Page 8
(A) POSITION THE FIREPLACE.
1.
Determine the exact position of your
fireplace. If possible, place the fireplace in
such a manner that the piping will be placed
between two studs so additional framing is
not necessary. Determine the width, depth
and height of the (optional) hearth.
Refer to Figure 4 below for various
installation options.
Maintain proper clearance to combustible
requirements listed on page #3.
Maintain proper clearances of vent system on
the exterior when horizontally terminating as
outlined on page #5.
CAUTION: COLD AIR TRANSFER AREA. THE
SURROUNDING WOOD CHASE OF THE
OUTSIDE WALL MUST BE INSULATED TO
PREVENT COLD AIR FROM ENTERING THE
ROOM.
NOTE: Due to high temperatures, this
fireplace should be located out of traffic areas
and away from furniture and draperies.
Figure 4
2.
HORIZONTAL TERMINATIONS
Determine the height* & location of where the venting will exit on the exterior.
ATTENTION: #700 SERIES DV SYSTEMS: THE HEIGHT TO THE TOP OF THE FRAMED OPENING
MUST BE A MINIMUM OF 49 ½" ABOVE THE HEIGHT OF THE FLOOR OR OPTIONAL HEARTH.
*Important: This measurement is determined by the vertical height and horizontal length of
the venting application desired. The measurement is to the top of the opening. Please refer
to pages #3- #6 of this installation manual for requirements and restrictions