Troubleshooting

 

 

Problem 

Possible Cause 

Action To Take 

POWER button was not been 
pushed or been pushed too short. 

Press the POWER button and hold more 
than 4 seconds. 

UPS not on, LCD not light 

PCB failure 

Replace the PCB, call for service 

Power cord loose 

Replace the power cord 

AC fuse burn out 

Replace the AC fuse 

Line voltage too high, too low or 
black out 

normal condition 

UPS always at battery mode 

PCB failure 

Replace the PCB, call for service 

Buzzer continuous beeping 

Overload 

Remove the nonessential loads 

UPS does not provide expected 
run time, low battery warning is 
sounded prematurely. 

Battery is weak due to wear or 
successive mains outages 

Allow UPS to recharge battery for a 
minimum of 8 hours. If up sounds low 
battery warning prematurely, when retested, 
battery should be replaced. 

 

Specifications 

 

Type 

CMP-UPS500 

CMP-UPS650 

CMP-UPS800 

CMP-UPS1000 

CMP-UPS1200 

 

Capacity 

500VA/300W 

650VA/390W 

800VA/480W 

1000VA/600W 

1200VA/720W 

Voltage 

165VAC-275VAC 

Input 

Frequency 

50Hz 

Voltage 

220V ± 10% 

Output 

Frequency 

50Hz ± 0.5 

Type 

Sealed, maintenance-free lead acid 

Capacity 

1X12V 7Ah 

1X12V 9Ah 

2X12V 7Ah 

Backup Time 
(half load) 

Over 8 Minutes 

Battery 

Typical 
Recharge Time 

8-hour 

LCD indicators 

Status 

NORMAL, FAULT, BATTERY, CHARGE, OVERLOAD 

Audible Alarm 

Battery Mode 

Beeps every four seconds. Beeps every second if approaches final discharge 

Power 
Maragement 
Software 

UPSilon2000 

Option 

Overload 

Automatic cut off output and beep last for 30 Seconds 

Battery Low 
Voltage 

Automatic cut off output 

Protection 

Short Circuit 

Automatic cut off output and beep last for 30 Seconds 

Temperature 

0 ~ 40°C 

Humidity 

10%RH~90%RH 

Operating 
Environment 

Audible Noise 

≤ 45dB(A) 

Size (mm) 

330 × 85 × 155 

300 × 120 × 195 

Physical 

Net Weight (Kg)  6.5Kg 

13.2Kg 

 

Performance 

 
Uninterruptible Power 

Summary of Contents for CMP Series

Page 1: ......

Page 2: ...y test mode The buzzer emits alarm every four seconds 6 POWER SWITCH Power on off Battery test and buzzer on off 7 OUTPUT SOCKET Connect with load equipment 8 OUTPUT PHONE JACK Connect to the Tel Fax Modem by another phone line 9 INPUT PHONE JACK Insert the phone line into the jack 10 INPUT POWER CORD Connect to the AC Power 11 FUSE SET Built in fuse avoid damaged by short circuit or overload 12 R...

Page 3: ...Back Elevation Digital Display ...

Page 4: ...ould be replaced Specifications Type CMP UPS500 CMP UPS650 CMP UPS800 CMP UPS1000 CMP UPS1200 Capacity 500VA 300W 650VA 390W 800VA 480W 1000VA 600W 1200VA 720W Voltage 165VAC 275VAC Input Frequency 50Hz Voltage 220V 10 Output Frequency 50Hz 0 5 Type Sealed maintenance free lead acid Capacity 1X12V 7Ah 1X12V 9Ah 2X12V 7Ah Backup Time half load Over 8 Minutes Battery Typical Recharge Time 8 hour LCD...

Page 5: ...ed limits in the Specifications Table Connect to Utility Connect the AC input power connector to utility power to power up the UPS Charge the battery The battery in the UPS will lose some charge in shipping and storage It will recharge completely after approximately 8 hours of normal operation Do not expect full battery runtime during this initial recharge period Connect the loads Plug the loads i...

Page 6: ...onnel knowledgeable of batteries and their precautions Keep unauthorized persons away 2 Charge the UPS s battery every 3 months during extended storage 3 Disconnect the power during extended storage to avoid overcharge of the battery 4 Avoid overload or short circuit though the UPS have built in overload and short circuit protecting function Accessories inside packing CMP UPS500 3A 250V fuse IPC T...

Page 7: ...USV Bedienungsanleitung DIGITALANZEIGE LANGES BACK UP AVR SOFTWARE TEL MODEM ANSCHLUSS ÜBERSPANNUNGSSCHUTZ ...

Page 8: ...ie Testmodus Alle 4 Sekunden ertönt ein Alarmsignal Buzzer 6 POWERSCHALTER Spannung ein aus Akkutest und Buzzer ein aus 7 AUSGANGSBUCHSE Verbraucheranschluss USV Ausgang 8 AUSGANG TELEFONBUCHSE Mit anderem Telefonkabel an Tel Fax Modem anschließen 9 EINGANG TELEFONBUCHSE Das Telefonkabel in die Buchse stecken 10 EINGANG NETZKABEL Mit einer Steckdose verbinden 11 SICHERUNG Eingebaute Sicherung um S...

Page 9: ...Ansicht Rückseite DIGITALANZEIGE ...

Page 10: ...enn die USV nach wiederholtem Test zu zeitig vor schwacher Batterie warnt sollte der Akku gewechselt werden SPEZIFIKATIONEN Typ CMP UPS500 CMP UPS650 CMP UPS800 CMP UPS1000 CMP UPS1200 Kapazität 500VA 300W 650VA 390W 800VA 480W 1000VA 600W 1200VA 720W Spannung 165VAC 275VAC Eingang Frequenz 50Hz Spannung 220V 10 Ausgang Frequenz 50Hz 0 5 Typ wartungsfreier Bleigel Akku Kapazität 1X12V 7Ah 1X12V 9A...

Page 11: ...USV nicht bei einer Temperatur und Luftfeuchtigkeit die außerhalb der spezifizierten Grenzen liegt Siehe Tabelle Anschluss an das Stromnetz Um die USV in Betrieb zu nehmen verbinden Sie das Netzkabel mit dem Stromnetz Laden des Akkus Der Akku der USV verliert während der Lieferung und Lagerung einen Teil der Ladung Sie wird innerhalb von 8 Stunden vollständig während des Normalbetriebs aufgeladen ...

Page 12: ...hängig von der Anzahl der Entladungen und der Temperatur Der Wechsel des Akkus sollte nur von einem Techniker vorgenommen werden Halten Sie unautorisierte Personen fern 2 Laden Sie den USV Akku alle 3 Monate bei längerer Lagerung auf 3 Trennen Sie das Gerät bei längeren Lagerzeiten vom Strom um eine Überladung der Batterie zu vermeiden 4 Vermeiden Sie Überladung und Kurzschlüsse auch wenn die USV ...

Reviews: