VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air
Conditioners are designed to require only the routine cleaning of air filters to assure
unimpeded air flow through the condenser heat exchanger. It is not possible to
recommend specific filter cleaning intervals since the level and the nature of airborne
particulate matter differs widely with each installation. It is generally sufficient to remove
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters
appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended.
Appropriate disposable filters are available from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design
capacity. The first indication of excessively clogged air filters is usually a gradual
increase of temperature within the equipment cabinet. If operation is continued under
these conditions, the compressor will be shut off by the thermal overload device. The
compressor will restart when its external temperature drops below the protector threshold
setting and the compressor will continue to cycle on and off. Continued operation under
these conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate
necessary cleaning.

CAUTION

1) Lift the filter, using the attached tab, to clear the lower filter retainer. Pull filter

toward you and downward until the top of the filter clears the upper filter retainer.

2) After removal, the filters should be flushed under warm running water with

the clean side up, driving contaminants out the dirty side of the filter. If the
accumulated dirt is oily, washing in a detergent bath is recommended, followed
by a warm water rinse as above.

3) The filters may be sprayed with Kooltronic A-16 Filter Recoating Adhesive to

trap fine airborne contaminants, or they may simply be dried and reinstalled as
strainer type filters. Recoating is recommended for best results.

4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper

retainer, (b) press filter against the unit and (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the

filter removed. The condenser coil may become clogged with dust or

lint from the air entering the face. A clogged condenser coil is not

readily detected and will give the same reaction as a clogged filter. A

clean filter is the best protection.

11

Summary of Contents for Traditional K2A4C10P47L

Page 1: ...IR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com Find a...

Page 2: ...page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to...

Page 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Page 6: ...delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and cond...

Page 7: ...stability and a tight seal High strength mounting screws are recommended Attach the brass drain pan fitting and drain hose supplied to the drain exit on the bottom or lower side panel of the Air Condi...

Page 8: ...ithin this area and equal or exceed size of cool air outlets FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out COOL AIR OUTLET TO ENCLOSURE Drawings and Dimensions P47...

Page 9: ...145 150 155 G G G KA3C8P _ _R56 8000 115 50 115 50 60 17 0 19 0 145 150 155 G G G K2A4C8P _ _L 8000 125 50 230 200 60 50 13 0 145 150 155 G G G K2A4C8P _ _L5 8000 115 50 230 50 12 5 145 150 155 G G G...

Page 10: ...29 6015 00 129 6015 00 130 6015 00 130 Filter 12251F 12251F 12251F 12251F 8 000 to 12 000 BTU H KA3C_P47R KA3C_P47R56 K2A3C_P47L K2A3C_P47L5 KA3C_P52R KA3C_P52R56 K2A3C_P52L K2A3C_P52L5 KA3C_P59R KA3C...

Page 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Page 12: ...valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refri...

Page 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Page 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: