BAKL6C502AA.doc
KONVEKTA AG
Edition: 12.07.2001
Page: 7/13
2. Determined use
The
KONVEKTA
air conditioner represents an air conditioning system that works with the ozone
friendly refrigerant R 134a and which creates a pleasant and individually adjustable room tempera-
ture by means of forced convection. The determined use includes also the observance of the Oper-
ating instruction and the proof of regular inspections as well.
3. Working with air conditioning unit
•
ACTIVATING CONDITIONS:
Control system does only work if ignition/D + and release of switch S362 are applicable. If one of
the 3 signals is interrupted, control system starts to close all outlets.
•
SELF CONTROL:
If control system on 24VDC is connected, self control is started in order to execute a trouble check
of the whole system.
•
Short circuit of the digital outlets
•
Re-registration from compressor and return air flap
•
Sensor data
•
Internal system
Setpoint room temperature:
If automatic control system of the a/c unit is switched on, control system starts to calculate a com-
fortable room temperature measured on basis of the outside temperature.
Outside temperature:
Setpoint room temperature:
-30°C up to 25°C
Between approx. 22°C and 24°C
25°C up to 30°C
approx. 3K below outside temperature
30°C up to 70°C
approx. 27°C