background image

VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will
verify the shipping integrity of the system. Please follow the steps below prior to instal-
lation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum,

allowing  the system to warm-up particularly in winter months.

2. Refer to the identification label for proper electrical voltage and current requirements.

Then connect the power cord to a properly grounded and fused electrical supply.
Leave the electrical power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4. Adjust thermostat to its maximum setting.

5. If your unit is equipped with an on-off switch, move it to the on position.

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting. The compressor should start. On units

equipped with a short cycle protector, the compressor will have a delayed start of 6
minutes from the time power is applied to the unit.

9. Verify that the condenser blower or fan is running. Note, on units equipped with a low

ambient kit, the start of the condenser fan or blower will be delayed until the system
pressures rise.

10. Operate the air conditioner for approximately ten (10) minutes. During this period no

unusual noise or vibration should be evident. Both the evaporator and condenser fans
or blowers should be delivering air through their respective discharge ports. The cool
air should be discharged should be less than 70°F when the room temperature is
between 70 and 80°F.

11. On units equipped with heaters, adjust both the cooling and heating thermostats to

their maximum settings. Verify that the compressor and condenser fan or blower has
stopped. Verify elevated discharge air temperature from the evaporator air discharge.

12. If your unit is equipped with an on-off switch, leave it in the on position. Return the

cooling thermostat to its original setting. If unit is equipped with a heater, return the
heating thermostat to its original position.

13. Turn off the electrical power source, and disconnect the air conditioner from the power

source.

14. If any cover plug is removed to adjust the unit, make certain to put back in place to

maintain the integrity of the closed-loop airflow system.

NOTE: Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a 

performance test.

The Air Conditioner must be standing in its proper mounting position for a

minimum of five (5) minutes prior to testing. Failure to follow this procedure

will cause permanent damage to the compressor.

6

Summary of Contents for Traditional K2A4C10P47L

Page 1: ...IR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com Find a...

Page 2: ...page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to...

Page 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Page 6: ...delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and cond...

Page 7: ...stability and a tight seal High strength mounting screws are recommended Attach the brass drain pan fitting and drain hose supplied to the drain exit on the bottom or lower side panel of the Air Condi...

Page 8: ...ithin this area and equal or exceed size of cool air outlets FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out COOL AIR OUTLET TO ENCLOSURE Drawings and Dimensions P47...

Page 9: ...145 150 155 G G G KA3C8P _ _R56 8000 115 50 115 50 60 17 0 19 0 145 150 155 G G G K2A4C8P _ _L 8000 125 50 230 200 60 50 13 0 145 150 155 G G G K2A4C8P _ _L5 8000 115 50 230 50 12 5 145 150 155 G G G...

Page 10: ...29 6015 00 129 6015 00 130 6015 00 130 Filter 12251F 12251F 12251F 12251F 8 000 to 12 000 BTU H KA3C_P47R KA3C_P47R56 K2A3C_P47L K2A3C_P47L5 KA3C_P52R KA3C_P52R56 K2A3C_P52L K2A3C_P52L5 KA3C_P59R KA3C...

Page 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Page 12: ...valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refri...

Page 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Page 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: