BAKL6C502AA.doc
KONVEKTA AG
Edition: 12.07.2001
Page: 10/13
5. Operator Controls
Risk of accident!
−
Priority must be given to the traffic.
−
Do only operate your air conditioner if the traffic situation does allow it.
−
Please make sure that all operation and indicating elements can be recognized and read prop-
erly.
−
Protect the displays and all indicating instruments against sun rays and other optical faults.
−
Take into consideration that the keys at the operation panel are not designed for extreme de-
mands.
−
An excessive or quick pressing of the keys / potentiometers for temperature adjustment does not
accelerate the cooling process but leads possibly to a damage on the operation panel and spoils
the total functioning of your air conditioner.
5.1. Operation panel / function of the keys
(BBZW0014)
(BBZW0015)
S362
H218
S363
S411
a/c switch
signal lamp
switch Reheat
Smog switch
disturbance
REHEAT:
Humidity Extraction
While activating switch „Reheat (S363)„, compressor starts to work for 20 minutes, which let
temperature in channel go down. Then heating valve is opened until setpoint temperature in
the channel is reached.
SMOG/RETURN AIR
If smog switch (S411) is activated, return air-, /mixed air-/ fresh air flap changes to position
return air, even if air flap position is e.g. adjusted to fresh air position.
Note:
After a while switch has to be readjusted to position mixed - or fresh air.