19
UAB KOMFOVENT we reserve the right to make changes without prior notice
C6M_GUIDE2-19-04
• Minimum intensity
– select ventilation intensity at which the unit will operate when air quality (impurity or humidity) is
good. If 0% is selected, the unit will stop when air impurity level is low.
• Maximum intensity
– select ventilation intensity limit, under which the unit will operate when air quality (impurity or
humidity) exceeds a defined value.
• Check period
– specify how often the unit shall turn on to check air quality, when minimum intensity is set to 0%.
Control sequence
– here you can activate additionally connected duct-mounted heating or cooling devices (see
“Installation Manual”) that will operate only when a heat exchanger or electrical heater alone cannot reach a desired
temperature.
Control sequence
1
/ 2
Stage 1
Electric heater
Stage 2
External coil
Stage 3
None
External coil type
Cold water
Icing protection
On
2
/ 2
Control sequence
Indoor humidity
Auto
Allow dehumidifying with cooling
Off
Numbers indicate the order of activation. All units have an integrated electrical heater, therefore it is factory-assigned as
Stage 1. You can also assign an “external coil” (duct-mounted water heater/cooler) or an “external DX unit” (direct evaporation
heat exchanger) as a stage. If an external coil is selected, you also must specify its type: “Hot water” (used for heating), “Cold
water” (used for cooling) or AUTO (both for heating and cooling). If AUTO type is selected, heating or cooling operations are
decided by an external signal connected to the controller board terminals (see “Installation Manual”). If additional heating/
cooling devices are not available, you do not want to use them or an electrical heater, select “None”.
Stage 1
None
Electric heater
External coil
External DX unit
Control sequence
1
/ 2
Stage 1
Electric heater
Stage 2
External coil
Stage 3
None
External coil type
Cold water
Icing protection
On
External coil type
Hot water
Cold water
Auto
If you turn off an electric heater and do not activate a duct-mounted heater, the desired air
temperature may not be reached when the outside air is cold.