kozy heat Minneapolis MPS-30 Installation And Operation Manual Download Page 1

DIRECT VENT FIREPLACE INSERT 

www.kozyheat.com 

JANUARY 2011 
MPS-30-REV-05 

INSTALLATION AND OPERATION MANUAL 

WARNING 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT GLASS 

WILL CAUSE BURNS. 

  

DO NOT TOUCH 

GLASS UNTIL COOLED. 

  

NEVER 

ALLOW CHILDREN TO TOUCH GLASS. 

WARNING:   This product must be installed by a licensed plumber or gas fitter when installed in the  

 

            commonwealth of Massachusetts. 

DO N

OT  

DISCA

RD 

This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes.  
A manufactured home (USA only) or mobile home OEM installation must conform with the 

Manufactured Home Construction and Safety  

Standard, Title 24 CFR, Part 3280, 

or when such a standard is not applicable, the Standard for 

Manufactured  Home Installations, ANSI/NCSBCS A225.1, 

or Standard for 

Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4 

   

  

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other  

        appliance. 

  

 IF YOU SMELL GAS: 

   

  Do not light any appliance. 

    

  Do not touch any electrical switch: do not use any phone in your building. 

    

  Immediately call gas supplier from a neighbors phone.  Follow the gas supplier instructions. 

    

  If you cannot reach your gas supplier, call the fire department. 

    

  Installation and service must be performed by a qualified installer, service agency or the gas

 

supplier.

 

WARNING:  If the information in these instructions are not followed exactly, a fire or explosion may                       
 

          result, causing property damage, personal injury or loss of life. 

This appliance is only for use with the type (s) of gas indicated on the rating plate.  
A conversion kit is supplied with the appliance. 

Shown with optional brushed stainless convex screen front 

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE. 

  

CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.

 

Report No. 216-S-33-6.5 

Summary of Contents for Minneapolis MPS-30

Page 1: ...hicles and Mobile Housing CSA Z240 4 Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance IF YOU SMELL GAS Do not light any appliance Do no...

Page 2: ...on and reliability but customer safety as well We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong Dudley Hu...

Page 3: ...NSTRUCTIONS Conversion Kit Instructions 12 13 GLASS FRAME ASSEMBLY SCREEN FRONT Glass Frame Assembly Screen Front Removal Installation 14 INSTALLATION Approved Venting 14 Combustion Air Venting Option...

Page 4: ...keep toddlers young children and other at risk individuals out of the room and away from hot surfaces Clothing or other flammable material should not be place on or near the appliance Adequate access...

Page 5: ...ly Black firebox liner Black Glass Media Kit IPI control system with remote control Engineer designed burner system Automatic fan kit 1 110CFM Co linear vent system 3 combustion air 3 exhaust Innovati...

Page 6: ...8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inch 1 2 in...

Page 7: ...SPECIFICATIONS PARTS DIAGRAM PAGE 6 1 Fireplace insert 2 Air chute 3 Module panel assembly 4 Valve access panel 5 Control board assembly 6 Burner 7 Glass frame assembly 8 Firebox liner 9 Black glass...

Page 8: ...M CLEARANCES TO COMBUSTIBLES Y X Combustible Floor Hearth Protection 9 229mm 12 305mm 19 22 483mm 559mm 14 356mm 17 432mm 0mm 0 102mm 4 203mm 8 0 13mm 2 1 2 64mm 5 127mm X Y Floor Protector 3 76mm Com...

Page 9: ...a Kit JOR 057T Glass Frame Assembly OCK A53L I MPS PSE LP Conversion Kit 816 CL1 Co Linear Air Duct 700 208 Remote Control 700 GLT Glass Latch Tool Vent System Part 816 CL For use with minimum 6 x 8 I...

Page 10: ...eter Existing Chimney Height Minimum 10 ft 3 05m Maximum 35 ft 10 67m 1 Remove and discard existing chimney cap 2 Position one person at fireplace and another person at top of chimney Measure from fir...

Page 11: ...steners If necessary remove firebrick to obtain at least minimum opening requirements The fireplace flue damper can be fully blocked open or removed for installation of this gas fireplace insert Remov...

Page 12: ...th the requirements of the ANSI Z223 1 installation code NOTE A listed and Commonwealth of Massachusetts approved 12 13 mm manual shut off valve and flexible gas connector included are connected to th...

Page 13: ...e cap Replace with orifice cap included with kit making sure to tighten cap securely NAT GAS 42 orifice L P GAS 53 orifice GAS TYPE CONVERSION Press and hold Learn Button on Main Control Module for 20...

Page 14: ...nlet pressure Visually check pilot flame Flame should envelope top of flame sensor and extend onto burner far enough for prop er ignition To Adjust pilot Turn pilot adjustment screw clockwise to decre...

Page 15: ...th slots on insert set into position To remove Lift frame up and out of slots PAGE 14 Figure 14a INSTALLATION COMBUSTION AIR VENTING OPTIONS OPTION 1 FULL CONNECTION Combustion air intake pipe is run...

Page 16: ...sealant around inner edge at end of exhaust pipe without collar red marking and slide onto corresponding collar on termination cap collar with label Secure with 3 self tapping screws provided Apply a...

Page 17: ...en vent system OPTIONAL 816 CL kits Secure termination cap to existing chimney with 2 self tapping screws and anchor straps provided through pilot holes located at sides of termination cap 3 From insi...

Page 18: ...llar on air duct Slide combustion intake pipe over collar Secure with 3 self tapping screws provided To ensure an air tight seal apply additional sealant around joint 4 Slide insert into fireplace ope...

Page 19: ...ly WARNING Do not block pilot assembly with glass media A blocked pilot assembly may result in a delayed ignition ATTENTION Do not operate this fireplace without glass media installed Various colors a...

Page 20: ...S Figure 19a IMPORTANT THIS SYSTEM REQUIRES ELECTRICITY 110 V AND OR BATTERIES TO OPERATE USING BATTERY BACK UP WILL OPERATE BURNER ONLY FAN COMPONENTS WILL NOT FUNCTION ON BATTERY BACK UP POWER Light...

Page 21: ...LOW LIMIT SCREW STEP MOTOR WIRE HARNESS MAIN VALVE INTERNAL SOLENOID CONNECTION PILOT INTERNAL SOLENOID CONNECTION PILOT ADJUSTMENT SCREW INLET PRESSURE SCREW OUTLET MANIFOLD PRESSURE SCREW IPI GAS V...

Page 22: ...N OFF SWITCH LEARN BUTTON MAIN CONTROL MODULE VALVE STEP MOTOR TERMINAL COMMUNICATION LINK TO EXTENSION MODULE AC ADAPTOR CONNECTION EXTENSION MODULE COMMUNICATION LINK TO CONTROL MODULE POWER TO LIGH...

Page 23: ...CONTROL INFORMATION CHILD PROOF ICON LIGHT LEVEL FLAME HEIGHT FAN SPEED BATTERY LIFE ICON THERMOSTAT MODE ICON SET TEMPERATURE visible only in THERMO MODE MANUAL ON OFF ROOM TEMPERATURE CONTINUOUS PI...

Page 24: ...d may cause an explosion Disconnect 110V before servicing The IPI gas control system has the option of a continuous standing pilot feature This allows you to change from a spark to pilot system to a s...

Page 25: ...n on right side access panel A Velcro strip has been attached to help secure in place The Hand Held Remote operates on 2 1 5V AAA batteries We recommend always using ALKALINE batteries to extend batte...

Page 26: ...ain will turn fireplace OFF NOTE The MODE button operates in a series that will cycle from ON to THERMO to OFF FAN MODE This remote will operate the fan allowing for 6 different speed levels When the...

Page 27: ...ature The FLAME ON and THERMO icons will appear on the LCD screen By pressing UP or DOWN buttons a new set temperature may be attained SET Temperature will only appear when THERMOSTAT MODE is activate...

Page 28: ...P CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air WHAT TO DO IF YOU SME...

Page 29: ...not operate follow instructions TURNING OFF GAS TO FIREPLACE and call your service technician or the gas supplier ATTENTION This fireplace is equipped with an ignition device which automatically ligh...

Page 30: ...re Follow instructions below for proper testing procedures INLET PRESSURE TEST PRESSURE TESTING NOTE If inlet pressure reading is too high or too low contact the gas company Only a qualified gas servi...

Page 31: ...t flame is actually present when valve is turned OFF if yes replace valve Replace pilot assembly Replace module SENSOR SAFETY Protection for Flame Sensor Error Code Four beeps every two seconds Descri...

Page 32: ...OR YOUR INSTALLATION NATURAL GAS LP PROPANE GAS 1 16 2 mm OPEN 100 OPEN BURNER TUBE VENTURI ADJUSTMENT GUIDELINES VENTURI POSITION FLAME COLOR VENTURI ADJUSTMENT Closed too far Dark orange flame with...

Page 33: ...E PERSON MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING BEDDING MATERIALS ETC IT IS IMPERATIVE THAT CONTROL COMPARTMENTS BURNERS AND CIRCULATION AIR PASSAGEWAYS OF THE APP...

Page 34: ...ing for a beep from receiver when ON is pressed on hand held remote If you do not hear a beep ensure main control module has learned the hand held remote See above Ensure black lead from pilot assembl...

Page 35: ...m that in which the hand held remote was tested It may take up to 3 hours for the temperature inside a packaged transmitter and several minutes for an unpackaged transmitter to equalize with room temp...

Page 36: ...neapolis IPI Valve Natural 700 226 Flexible Gas Line Valve to Burner Connection 700 404 MPS 1 Minneapolis IPI Valve LP 700 242 Natural Gas Orifice 42 700 200 Pilot Assembly Natural Gas 700 253 LP Gas...

Page 37: ...PAGE 36 LIMITED WARRANTY...

Page 38: ...PAGE 37 LIFETIME WARRANTY...