KONICS DPU Series Manual Download Page 11

DPU 

Series

E-12

 SLOW UP / SLOW DOWN [ 

UP-T

UP-T

DN-T

DN-T

 ]  

It is same purpose as soft start function. Soft start starts 
only one time at 

fi

 rst but slow up/slow down function start 

during operation. 

Regardless of control method setting (phase control or 
cycle control), it operates as phase control. 

When it reaches to the target output value, slow up/slow 
down functions end. 

 

Set range : 0 to 999 sec. (0 sec.: not using this function)

 

A : SOFT START function ends

 

B : SLOW UP function ends

 

C : SLOW DOWN function ends

 Output high/low limit [ 

H-OL

H-OL

L-OL

L-OL

 DI(Digital Input) 

 RESET

 

RST

This function is to limit output range to protect load.

 

Set range : 0 to 110%

  (Output low limit value < Output high limit value)

After selecting RESET function, turn digital input 
ON(close) and open, this unit resets and re-starts.

Below functions are available by terminal input.

Digital input has 

fi

 ve terminals; AUTO/MANUAL terminal, 

RUN/STOP terminal, and DI-1 to 3 terminals. 

Select the function for each input terminal of DI-1 to 3. 

 

AUTO/MANUAL selection digital input

 [no. 7 and 11 terminals]

 

RUN/STOP switching digital input

 [no. 6 and 11 terminal]

 

DI-1 to DI-3(no. 1 to 3 of digital input ) terminal 

 [no. 8, 9, 10 and 11(COM) terminal]

Select AUTO(close)/MANUAL(open) input by terminal 
input.

AUTO mode controls output according to control input 
as analog input (voltage, current) or ON/OFF input 
(including SSR pulse input). 

MANUAL mode controls according to control input as 
the inside VR adjustment or an outside VR adjustment. 

When selecting AUTO (close), the front AUTO lamp 
turns ON or selecting MANUAL(open), the front AUTO 
lamp turns OFF. 

Select RUN(close)/STOP(open) operation status by 
terminal input. 

RUN mode operates as the set contents by control 
input. STOP mode is standby status. 

When selecting RUN(close), the front RUN lamp turns 
ON or selecting STOP(open), the front RUN lamp turns 
OFF.

Select the each function for each digital input at 
parameters [ 

DI-1

DI-2

DI-3

].

When setting ON(close) to DI input, the front EVT lamp 
turns ON or setting OFF(open), the front EVT lamp 
turns OFF.

As below, there are 6 functions to select.

 

SP-M 

is available only in

 D1-1

.

 Current limit [ 

C-LM

C-LM

 

]     

It operates when normal, static voltage, static current 
mode of phase control.

When using the load which has high inrush current, it 
restrains the current to protect thyristor. 

Especially, in case of voltage feedback, only voltage 
current, it may over the rated current of thyristor because 
current 

fl

 ows by resistance value of the load. To prevent 

over the rated current, limit the current. 

 

Set range : 0 to 110% of rated current

Output(%)

SOFT START set time

Time

SLOW UP set time

SLOW DOWN set time

Overcurrent

alarm

Output high-limit: 

H-OL

Output low-limit : 

L-OL

Control input signal(%)

Output(%)

Current

alarm

Output

current

(%)

Current limit set position 

(0 to 110%)

Current limit 

set point

Over current 

alarm point

Time

Select 

function

No. 8 and 11 terminal 

ON (CLOSE)

Executes 

selected 

function

No. 9 and 11 terminal 

ON (CLOSE)

No. 10 and 11 terminal 

ON (CLOSE)

Summary of Contents for DPU Series

Page 1: ...control part separately Applicable load all loads such as super kanthal platinum molybdenum carbon halogen lamp chrome nickel etc Number of phases Item Rated current capacity Size Power supply Option DPU Digital Power Controller Unit R RS485 communication D Remote Display Unit A Remote Display Unit RS485 communication N No option 1 110 V 2 220 V 3 380 V 4 440 V 1 1 phase 3 3 phase 1 phase 3 phase ...

Page 2: ... Display method Display value and SV display 7Segment 4digit Status display 4LED Display value percentage display 11LED Bar Display value and SV display 7Segment 4digit Status display 6LED Display value percentage display 11LED Bar Output accuracy Static voltage feedback control Within 3 F S of rated voltage within variable 10 F S of rated voltage Static current feedback control Within 3 F S of ra...

Page 3: ...y power for effective noise DI input switch should be for low current and ON resistance should be max 20 Ω including cable resistance DI input terminals are COM DI 1 to 3 RUN AUTO For remote display unit option model use connection cable as our standard cable When connecting it operates as MANUAL When connecting it operates AUTO R S U F G R S U F G R S U F G R S U F G Inside VR 10kΩ 3 level slide ...

Page 4: ...nductive noise it is recommended to use shielded cable at high frequency power for effective noise DI input switch should be for low current and ON resistance should be max 20Ω including cable resistance DI input terminals are COM DI 1 to 3 RUN AUTO For remote display unit option model use connection cable as our standard cable When connecting it operates as MANUAL When connecting it operates AUTO...

Page 5: ...A 25 40 50 70 25A 40A 50A are not attached a fan B Size DPU1 B 80 100 120 150 180 200 80 135 154 209 5 110 147 170 60 Fixed 4 M5 82 P1 97 40 150 P2 260 30 3 120 Fixed 4 M5 127 P1 140 50 150 P2 280 30 3 120 135 222 241 5 121 5 151 174 Dimensions ...

Page 6: ...ze DPU1 C 250 350 D Size DPU1 D 400 500 600 In case of remote display unit RS485 communication option It is recommended for remote panel cable to use max 5 m to prevent noise Check the length when ordering it 250 278 160 494 156 195 Fixed 4 M6 261 P1 278 40 200 P2 280 90 212 418 345 38 4 213 160 365 132 163 Fixed 4 M6 193 P1 213 50 200 P2 179 338 300 38 4 Panel cut out 53 5 0 5 0 100 5 0 5 0 55 10...

Page 7: ...P2 63 5 26 306 160 235 6 138 200 239 199 183 160 364 176 217 278 Fixed 4 M6 195 P1 213 200 P2 40 280 365 43 1 Panel cut out 53 5 0 5 0 100 5 0 5 0 In case of remote display unit RS485 communication option It is recommended for remote panel cable to use max 5 m to prevent noise Check the length when ordering it 55 102 ...

Page 8: ...ure transmitter H Temp transmitter I Thermometer J Pressure gauge K Accessories DPU DPUS C Size DPU3 C 250 350 D Size DPU3 D 400 500 600 Fixed 4 M6 261 P1 278 200 P2 280 40 140 5 92 5 450 370 40 125 5 160 489 173 5 227 5 311 Fixed 4 M8 405 P1 427 330 P2 453 66 5 160 746 204 5 275 5 404 5 204 5 167 167 528 463 32 5 ...

Page 9: ...w Ex At pure resistance load in feedback control when input is 4 20mA and rating is 220V or 50A Input 4mA 8mA 12mA 16mA 20mA MV 0 25 50 75 100 Display voltage 0 0V 70V 155 5V 209 7V 220 0V Input 4mA 8mA 12mA 16mA 20mA MV 0 25 50 75 100 Display voltage static voltage control 0 0 55 0 110 0 165 0 220 0 Display voltage static current control 0 0 12 5 25 0 37 5 50 0 Type Description MAN INT Adjust out...

Page 10: ...hod setting phase control or cycle control it operates as phase control Set range for start limit 0 to 110 of output Set range for start limit time 0 to 100 sec 0 sec not using this function This function is to adjust manually inside or outside VR output value ratio for control input When AUTO operation and output slope manual adjustment A GA is set as ON SLOP is not able to set It displays slope ...

Page 11: ...e controls according to control input as the inside VR adjustment or an outside VR adjustment When selecting AUTO close the front AUTO lamp turns ON or selecting MANUAL open the front AUTO lamp turns OFF Select RUN close STOP open operation status by terminal input RUN mode operates as the set contents by control input STOP mode is standby status When selecting RUN close the front RUN lamp turns O...

Page 12: ...trol or overshoot or hunting After selecting HOLD function and digital input is ON close output and display value of this unit is hold it operates hold when digital input maintains ON close status Proportional constant set P It compensates error from the target value proportionally If proportional constant value is small response is fast and it may cause overshoot or hunting If proportional consta...

Page 13: ... Current alarm CAL Continues operation Automatically cleared within the set range Heater break alarm HBK Bar Graph display value content selection BAR BAR Load resistance display method DRES DRES You can select display value content for the bar graph Selectable display value content load voltage U V V W W U load current LA U LA V LA W power KW control input REF This function is for display load re...

Page 14: ...ntage Displays frequency of power IN 10 0 LD V 22 0 LD A 5 0 KW 1 00 RES 50 FREQ 6 00 P P P P P P Input value Load voltage Load current Load power Load resistance Power frequency V V A A 1 For ON OFF input or SSR pulse input it displays 0 or 100 Set range Within 0 0 to 100 0 Monitors measured voltage at load within the rated voltage range Monitors measured current at load within the rated current ...

Page 15: ...only for static voltage static current static power in phase control Set range 0 to 100 Displayed only when DI 1 of ST 1 is set SP M Set slow up time Set range 0 to 999sec Not displayed when C MD mode is set as cycle control Set slow down time Set range 0 to 999sec Not displayed when C MD mode is set as cycle control OP H OL 50 ST T C LM S LM SP1 S LT SP2 A GA SP3 SLOP SP4 B UP SP5 UP T SP6 DN T P...

Page 16: ...NA Enables to write DISA Disables to write OP ST 1 DRES 4 20 IN P P F LD C MD ADDR DI 1 BAUD DI 2 COMW DI 3 LOCK IN B SPAN DISP BAR Operating Mode Setting Mode 1 Control input type Control method DI 1 function DI 3 function DI 2 function Input correction Input slope correction Display value content Bar content Load resistance display method Full load auto recognition Com address Com speed Com writ...

Page 17: ... A FUSE Operating Mode Setting Mode 2 Setting Mode 1 Overcurrent alarm value Element error alarm CH Heat sink overheating alarm CH Fuse break alarm CH Overvoltage alarm CH Overvoltage delay time Overvoltage alarm value Current alarm CH Overcurrent alarm CH Overcurrent delay time Heater break alarm value Heater break alarm CH AL2 AL1 NON AL2 AL1 NON AL2 AL1 NON 1 Displays setting mode 2 RUN mode Pr...

Page 18: ...default 38400 Data length 8Bit Stop Bit 1Bit Parity Even Max connections 32 units Protocol MODBUS 1 1 RTU Function code 3 0 03 Read holding resisters Master Slave 0 01 0 03 0 00 0 00 0 00 0 16 Add Com mand Start add Number of data CRC 16 High Low High Low High Low Slave Master 0 01 0 83 Address Response command Exception code CRC 16 Slave Master 0 01 0 03 0 10 0 03 0 E8 0 03 0 E8 Add Response comm...

Page 19: ...73 Reserved Reserved 30117 0074 Reserved Reserved 30118 0075 Coil start address 0 30119 0076 Coil quantity 0 30120 0077 Input start address 0 30121 0078 Input quantity 0 30122 0079 Holding reg start address 0 30123 007A Holding reg quantity 32 30124 007B Input reg start address 0 30125 007C Input reg quantity 5 Input resisters 3 phase Address Item Factor 30001 0000 Load voltage between U V line di...

Page 20: ...3 Load detector alarm value 0 1 1 to 2000 40021 0014 Display content selection 0 to 3 40022 0015 Bar display mode 0 to 3 40023 0016 Control integer KP value 0 to 9999 40024 0017 Control integer KI value 0 1 1 to 999 9 40025 0018 Output control mode 0 to 6 40026 0019 Event input 1 mode 0 to 4 40027 001A Event input 2 mode 0 to 4 40028 001B Event input 3 mode 0 to 4 40029 001C Auto ref input selecto...

Page 21: ...BAR 4 LA V 5 LA W 6 KW 7 REF 40023 0016 Proportional value P 1 to 2000 1 40024 0017 Integral value I 0 1 to 999 9 0 1 40025 0018 Control method C MD 1 to 6 1 1 F CY 2 ONOF 3 PA 4 V FB 5 C FB 6 W FB 40026 0019 Digital input 1 DI 1 0 to 5 1 0 SP M 1 SP 1 2 SP 2 3 SP 3 4 RST 5 HOLD 40027 001A Digital input 2 DI 2 1 to 5 1 1 SP 1 2 SP 2 3 SP 3 4 RST 40028 001B Digital input 3 DI 3 5 HOLD 40029 001C Co...

Reviews: