Digital Thyristor Unit
E-21
A. Recorder
B. Indicator
C. Converter
D. Controller
E. Thyristor
unit
F. Temp.
sensor
G. Pressure
transmitter
H. Temp.
transmitter
I. Thermometer
J. Pressure
gauge
K. Accessories
DPU
DPUS
■
Address mapping table
Holding resisters [1-phase]
Address
Item
Factor
40001(0000)
Reference value
* 0.1(1 to 1000)
40002(0001)
Start Time
0 to 99
40003(0002)
Start limit
* 0.1(1 to 1000)
40004(0003)
Soft Start Time
0 to 99
40005(0004)
Output high-limit limit
* 0.1(1 to 1100)
40006(0005)
Output low-limit limit
* 0.1(1 to 1000)
40007(0006)
Remote Sp1 value
* 0.1(1 to 1000)
40008(0007)
Remote Sp2 value
* 0.1(1 to 1000)
40009(0008)
Remote Sp3 value
* 0.1(1 to 1000)
40010(0009)
Remote Sp4 value
* 0.1(1 to 1000)
40011(000A)
Remote Sp5 value
* 0.1(1 to 1000)
40012(000B)
Remote Sp6 value
* 0.1(1 to 1000)
40013(000C)
Slow up time
0 to 99
40014(000D)
Slow stop time
0 to 99
40015(000E)
CL value
* 0.1(1 to 2000)
40016(000F)
OC value
* 0.1(1 to 1100)
40017(0010)
OC time
0 to 99
40018(0011)
OV value
* 0.1(1 to 1100)
40019(0012)
OV time
0 to 99
40020(0013)
Load detector alarm value
* 0.1(1 to 2000)
40021(0014)
Display content selection
0 to 3
40022(0015)
Bar display mode
0 to 3
40023(0016)
Control integer KP value
0 to 9999
40024(0017)
Control integer KI value
* 0.1(1 to 999.9)
40025(0018)
Output control mode
0 to 6
40026(0019)
Event input 1 mode
0 to 4
40027(001A)
Event input 2 mode
0 to 4
40028(001B)
Event input 3 mode
0 to 4
40029(001C)
Auto ref input selector
0 to 3
40030(001D)
Load resistance display method
0 to 1
40031(001E)
Operation status
0×0000
Bit0...
Bit1...
Bit2...
Bit3...
Bit4...
Bit5...
Bit6...
Bit7...
Bit8...
Bit9...
Bit10...
Bit11...
Bit12...
Bit13...
Fault
I-OC
Over current
Over volt
Over temp
Fuse cut
Phase loss
Load open
Over SCR
Over Freq
Run/Stop
Auto/Manual
EMS Power
Not Load
40032(001F)
Output slope(%)
0 to 2
40033(0020)
Output for 0% input(%)
0 to 2
40034(0021)
Input correction
0 to 2
40035(0022)
Input slope correction
0 to 2
40036(0023)
Overcurrent alarm output
0 to 2
40037(0024)
Current alarm output
0 to 2
40038(0025)
Overvoltage alarm output
0 to 2
40039(0026)
Fuse break alarm output
0 to 2
40040(0027)
Frequency error alarm output
0 to 2
40041(0028)
Heatsink overheat alarm output
0 to 2
40042(0029)
Element error alarm output
0 to 2
40044(002A)
Heater break alarm output
0 to 2