VI. Description

Standard KoolTray II

The KOOLTRONIC 

KoolTray II

delivers cooling air to hot spots by localizing fan placement to the heat generating

area(s).  With its 1¾-inch [44.5mm] single-U height it fits right under card racks or near heat-producing sources.
Standard units are available in 1, 2, or 3 row models. 19-inch [482.6mm] unit width is standard.

Smart KoolTray II

In addition to specific cooling fan placement, the 

Smart KoolTray II

provides two optional choices of component

protection. The 

X5 

option sends both a visual and external alarm in the event of fan failure or low fan speed. The

X7

option varies the fan speed as temperature decreases or increases relative to the set point and sends an alarm

for high temperature conditions. The 

X6

option combines both the X5 and X7 options.

Filtered KoolTray II

For environments which require filtration of the ambient or cabinet air, KOOLTRONIC’s 

Filtered KoolTray II

filters

the air from the bottom side of the tray. Other filter location options are available. Filtered versions are available on
both the 

Standard

and 

Smart KoolTray II.

Options for Smart Kooltray II

OPTIONS:

X5

X6

X7

Individual Fan Sensors

x

x

Variable Speed Fans

x

x

AC

x

x

x

DC

x

x

x

Alarm Types

Low Fan Speed/Fan Failure

x

x

High Temperature

x

x

The 

X5

option provides both a visual and external alarm for fan failure or low fan speed. The visual alarm is provided

by L.E.D.s corresponding to individual fans. The external alarm is provided by relay contact connection on the rear
mounted terminal block for a remote warning device.

For 

X7

option provides variable speed fan control based on temperature. High temperature alarm relay contacts are

provided by way of a rear mounted terminal block for a remote warning device.

The 

X6

option incorporates both the X5 and X7 options.

Isolated OR’d Alarm Outputs (Rear of Unit) - (X5 and X6 Options Only)

These optically isolated outputs provide both normally open (N.O.) and normally closed (N.C.) alarms permitting
connection to logic circuits or other loads with no electrical connection to the control circuit. 
The outputs are from a Dual-Pole MOS Relay, which are intended to drive heavy loads. These outputs have a
maximum on-state resistance of 50 Ohms, maximum sinking current is 100 mA, and a maximum of 230 VAC can
be applied to the alarm terminals. The outputs also trigger in the event of cooling system power failure. 

Note: At power-up, all outputs are held in the normal state for ten seconds.

Circuit

Above Trigger Speed Below Trigger Speed

Power Removed

1.

NC

Closed

Open

Open

2.

NO

Open

Closed

Closed

Alarm Logic Table 

Summary of Contents for Kooltray II Series

Page 1: ...0 FAX 609 466 1114 www kooltronic com 900 057 03 12 18 CDR 20111 CAUTION BEFORE INSTALLING AND USING THIS KOOLTRAY IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRAY II SERIES...

Page 2: ...ature Selection VII Drawings and Dimensions 5 VIII Specific Model Data 6 Technical Data Major Component Replacement IX Maintenance 7 X Packing Procedure for Warranty Return 7 XI Warranty 8 I Introduct...

Page 3: ...im III Product Handling I Do not attempt to operate your Kooltray until you read and thoroughly understand this Manual I Before operating this unit all electrical wiring must be checked to assure the...

Page 4: ...x x x DC x x x Alarm Types Low Fan Speed Fan Failure x x High Temperature x x The X5 option provides both a visual and external alarm for fan failure or low fan speed The visual alarm is provided by L...

Page 5: ...unted X7 Standard KoolTray power receptacle with temperature instead of power sensitive variable cord speed fans KOOLTRAY II MODEL NUMBER AND FEATURE SELECTION GUIDE 19 00 482 6 TYP 10 76 273 3 18 31...

Page 6: ...120 20 9 115V 60 Hz operation Major Component Replacements 6 VIII Specific Model Data Fan Voltage 115VAC 230VAC 12VDC 24VDC 48VDC Option X1 0265 09 0265 10 0265 08 0265 15 0265 13 X5 0265 12 0265 12...

Page 7: ...with each installation It is generally sufficient to remove and wash the reusable aluminum mesh air filter when the outer surface of these filters appears covered with a thin layer of dust or lint Fil...

Page 8: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a...

Reviews: