IX. Specific Model Data

Mounting

CAUTION

The Kooltronic HL Series Air Conditioners K_A6C6HL40LV have been engineered to be installed easily.  Prior to
mounting, refer to page 13 for the mounting plan showing dimensions and locations of mounting holes and
cutouts. Prior to cutting or drilling, make sure that cutouts and mounting holes do not interfere with components
inside the cabinet. To avoid damaging your air conditioner, please read the following information before installation:

1. It is recommended that a lift truck be used for installation.

2. These externally mounted air conditioners utilize a gasket to ensure a proper seal. This seal is necessary to 

maintain the integrity of the closed-loop system and the enclosure NEMA 4 or NEMA 4X Rating. 

3. Secure the air conditioner to the enclosure using (18) 

1/4

-20 x 1-

1/4

inch stainless steel bolts (supplied).

4. Using a clamp, attach plastic drain hose to the drain tubing near the bottom of the air conditioner.

5. The customer must connect the Purge/Pressurized System control line to the Swagelok fitting (B400-1-OR, 

1/4 inch NPT). The customer has a choice of two connection fittings on the unit. One is for internal connection,
and the other is for external connection (see illustration below). The unused fitting must be sealed with the 
provided cap. NOTE: Some earlier models may only have external connection.

6. The customer could use a Tee fitting, or any type fitting to connect the Purge/Pressurized System control 

line to the air conditioner.

The air conditioner must be mounted in accordance with the mounting instructions in order

to maintain the integrity of the panel enclosure.

12

CUSTOMER’S

PRESSURIZED

ENCLOSURE

KOOLTRONIC

HL SERIES

AIR CONDITIONER

PURGE/PRESSURIZATION

SYSTEM 

(CUSTOMER SUPPLIED)

TEE (CUSTOMER SUPPLIED)

SWAGELOK

TUBING FITTING

B400-1-OR,

1/4" NPT

INTERNAL

CONNECTION*

EXTERNAL

CONNECTION*

*NOTE: THE UNUSED CONNECTION MUST BE SEALED WITH PROVIDED CAP

PRESSURIZED AIR 

(CUSTOMER SUPPLIED)

RELIEF VALVE

(CUSTOMER SUPPLIED)

AUXILIARY SOLENOID

VALVE AND ORIFICE

IF NEEDED

(CUSTOMER SUPPLIED)

S

Summary of Contents for K2A6C6HL40LV

Page 1: ...BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 74 1 18 CDR 20053 HAZARDOUS LOCATION SERIES K...

Page 2: ...oting 17 18 XII Warranty 19 NOTE Wiring Schematics are available on the specific model page of the Kooltronic website I Introduction Kooltronic Hazardous Location Air Conditioners HL Series are design...

Page 3: ...nimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the...

Page 4: ...R USE WITH CLASS I DIVISION 1 GROUPS A B C AND D HAZARDOUS LOCATIONS TYPE X PURGE AND CLASS I DIVISION 2 GROUPS A B C AND D TYPE Z PURGE ENCLOSURES WHEN INSTALLED ON AN APPROVED PRESSURIZED ENCLOSURE...

Page 5: ...of combustible materials or unless all devices within have been de energized WARNING HIGH TEMPERATURE INTERNAL PARTS This Air Conditioner must not be opened unless the area atmosphere is known to be b...

Page 6: ...urized customer enclosure must be connected to the Purge Pressurized Control System by gas air lines in parallel The Kooltronic HL Series Air Conditioner must be powered from the pressurized customer...

Page 7: ...ter consists of a heater a heat control thermostat and a heater limiter The heater control thermostat is a bimetal disk with a fixed set point of 60 F When the entering evaporator air temperature rise...

Page 8: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Page 9: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 10: ...charge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F It is normal for the condenser blower to cycle on off during this period 9 Reset the th...

Page 11: ...to the enclosure The contact closure may be used with their control system having a timer function and output signal The output signal would energize a solenoid valve equipped with a fixed orifice or...

Page 12: ...r the bottom of the air conditioner 5 The customer must connect the Purge Pressurized System control line to the Swagelok fitting B400 1 OR 1 4 inch NPT The customer has a choice of two connection fit...

Page 13: ...10 30 261 6 10 30 261 6 1 11 28 1 33 8 5 TYP 1 2 4 70 119 4 68 17 3 23 5 8 23 5 8 23 5 8 4 67 118 5 6 00 152 4 6 00 152 4 6 00 152 4 6 00 152 4 6 00 152 4 4 67 118 5 MOUNTING PLAN Dimensions inches me...

Page 14: ...TEMPERATURE ALARM TERMINAL BLOCK THERMOSTAT ON OFF SWITCH POWER CORD PRESSURE COMPENSATION TERMINAL BLOCK 3 8 OD DRAIN PURGE PRESSURE FITTING 1 4 NPT 3 8 OD DRAIN 1 2 3 3 4 K_A6C6HL40LV Dimensions inc...

Page 15: ...ass I Zone 2 Groups IIA IIB plus hydrogen and IIC Hazardous Locations when used with an approved Type Z Purge System on the electrical enclosure Temperature Classification is T 4 275 F 135 C Maintains...

Page 16: ...ed under warm running water with clean side up If the accumulated dirt is oily washing in a detergent bath is recommended followed by a warm water wash as above After filter removal the exposed conden...

Page 17: ...ent controller or enclosure see below Removing Air Conditioner from Pressurized Enclosure Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONE...

Page 18: ...ondensate Eliminate the frequency of door openings draining and loss of A C sensible cooling performance Unit overcooling Failed Thermostat Check Thermostat wire connections Evaporator Blower Condense...

Page 19: ...was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit...

Reviews: