V. Principles of Operation

The main component of the heat exchangers is counterflow aluminum element through
which heat transfer occurs.
Ambient blower draws ambient air from the bottom inlet through an aluminum mesh air
filter, through the element and exhaust it through a discharge grill.
Cabinet blower draws cabinet air from the top inlet through the element and exhaust it
through the bottom discharge into the cabinet.

VI. Specific Model Data

Blower

Ambient Air

with

Heat Load

Heat

Exchanger

Cooled Air

Cabinet

Blower

Heated Air

Ambient

Air

In an Air-to-Air Heat
Exchanger, heat from air
surrounding the compo-
nents is removed by a
specially designed heat
transfer element before
being routed back into the
enclosure.

Major Component Replacements

KNHX38

KNHX47

KNHX59

KNHX38E

KNHX47E

KNHX59E

Condenser Blower Assembly

6015-00-129

6015-00-129

8060-00-11

Condenser Blower Capacitor

0452-06

0452-06

0452-03

Condenser Blower Blower Motor

0261-08

0261-08

0261-149

Evaporator Blower Assembly

6015-00-129

6015-00-129

604559-00-36

Evaporator Blower Capacitor

0452-06

0452-06

0452-03

Evaporator Blower Blower Motor

0261-08

0261-08

0261-149

Filter

10871F

10871F

10871F

Above parts are for 115V units.  For 230V, consult factory.

Technical Data

**

KNHX38

115

3.00

340

160

131

44

88

115

KNHX38E

115

3.00

340

160

131

44

88

115

K2NHX38

230

2.10

440

160

131

46

92

115

K2NHX38E

230

2.10

440

160

131

46

92

115

KNHX47

115

3.00

340

160

131

54

108

135

KNHX47E

115

3.00

340

160

131

54

108

135

K2NHX47

230

2.10

440

160

131

56

112

135

K2NHX47E

230

2.10

440

160

131

56

112

135

KNHX59

115

4.50

400

160

131

65

130

170

KNHX59E

115

4.50

400

160

131

65

130

170

K2NHX59

230

3.30

660

160

131

65

130

170

K2NHX59E

230

3.30

660

160

131

65

130

170

Maximum Allowable

Performance

Approx.

Power

Temperature °F

Watts/°F

Weight

Model

Volts

Amps

Watts

Enclosure Ambient

Air In

Air Out

(lbs.)

**60 Hz. operation. For 50 Hz. operation, consult Kooltronic.

Summary of Contents for KNHX38 Series

Page 1: ...ING THIS HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 07 12 18 CDR 20111 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Page 2: ...c TrimLine Heat Exchangers are designed for indoor applications with ambient temperatures from 50 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general information for pro...

Page 3: ...er stand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO MAX CABINET VOLTS FREQ PH AMPS TEM...

Page 4: ...0 00 11 Condenser Blower Capacitor 0452 06 0452 06 0452 03 Condenser Blower Blower Motor 0261 08 0261 08 0261 149 Evaporator Blower Assembly 6015 00 129 6015 00 129 604559 00 36 Evaporator Blower Capacitor 0452 06 0452 06 0452 03 Evaporator Blower Blower Motor 0261 08 0261 08 0261 149 Filter 10871F 10871F 10871F Above parts are for 115V units For 230V consult factory Technical Data KNHX38 115 3 00...

Page 5: ...tuds installed on the heat exchanger side panels into the inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the heat exchanger to the cabinet wall All holes in the heat exchanger flange must be used to maintain the NEMA 4 rating 7 Remove the heat exchanger from the M TAB and drill 218 dia mounting holes in the cabinet Do not attempt to drill mounting holes in the ...

Page 6: ...d air filter is usually a gradual increase of temperature within the equipment cabinet Continued operation under these conditions will cause damage shorten blower motor life and void the warranty 11 2 53 16 TYP POWER CORD FILTER M TAB 18 K 171 16 WARM AIR RETURN FROM ENCLOSURE WARM AMBIENT AIR OUTLETS COOL AIR OUTLET TO ENCLOSURE WARM AIR RETURN FROM ENCLOSURE FILTERED AMBIENT AIR INLET COOL AIR O...

Page 7: ...e tab slide the filter into the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clog...

Page 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Reviews: