Multi Indicator

KN-2000W SERIES

I  N  S  T  R  U  C  T  I  O  N      M  A  N  U  A  L

1

2

3

4

6

5

10

90

Min. 116

92

+0.6

  0

Min. 52

96

48

108

91

44.8

W DIN W96×H48mm

KN-2 Multi Indicator

0

100-240VAC 50 to 60Hz

1

24VDC

0

No option

1

Transmission output (4-20mA)

※1

4

RS485 communication output

5

Transmission output (4-20mA)  

+ RS485 communication output

0

No alarm output

2

Alarm output: 2

4

Alarm output: 4

KN-2

0

0

0 W

IN-P

aMA2

S

MODE

MODE

UNIT

?C

OFF

)00

?F

0

?C

)000

?F

S

S

S

S

S

S

S

MODE

dUNT

?/O

MODE

L-RG

0$00

MODE

H-RG

2)00

MODE

1

2

3

dP

)0

MODE

L-SC

00)0

MODE

H-SC

10)0

MODE

3

3

3

3

3

3

3

4

4

4

4

4

4

4

 KN-20

W

 KN-24

W

 KN-22

W

Power supply

Option output

Alarm output

Size

Item

 

Ordering Information

Thank you very much for selecting KONICS products.

For your safety, please read the following before using.

 Safety Considerations

The above specifications are subject to change without notice.

 Connections

 Unit Description

1. Display part(red) 

● Run mode: Displays current measurement value

.

● Parameter set mode: Displays parameter and SV

.

2. Unit indicator:

 Displays the set unit.

3. Alarm output indicator

: Turns ON when the alarm is ON.

4. 

 key

: Used to enter parameter set mode, move to parameters, save SV and return to 

  RUN mode.

5.  ,  ,   key

: Used to change parameter SV.

6. D.IN3

 

: Press the   and   keys for 3 sec at the same time, it operates the set function 

  (alarm clear, display hold, zero-point adjustment) at [

DI-K

] at program mode. 

 Dimensions

(unit: mm)

● 

Panel cut-out

Series

KN-2000W 

Power

supply

AC voltage

100-240VAC  50 to 60Hz 

DC voltage

24VDC

Allowable voltage range 90 to 110% of rated voltage
Power 

consumption

AC voltage

Max. 8VA 

DC voltage

Max. 3W 

Display method

4½-digit, 7-segment LED (selectable red, green, yellow) method

Character size

W10×H17mm

Input type 

RTD

JPt100Ω, DPt100Ω, DPt50Ω, Cu50Ω, Cu100Ω (5 types)

Thermocouple K, J, E, T, R, B, S, N, C (W5), L, U, PLII (12 types)
Analog

●Voltage: ±1.0000V, ±50.00mV, ±200.0mV, -1.000-10.000V (4 types)

●Current: 4.00-20.00mA, 0.00-20.00mA (2 types)

Digital input

●Contact input: max. 2kΩ in ON,Max. 90kΩ in OFF

●Non-contact input: residual voltage max. 1.0V in ON, 

                                

 

leakage current max. 0.03mA in OFF

●Outflow current: approx. 0.2mA

Sub

output

Alarm output

●2-point: relay contact capacity 250VAC

 3A 1c

●4-point: relay contact capacity 250VAC

 1A 1a

Transmission 

output

ISOLATED DC4-20mA (PV transmission) load resistance max. 600Ω

Com. output RS485 (Modbus RTU)

Display accuracy

±0.2% F.S. ±1-digit (25±5

)

±0.3% F.S. ±1-digit (-10 to 20

, 30 to 50

)

In case of thermocouple and below -100°C input, [±0.4% F.S.]±1-digit

TC-T, TC-U is min. ±2.0

Setting method

Set by front keys or RS485 communication

Alarm output hysteresis 

Set ON/OFF interval (1 to 999-digit)

Sampling cycle

Analog input: 100ms, temperature sensor input: 250ms

Dielectric voltage

2000VAC 50/60Hz for 1 min (between input terminal and power terminal)

Vibration

0.75 mm amplitude at frequency of 5 to 55Hz (for 1 min) in each X, Y, Z 

direction for 2 hours

Relay

life 

cycle

2-point

Mechanical: min. 10,000,000, 

Electrical: min. 100,000 (250VAC 3A resistance load)

4-point

Mechanical: min. 20,000,000, 

Electrical: min. 500,000 (250VAC 1A resistance load)

Insulation resistance

Over 100MΩ (at 500VDC megger)

Noise immunity

±2kV the square wave noise (pulse width 1

) by noise simulator

Memory retention

Approx. 10 years (non-volatile semiconductor memory type)

Environ

-ment

Ambient temp. -10 to 50

, storage: -20 to 60

Ambient humi. 35 to 85%RH, storage: 35 to 85%RH

Approval
Weight

※1

Approx. 332g (approx. 200g)

 

Specifications

1: The weight includes packaging. The weight in parenthesis is for unit only.

Environment resistance is rated at no freezing or condensation. 

 

Communication

 

Monitoring Mode

■ 

Communication set [Program mode: 

ADDR

BAUD

]

You can set communication address [ 

ADD R

] and communication speed [ 

BA UD

] for 

RS485 communication.

■ 

Communication write enable/disable [Program mode: 

COmW

]

You can set to enable [ 

EnA

] or disable [ 

DIsA

] or writing parameter setting by RS485 

communication.

Refer to communication manual for RS485 communication. 

Visit our web site (www.konics.com) to download communication manual and software 

[Integrated device management program: DAQMaster].

■ 

Communication manual

■ Communication specifications

Item

Specifications

Com. method RS485 2-wire half duplex
Com. 

speed(BPS)

19200, 9600, 4800, 2400, 

1200

Converter

Converter built in RS232

Max. 

connections 32 units
Com. 

distance

Max. 1200m (within 700m 

recommended)

Protocol

Modbus 1.1 RTU

Parity

None

Stop Bit 

1-bit

Data length

8-bit

Input type

Parameter Input range(

)

Input range(

)

Thermo

-couple

K(CA)

TC-K

-200.0    to  1350.0

-328  to  2462

J(IC)

TC-J

-200.0  to  800.0

-328.0  to  1472.0

E(CR) 

TC-E

-200.0    to  800.0

-328.0  to  1472.0

T(CC)

TC-T

-200.0    to  400.0

-328.0  to  752.0

R(PR)

TC-R

0.0    to  1750.0

32  to  3182

B(PR)*

TC-B

400.0    to  1800.0

752  to  3272

S(PR)*

TC-S

0.0    to  1750.0

32  to  3182

N(NN)*

TC-N

-200.0    to  1300.0

-328  to  2372

C(W5)*

TC-C

0    to  2300

32  to  4172

L(IC)*

TC-L

-200.0   to  900.0

-328.0  to  1652.0

U(CC)*

TC-U

-200.0   to  400.0

-328.0  to  752.0

Platinel II*

TC-P

0.0   to  1390.0

32  to  2534

RTD

Cu50Ω*

Cu50

-200.0   to  200.0

-328.0  to  392.0

Cu100Ω*

Cu10

-200.0   to  200.0

-328.0  to  392.0

JPt100Ω

JPt1

-200.0   to  600.0

-328.0  to  1112.0

DPt50Ω

DPt5

-200.0   to  600.0

-328.0  to  1112.0

DPt100Ω

DPt1

-200.0   to  850.0

-328.0  to  1530.0

Analog

Current

0.00 - 20.00mA

aMA1

 19999 to 19999

(display range is variable 

depending on decimal point position)

4.00 - 20.00mA

aMA2

Voltage

-50.00 - 50.00mV

aMV1

-200.0 - 200.0mV

aMV2

-1.0000 - 1.0000V

A-V1

-1.000 - 10.000V

A-V2

Above input types which have the * mark are not displayed. 

To display the above input types, supply the power with pressing the 

 key.

 Input Type and Range

1: 

S

:Press any key among the 

1

3

4

2: 

1

: Moves digits  /  

4

3

: Changes SV.

3:   Press  the 

MODE

 key after checking/changing SV in each parameter.  

The value flashes twice and is saved. It moves to next parameter.

After entering setting group, press the 

MODE

 key for 3 sec or there is 

no additional key operation in 30 sec, it returns to RUN mode. 

:  This parameter may or may not appear, depending on the 

other parameter set or model type.

AL1

09(9

AL2

09(9

AL3

00)1

AL4

00)1

hPEK

----

lPEK

----

MODE

S

S

S

S

S

S

MODE

MODE

MODE

MODE

MODE

MODE

Alarm 1 

value

Press 

MODE

 key.

