background image

11

* Rating shown is for operation at maximum ambient temperature. 

Major Component Replacements

KA4C2DSP23L

K2A4C2DSP23L

KNA4C2DSP23L

K2NA4C2DSP23L

Part

Part Number

Part Number

Part Number

Part Number

Compressor

0665-123

0665-151

0665-123

0665-151

Compressor Capacitor

0452-88

0452-87

0452-88

0452-87

Condenser Coil

0667-49

0667-49

0667-49

0667-49

Condenser Impeller

0194-121

0194-122

0194-121

0194-122

Condenser Capacitor

0452-76

0452-64

0452-76

0452-64

Evaporator Coil

0667-28

0667-28

0667-28

0667-28

Evaporator Fan

0265-03

0265-03

0265-03

0265-03

Thermostat

0750-136

0750-137

0750-136

0750-137

Thermostat Probe

0750-136-01

0750-136-01

0750-136-01

0750-136-01

Filter Drier

0668-03

0668-03

0668-03

0668-03

Drain Tube

0265-38-0500

0265-38-0500

0265-38-0500

0265-38-0500

Filter (Optional)

6814F

6814F

6814F

6814F

Heater (Optional)

0718-38

0718-40

0718-38

0718-40

Technical Data

KA4C2DSP23L

2000

2373

122/-20

115

60

5.03

15

K2A4C2DSP23L

2000

2360

122/-20

230

60

2.87

15

K2A4C2DSP23L

2000

2170

122/-20

230

50

2.3

15

KNA4C2DSP23L

2000

2373

122/-20

115

60

5.03

15

K2NA4C2DSP23L

2000

2360

122/-20

230

60

2.87

15

K2NA4C2DSP23L

2000

2170

122/-20

230

50

2.3

15

Ambient

Approximate

BTU/H

BTU/H

Temp. °F

Running

Weight

Model

Capacity

95°F/95°F

Max./Min.

Volts

Hz

Amps

(lbs.)

Standard Features

Built-in Condensate Evaporator
CFC-Free Refrigerant
Closed-Loop Cooling
Compact Design/Slim Mounting Footprints
Compressor Short Cycle Protector
Condenser Impeller Cycling Control
Epoxy-Coated Evaporator and Condenser Coils
Galvanized Steel U90 Exterior Shell (NEMA 3R)
NEMA 12 & 3R Rated (UL50)
Programmable Temperature Alarm (Not available with Heater Option)
Programmable Thermostat
UL/CUL Listed 

Accessories and Options

Enclosure Heater
Filter (P/N 6814F)
Filter Recoating Adhesive
304 Stainless Steel Shell (NEMA 4 & 4X)
Heavy-duty Steel Shell
Lead-Lag Controller

Remote Monitoring
Remote Thermostat Relay

Summary of Contents for ACCESS Series

Page 1: ...E READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 105 5 21 CDR 20322 Find additional information...

Page 2: ...tronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes...

Page 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Page 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit FILTER P N FUS...

Page 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Page 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Page 7: ...enser blower to cycle on off during this period 8 Turn off the electrical power source and disconnect the air conditioner from the power source 9 If any cover plug is removed to adjust the unit make c...

Page 8: ...URE PANEL 15 49 393 4 TYP 7 50 190 5 56 14 2 TYP 21 72 551 6 TYP 5 59 141 9 2 PLACES 135 TYP 4 03 102 3 1 25 31 7 1 69 42 9 0 11 45 290 8 7 38 187 4 1 51 38 3 6 21 157 7 49 12 4 TYP 7 99 202 9 TYP 11...

Page 9: ...GURATION INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING REAR PANEL L BRACKETS 2 1 KA4C2DSP23L K2A4C2DSP23L KNA4C2DSP23L K2NA4C2DSP23L INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING FRONT...

Page 10: ...OPTION R 11 2 8 38 9 5 26 6 6 1 37 34 7 R 19 4 7 11 80 299 7 20 75 527 1 7 48 190 0 1 03 26 2 70 17 8 CONDENSER AIR OUTLET 2 1 115 VOLT MODEL 230 VOLT MODEL DIGITAL THERMOSTAT EVAPORATOR AIR INLET NOT...

Page 11: ...8 0718 40 0718 38 0718 40 Technical Data KA4C2DSP23L 2000 2373 122 20 115 60 5 03 15 K2A4C2DSP23L 2000 2360 122 20 230 60 2 87 15 K2A4C2DSP23L 2000 2170 122 20 230 50 2 3 15 KNA4C2DSP23L 2000 2373 122...

Page 12: ...ff Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet...

Page 13: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Page 14: ...mostat improperly set Low Temperature Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Uni...

Page 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...