Gas Requirements
This unit has been certified for use with both Natural Gas (NG) or Liquid Propane (LP). The
following is a chart for the minimum and maximum supply pressures.
Gas
Minimum Supply
Pressure
Normal Supply
Pressure
Maximum Supply
Pressure
Natural Gas
(NG)
5.0" W.C
7.0" W.C.
8.0" W.C
Propane (LP)
10.5" W.C.
11.5" W.C.
13.0" W.C.
The gas valve has it’s own internal regulator which reduces the pressure within the following
ranges: 0.9 to 3.5” W.C. for natural gas and 2.5 to 10.0” W.C. for propane.
The gas connection provided with this unit is a flexible connector and is easily accessible
through the rear, side and bottom of the stove or by opening the side door panel and reaching in
through the access hole. The gas line can also be rigid pipe, if so desired. To make the
installation easier, use the flexible connector and manual shutoff valves necessary, according to
the local building codes.
Pressure taps are provided for checking the inlet and outlet gas pressure. The taps are located
on the front of the valve body.
The appliance and it’s appliance main gas valve must be disconnected from the gas supply
piping system during any pressure testing of that system at test pressures in excess of ½ psi
(3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment
shutoff valve during any pressure testing of the gas supply piping system at test pressures
equal to or less than ½ psi (3.5 kPa).
Venting Requirements
This stove has been tested and certified with the following venting kits and their components.
Only the parts listed below can be used for the installation of this appliance.
Venting Kit #DV1-MVK1 –
venting installations under 15 ft. vertical rise
Venting Kit #DV1-MVK2
– venting installations over 15 ft. and under 30 ft. vertical rise.
Each of the above kits contains the following components:
One Vent Terminal Cap
•
•
•
•
•
One Terminal Adapter Box
Two 3” diameter 2 ply Aluminum flex pipes of suitable length
Four 3” Stainless Steel adjustable hose clamps, and sheet metal screws
High temperature sealant
Installers may be required to provide a Chimney Cover Plate for certain installations.
Venting terminals shall not be recessed into a wall or siding.