VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing  the

system to warm-up particularly in winter months.

2. Refer to the identification label for proper electrical voltage and current requirements.  Then

connect the power cord to a properly grounded and fused electrical supply.  Leave the electrical
power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4. Adjust thermostat to its maximum setting.  

5. If your unit is equipped with an on-off switch, move it to the on position.

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting.  The compressor should start.  On units equipped

with a short cycle protector, the compressor will have a delayed start of 6 minutes from the time
power is applied to the unit.  

9. Verify that the condenser blower or fan is running.  Note, on units equipped with a low ambient

kit, the start of the condenser fan or blower will be delayed until the system pressures rise.

10. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual

noise or vibration should be evident.  Both the evaporator and condenser fans or blowers should
be delivering air through their respective discharge ports.  The cool air should be discharged
should be less than 70°F when the room temperature is between 70 and 80°F.  

11. On units equipped with heaters, adjust both the cooling and heating thermostats to their

maximum settings.  Verify that the compressor and condenser fan or blower has stopped.  Verify
elevated discharge air temperature from the evaporator air discharge.

12. If your unit is equipped with an on-off switch, leave it in the on position.  Return the cooling

thermostat to its original setting.  If unit is equipped with a heater, return the heating thermostat
to its original position.

13. Turn off the electrical power source, and disconnect the air conditioner from the power source.

14. If any cover plug is removed to adjust the unit, make certain to put back in place to maintain the

integrity of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a 

performance test.

6

The air conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

Summary of Contents for TRIMLINE KA4C6NP47-1

Page 1: ...ON BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 6...

Page 2: ...n Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enclosures in...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...ements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent dam...

Page 5: ...ed through the condenser coil where it absorbs the heat and is then discharged to the environment The unit is equipped with a Bypass Thermostat to prevent the evaporator coil from freezing and elimina...

Page 6: ...delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and cond...

Page 7: ...M TAB by sliding the studs located on each side panel into the slots on the M TAB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the air conditioner side panel and...

Page 8: ...25 1200 2 Drawings and Dimensions NP47 SERIES Dimensions inches metric are for reference only and are subject to change FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air O...

Page 9: ...lower Assembly 6015 00 11 Filter 12251F Technical Data KA4C6NP47 1 6000 125 50 115 100 60 50 16 5 150 160 Switchable Switch is internally mounted for security Rating shown is for operation at maximum...

Page 10: ...ng Schematic SOLENOID VALVE GN S C R WE SUPPRESSOR O L CAP CAP 1 3 EVAP BLOWER MOTOR MOTOR BLOWER COND START RELAY S L 2 1 M CAP COMPR 6 8 RELAY T STAT 70 BU Y R T STAT 75 Y BU R BK BYPASS WD 872 KA4C...

Page 11: ...off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inle...

Page 12: ...e air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is...

Page 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: