5.2.2. Outdoor compensated ventilation (OCV)
Setting winter and summer outdoor temperature limits for reducing ventilation intensity. When the outdoor tempera-
ture is within the range of “Winter compensation start” and “Summer compensation start”, the unit operates in a selected
ventilation mode.
Enable
Winter compensation stop
Winter compensation start
Summer compensation start
Summer compensation stop
OUTDOOR COMPENSATED VENTILATION (OCV)
-40.0
°C
°C
0.0
20.0
°C
°C
50.0
5.2.3. Minimum temperature control (MTC)
Setting a minimum desired supply air temperature.
Enable
Setpoint
MIN. TEMPERATURE CONTROL (MTC)
18.0
°C
5.2.4. Summer night cooling (SNC)
Setting two indoor temperatures for the function to start running and stop.
Enable
Stop when indoor
SUMMER NIGHT COOLING (SNC)
Start when indoor
25.0
°C
25.0
°C
5.2.5. Override function (OVR)
Selecting conditions for activating the function (all the time, only when the unit is running, only when the unit is stopped)
and specifying ventilation mode for the unit to run when the function starts. If the “Standby” ventilation mode is selected,
the unit will be stopped.