2.5.2.1. Air quality control
Air quality control is designed according to:
• CO
2
sensor [0...2000 ppm];
•
air quality sensor VOCq [0...100 %];
•
air pollution sensor VOCp [0...100 %];
•
relative humidity sensor [0...100 %];
Depending on the type of the selected sensor, the value of the air quality
function to be maintained is set, and the air handling unit intensity will be adjusted
according to that value. Ventilation intensity will be increased automatically in the
case of deviation from the set value and decreased again when it is approached.
For example, if the unit is designed with the CO
2
maintenance function and is
equipped with a CO
2
sensor, after setting value 800 ppm, this set CO
2
level will
be maintained by adjusting ventilation intensity, i.e. ventilation intensity will be
increased if the CO
2
level grows and will be decreased when it returns to the
previous condition.
This function is provided only in units with EC fans.
2.5.2.2. Exhaust air flow correction
Set air flow intensity (or maintained air volume) for 1–99 minutes period can be
corrected from -50 % till +50 % from set value. Example, after reducing exhaust
air flow intensity, for some time overpressure will be caused (sometimes needed
to start the fireplace or such).
Note: After this function has been activated unit will work for the set time period
with present exhaust correction. After time period is over this function turns off
automatically.
This function is provided only in units with EC fans. This function is not
available in supply air units (OTK).
2.5.2.3. Summer night cooling
If the room temperature (exhaust air) in summertime is 5 °C higher than the set-
point and outside temperature is between 12 °C and the setpoint, the ventilation
level is automatically switched to the third intensity level at 00:15 am. The unit
will operate in the third intensity level until 06:00 am or when outside air cools
down (warms up) too much or the room temperature equals the setpoint. The air
is being cooled only by fans, without heat or coolness recovery and additional air
heating or cooling. When function is switched off the unit continues operating in
the previous mode.
Function starts operating automatically if only the unit operates in the
first or second operation mode. Function stops operating, when the
mode is being changed.
Summer night cooling and minimum temperature control functions can
not be activated at the same time. When one is selected, another’s
function operation is blocked.
Enable
Setpoint
1000 ppm
Sensor
CO
2
Air quality control
Enable
Extract flow
-50%
Time
1 min.
Exhaust air flow correction
Enable
Summer night cooling