4 x 6 5 8 pipe 25 7 6m max 4 x 6 5 8 horizontal length termination cap Maximum of 5 90 elbows For e...

Page 39: ...at least 1 4 6mm rise for every 12 305mm of travel IMPORTANT The vent heat shield assembly must be installed when incorporatingminimumhorizontalventingoffthetopoftheappliance IMPORTANT Careshouldbeta...

Page 40: ...installed when incorporatingminimumhorizontalventingoffthetopoftheappliance IMPORTANT Careshouldbetakenwheninstallingflexiblepipetoavoid a tight bend that may cause abrasion or damage to the flexible...

Page 41: ...e heat shields as necessary to accommodate wall thickness The sections must overlap a minimum of 1 1 2 38mm Secure to exterior wall with 4 screws not provided 7 8 2 Vent Assembly and Installation 1 Mo...

Page 42: ...task ATTENTION If converting to propane complete the conversion before installing any light kit components Follow instructions provided with the conversion kit sold separately NOTE To avoid damage and...

Page 43: ...o the 2 mounting pins at the back of the burner assembly 3 Position the holes in the bottom of SF36 2 and SF36 3 onto the corresponding mounting pins on the burner 4 Position the hole in the bottom of...

Page 44: ...e from firebox 7 Remove the burner heat shield There are 2 screws located at the back firebox wall 8 Remove light kit assembly 2 screws 9 Remove and save 10 screws securing control board to firebox fl...

Page 45: ...lectrical Specifications This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or t...

Page 46: ...all electric power to the appliance 10 Press the wireless remote POWER button 11 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technicia...

Page 47: ...the UP and DOWN arrows highlight the PILOT icon and press SELECT 3 Use the UP and DOWN arrows to turn the pilot on demand ON or OFF then press SELECT A single beep will be emitted from the control mo...

Page 48: ...into a standby mode if no buttons are pressed within 5 minutes Press the POWER button to reactivate the remote control to ON mode Active functions will be displayed once in ON mode POWER BUTTON MENU B...

Page 49: ...Appliance With the system in the ON position press the remote control POWER button to turn OFF the appliance Functions AUX1 AUX2 and Pilot on Demand can be accessed when the remote control is OFF Only...

Page 50: ...function 1 Press the MENU button to activate the menu 2 Using the UP and DOWN arrows highlight the THERMO icon and press SELECT 3 Use the UP and DOWN arrows to turn the THERMO ON or OFF then press SE...

Page 51: ...the UP and DOWN arrows highlight the AUX1 icon and press SELECT 3 Use the UP and DOWN arrows to adjust to desired light kit intensity The transmission indicator icon will flash and a single beep will...

Page 52: ...tween the minimum and maximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not o...

Page 53: ...llow flame but may produce soot on the glass Opening the air shutter will cause a short blue flame that may lift off the burner Slight adjustments to the venturi opening will create dramatic results A...

Page 54: ...Verify the baffle door restrictor is set into down position and not flipped up 1 Remove the safety barrier and glass frame assembly to access the baffle door restrictor adjustment handle 2 Loosen 2 t...

Page 55: ...atic in this manual to determine that all wiring connections are secure and correct Control module selector switch not set properly Verify the ON OFF REMOTE selector switch is ON mode or REMOTE mode G...

Page 56: ...peration is turned OFF Pilot and burner extinguish while in operation No propane in tank Check propane tank Refill if necessary Incorrect glass assembly installation Refer to section 8 1 GLASS FRAME A...

Page 57: ...vent system Check the vent pipes for leaks and the vent cap for debris Repair the vent pipes or remove debris from vent cap if necessary No reaction to command Battery back batteries or remote contro...

Page 58: ...to section 7 0 VENTING on page 30 Performed by Qualified Service Person Frequency Annually Action Examination of the vent system is required Inspect the condition of vent and vent terminal for sooting...

Page 59: ...the operation of the flame safety system Pilot or Flame rectification device Visually check pilot light when in operation Inspect and ensure the lighting of the main burner occurs within 4 seconds of...

Page 60: ...sion Kit Natural Gas DEX 191 NG Dexen PSE IPI Pilot Assembly 700 191 LCK SF36 D Dexen Conversion Kit Propane DEX 191 1 Propane Dexen PSE IPI Pilot Assembly 700 191 1 SF36 350 Burner Assembly DEX RC3 D...

Page 61: ...is warranty does not cover installation and operational related problems such as environmental conditions nearby trees buildings hilltops mountains inadequate venting or ventilation excessive offsets...

Page 62: ......

Reviews: