VIII. Maintenance

The RP55 is designed to require only the routine cleaning of air filters to assure unimpeded airflow through
the condenser heat exchanger. It is not possible to recommend specific filter cleaning intervals since the
level and the nature of airborne particulate matter differs widely with each installation. It is generally
sufficient to remove and wash the reusable aluminum mesh air filters when the outer surfaces of these filters
appear covered with a thin layer of dust or lint. Filter recoating adhesive, 

(Part No. A-16)

, available from

Kooltronic, is recommended. Replacement aluminum mesh filters are also available from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design capacity. The first
indication of excessively clogged air filters is usually a gradual increase of temperature within the equipment
cabinet. If operation is continued under these conditions, the compressor will be shut off by the thermal
overload device. The compressor will restart when its external temperature drops below the protector
threshold setting and the compressor will continue to cycle on and off. Continued operation under these
conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning.

CAUTION

1) Loosen the screw on the bottom of the filter holder.

2) Push the filter holder forward and move it down.

3) Remove the filter from the filter holder.

4) After removal, the filters should be flushed under warm running water with the clean side up,

driving contaminants out the dirty side of the filter. If the accumulated dirt is oily, washing in a
detergent bath is recommended, followed by a warm water rinse as above.

5) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

to trap fine airborne

contaminants, or they may simply be dried and reinstalled as strainer type filters. 

Recoating is

recommended for best results.

6) Reinstall the filter: Insert the filter inside the filter holder, push the filter holder forward, move it up

into place and replace the screw on the bottom of the filter holder.

Do not operate the air conditioner for extended periods of time with the

filter removed. The condenser coil may become clogged with dust or

lint from the air entering the face. A clogged condenser coil is not

readily detected and will give the same reaction as a clogged filter. A

clean filter is the best protection.

Summary of Contents for Advantage RP55 Series

Page 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 38 2 19 CDR 20131 ADVANT...

Page 2: ...tion Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Page 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Page 5: ...hen passed through the condenser coil where it absorbs the heat and is then discharged to the environment The unit is equipped with a Bypass Thermostat to prevent the evaporator coil from freezing and...

Page 6: ...r respective discharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F 10 Turn off the electrical power and disconnect the air conditioner fro...

Page 7: ...e front panel on the hooks of the M TAB Using the two hooks on each side of the M TAB as a guide be sure that the air conditioner is absolutely parallel to the M TAB We recommend using a lift truck fo...

Page 8: ...1 25 31 7 0 74 18 7 19 25 488 9 1 00 31 44 798 5 10 00 1 36 34 5 18 00 457 2 25 4 53 35 1355 0 20 64 524 2 7 31 185 6 TYP LEFT FRONT RIGHT REAR BOTTOM TOP 254 0 10 00 254 0 0 69 17 5 6 00 15 2 21 99...

Page 9: ...P55R Part Part Number Compressor 0665 78 Compressor Capacitor 0452 61 Condenser Blower Motor 0261 138 Condenser Blower Capacitor 0452 44 Evaporator Blower Motor 0261 288 Evaporator Blower Capacitor 04...

Page 10: ...OTOR CAP BK WE CRANKCASE HEATER PRESSURE SWITCH N O COOLING EFFECT DETECTOR TERMINAL BLOCK TO CUSTOMER ALARM SYSTEM RELAY 1 R CONTROL Y B T STAT HEATER HEATER B C T STAT CUT OUT THERMAL TRANSFORMER DI...

Page 11: ...operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to fa...

Page 12: ...ss valve fails it is strongly recommended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect ref...

Page 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: