![KOREL M2OC-18HFN8-Q Service Manual Download Page 45](http://html1.mh-extra.com/html/korel/m2oc-18hfn8-q/m2oc-18hfn8-q_service-manual_1997705045.webp)
44
10.3.3.3 Voltage protection(ODU E5)
Voltage protection
Check the voltage of
outdoor unit power supply,
whether the voltage
between L(L1) and N (L2) is
about 220~240VAC
Check the power supply
Check whether the voltage
of IPM board P and N is
normal? DC277-356V for
18-27KBtu/h; DC277-410V
for 36-42KBtu/h
Replace bridge rectifiers,
and then check whether the
system can run normally
Replace IPM board, and
then check whether the
system can run normally
Replace outdoor main board
Yes
No
No
No
No
Yes
Trouble is solved
Yes
Yes
Summary of Contents for M2OC-18HFN8-Q
Page 8: ...7 5 Wiring diagram M2OC 18HFN8 Q M2OG 14HFN8 Q...
Page 9: ...8 M2OD 18HFN8 Q...
Page 11: ...10 M3OE 27HFN8 Q...
Page 12: ...11 M3OF 21HFN8 Q M3OF 27HFN8 Q M4OE 28HFN8 Q...
Page 13: ...12 M4OB 36HFN8 Q...
Page 14: ...13 M5OD 42HFN8 Q...