13
UAB KOMFOVENT we reserve the right to make changes without prior notice
C6M2-19-03
Wall mounted
units:
Domekt R 300 V - 400 V - 450 V
Domekt CF 400 V
30 cm
30 cm
30 cm
70 cm
Flat units are attached
to the ceiling:
Domekt R 250 F - 400 F - 700 F
Domekt CF 150 F - 250 F - 500 F - 700 F
10 cm
5 cm
5 cm
30 cm
30 cm
5 cm
5 cm
Suspended
ceilings
Service opening
Flat units that can be suspended on
the wall:
Domekt R 250 F - 400 F - 700 F
30 cm
30 cm
30 cm
120 cm
Fig. 6.
Minimum space for maintenance
•
It is forbidden to drill or screw into the casing of the unit, in places not provided for purpose, as there
is a danger of damaging cables or tubes inside the housing.
•
Domekt CF 150 F, CF 250 F, CF 500 F and CF 700 F flat units must be fitted with a 15 mm slope on the
drainage side to facilitate the discharge of condensate from the unit.
•
Only these units can be mounted on the ceiling or wall and only in such positions as specified in
Fig. 6.
3.2.2. Humidity in the installation room
If the unit is installed in a room with high humidity, condensation may occur on the walls of the unit in cold weather
conditions (see Fig. 7). Newly built flats or homes have high probability of condensation, especially in the first year, until the
construction or finishing materials haven’t dried up completely. When installing the unit in the rooms with a high probability
of condensation, it is necessary to ensure that the condensate does not damage the building structures or furniture.
To reduce condensation on the outside of the AHU, the following is recommended:
• maintain a lower relative humidity in the room where the AHU is installed;
• install a pre-heater to increase the air temperature of the outdoor air entering the unit.
• if the air is drier outside, you can increase the ventilation intensity and the temperature settings so that the rooms are
dried faster. For this purpose, you can also use the “Humidity control function” (see “Domekt User Guide”).
If the unit is shut down in cold outside temperatures, due to free air circulation, condensate can form inside of the unit,
therefore, it is important to install air closing dampers (motorized are recommended) to close the air intake and exhaust
openings when the unit is OFF. This will prevent cold air from the outside and warm air from the premises to enter the unit.
We recommend that you always keep the unit turned on and use it at minimum of 20% intensity even
if no ventilation is required. This will ensure good indoor climate conditions and reduce condensation
inside the unit, which might damage electronic components.