Alarm 2 

value

Alarm 3 

value

Alarm 4 

value

High peak 

value

Low peak 

value

※1

2

3

 RUN mode

Displays high/low peak value.

High/Low peak value is available only to check and initialize 

it. (Refer to ‘  High/Low peak monitoring’ for initialization.)

Initial high/low peak is saved after 2 sec from supplying the 

power.  

Displayed only for alarm output models.

Set each alarm value; [ 

AL-1

 to  

AL-4

] in program mode.

• Setting range

: Temperature sensor input → within temperature range

  Analog input → 

L-SC

 to  

H-SC

 

When alarm operation [ 

AL-1

 to  

AL-4

] in program mode 

is no alarm [ 

AT)_

] or sensor break alarm [ 

SBa_

], these 

parameters are not displayed. 

For model with 2 alarm output (KN-22

W), 

AL3

AL4 

are 

not displayed.

 

Program Mode

Press 

MODE

 key

for 3 sec

Input type

Temperature

unit

Front display

unit

Low limit

input value

High limit

input value

Decimal 

point

Low limit 

scale value

High limit 

scale value

Displayed only when selecting 

temperature sensor input type.

Displayed only when selecting analog input type.

Select front display unit. 
Set low limit of input range.

• 

Setting range: within analog input type range

Set high limit of input range.

• 

Setting range: within analog input type range

Select decimal point position of display scale value.
Set low limit scale value.   

• Setting range: -19999 to 19999

Set high limit scale value.   

• Setting range: -19999 to 19999

1. In case of using this unit with machinery(E.g.: nuclear power control, medical 

equipment, ship, vehicle, train, airplane, combustion apparatus, safety device, 

crime/disaster prevention equipment, etc) which may cause damages to 

human life or property, it is required to install fail-safe device. 

Failure to follow this instruction may result in fire, 

human injury or damage to property. 

2. Install this unit on a panel. 

Failure to follow this instruction may result in electric shock. 

3. Do not connect, repair, or inspect this unit when power is ON.

Failure to follow this instruction may result in electric shock. 

4. Do not disassemble the case. Please contact us if it is required. 

Failure to follow this instruction may result in electric shock or fire. 

5. Wire properly after checking terminal numbers. 

Failure to follow this instruction may result in fire. 

1. This unit shall not be used outdoors.

Failure to follow this instruction may result in shortening the life cycle of the product 

or electric shock. 

2. Please observe the rated specifications.

Failure to follow this instruction may result in shortening the life cycle of the product 

or fire. 

3. In cleaning this unit, do not use water or organic solvent. And use dry cloth. 

Failure to follow this instruction may result in electric shock or fire. 

4. Do not use this unit where there are flammable or explosive gas, humidity, 

direct ray of the sun, radiant heat, vibration and impact etc. 

Failure to follow this instruction may result in fire or explosion. 

5. Do not inflow dust or wire dregs into the unit. 

Failure to follow this instruction may result in fire or malfunction. 

6. Wire it properly after checking terminal numbers when connecting power 

cable and measuring input.

Failure to follow this instruction may result in fire or explosion. 

Warning

Please keep these instructions and review them before using this unit.

Please observe the cautions that follow;

Warning

 

Serious injury may result if instructions are not followed.

Caution

 

Product may be damaged, or injury may result if instructions are not followed.

The following is an explanation of the symbols used in the operation manual.

   

     Caution:

 Injury or danger may occur under special conditions.

Caution

Select input type. (Refer to ‘ Input Type and Range’.)

10P

0P

S

S

S

S

S

S

S

S

EX.I0

SP

MODE

AL-1

MODE

AL-2

MODE

lOUT

00)0

MODE

AL-3

MODE

hOUT

10)0

MODE

AL-4

MODE

A-HY

001

MODE

3

3

4

4

4mA output 

scale value

20mA output 

scale value

Input and 

transmission 

output 

extension

AL1 mode

AL2 mode

AL3 mode

AL4 mode

AL output 

hysteresis

Set output scale value for 4mA. 

 Setting range:  Temperature sensor input 

 within temperature range,  

Analog input 

 

L-SC

 to 

H-SC

Set output scale value for 20mA.

 Setting range:  Temperature sensor input 

 within temperature range,  

Analog input 

 

L-SC

 to 

H-SC

Displayed only for transmission output model. 

Displayed only when selecting analog input type.

Select extension range of 4-20mA input and transmission output. 

Displayed only for alarm output models.

S

AT!A

AT@A

SBa_

AT)_

AT!A

AT!B

AT!C

AT!D

MODE

MODE

MODE

MODE

MODE

AL-1

AL-2

AL-3

AL-4

<Alarm operation> <Alarm option>

Next parameter

Set AL1 to 

AL4 alarm 

operation 

and option

SV changing method of 

AL-2

 to  

AL-4

 is same as 

AL-1

’s.

For model with 2 alarm output

 (KN-22

W), 

AL3

AL4 

are not displayed.

No alarm [ 

AT)_

], sensor break alarm [ 

SBa_

] do not have alarm option.

Set alarm value [ 

AL1

 to  

AL4

] in monitoring mode. 

1(2K

LOC1

DIsA

OFF

ZERO

ZERO

@4K

$8K

!2K

LOC2

AlRE

AlRE

S

S

S

S

S

S

S

S

S

S

S

S

InSF

LIN

ROOT

SQAR

TUF

MODE

IN-B

0000

MODE

MAvF

04

MODE

COmW

EnA

LOCK

OFF

ADDR

01

BAUD

(6K

BURN

ON

CLOR

RED

GRN

YELO

R--G

G--R

DI-T

HOLD

DI-K

HOLD

C-AL

RRRR

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

Input special

 function

Input

correction

Digital filter

Digital input 

terminal

Digital input 

key

Display color

Alarm 

display color

Sensor 

break

alarm

output

Com.

address

Com.

write

Lock

Displayed only when selecting analog input type.

Select input special function.

Set input correction value.   

• Setting range: -999 to 999

Set the number of moving average digital filters. 

• Setting range: 01 to 16

Select digital input function by front keys. 

Press the 

4

3

 keys for 3 sec at the same time and it executes the selected function.

For the model without alarm output (KN-20

W), 

AlRE

is not displayed.

Select digital input function by no. 6 and 7. 

For the model without alarm output (KN-20

W), 

AlRE 

is not displayed.

Select display part color for RUN mode and error

.    

Refer to 

 Display color

.

Select display part color for alarm.   

Refer to

 ‘

 Display color

.

Displayed only for alarm output models. 

Displayed only for transmission output models.

Select output status when sensor disconnection.

Displayed only for RS485 communication output model. 

Set communication address.   

 Setting range: 01 to 99

Select communication speed (baud rate).

Select enable/disable to communication write. 

 (

EnA

: enable to write,  

DIsA

: disable to write)

Select lock function.

Com.

speed

Set alarm output hysteresis. 

 Setting range: 001 to 999

When alarm operation [ 

AL-1

 to  

AL-4

] in program mode is no alarm  

 [ 

AT)_

] or sensor break alarm [ 

SBa_

], this parameter is not displayed. 

AT!A

AT!A

AT@A

AT@A

46

+0.6   0

Integrated device management program, 

DAQMaster, is able to set and monitor parameters. It 

is available only for RS485 communication models.

■ 

Software [Integrated device management 

    program: DAQMaster]

Item

Minimum requirements

System

IBM PC compatible computer with Intel 

Pentium 

 or above

Operating 

system

Microsoft Windows 98/NT/XP/Vista/7/8/10

Memory

256MB or more

Hard disk More than 1GB of free hard disk space
VGA

1024×768 or higher resolution display

Others

RS-232 serial port (9-pin), USB port

1: 

S

:Press any key among the 

1

3

4

2: 

1

: Moves digits  /  

4

3

: Changes SV.

3:   Press  the 

MODE

 key after checking/changing SV in each parameter.  

The value flashes twice and is saved. It moves to next parameter.

After entering setting group, press the 

MODE

 key for 3 sec or there is 

no additional key operation in 30 sec, it returns to RUN mode. 

:  This parameter may or may not appear, depending on the 

other parameter set or model type.

 RUN mode

DRW170687AB

1: For transmission output(4-20mA), select one between transmission alarm output 2 or 

transmission alarm output 4.

F.G.

RTD/TC/mV/±1V 

-1~+10V

0~20mA

transmitter

Reviews: