Graphic Operator Terminal
Installation Manual

Edition B, October 2014

AKI-CDB-MOD-07T 7” Touchscreen HMI

Keep all manuals as a product component during the life span of the product.
Pass all manuals to future users / owners of the product.

Summary of Contents for AKI-CDB-MOD-07T

Page 1: ...r Terminal Installation Manual Edition B October 2014 AKI CDB MOD 07T 7 TouchscreenHMI Keep all manuals as a product component during the life span of the product Pass all manuals to future users owners of the product ...

Page 2: ...OTICE Technical changes which improve the performance of the device may be made without prior notice Printed in the United States of America This document is the intellectual property of Kollmorgen All rights reserved No part of this work may be reproduced in any form by photocopying microfilm or any other method or stored processed copied or distributed by electronic means without the written per...

Page 3: ...Peripherals 10 4 Technical Data 5 Chemical Resistance 5 1 Metal Casing 13 5 2 Touch Screen and Overlay 14 5 2 1 Autoflex EBA 180L 14 5 2 2 Touch Screen Surface 14 5 2 3 TouchKeyboard and Screen Protection Film 15 6 Operator Panel Drawings 6 1 Connectors 16 6 2 Communication Ports 16 6 3 AKI CDB MOD 07T Outline 17 7 Additional Installation Tips 7 1 Grounding the Operator Panel 18 7 2 Ethernet Conne...

Page 4: ...nderstand and use Configuration is carried out on a PC using the Kollmorgen Visualization Builder configuration tool The project can then be transferred and stored in the operator panel itself Various types of automation equipment such as PLCs servos or drives can be connected to the Advanced Kollmorgen Interfaces In this manual the term the controller refers to the connected equipment This manual...

Page 5: ...urpose Because of the many variables associated with any particular installation the supplier cannot assume responsibility for actual use based on the figures The supplier neither guarantees that the HMI panel is suitable for your particular application nor assumes responsibility for your product design installation or operation It is recommended to turn on and shut down the HMI panel at least onc...

Page 6: ...lock Connector Wire Size TQ Lb In X1 X100 Phoenix connectors AWG 30 12 5 7 X1 X100 Anytek connectors AWG 24 12 3 5 These devices are Class 2 supplied programmable controllers industrial PCs for the use in industrial control equipment and are intended to be front panel mounted Type 1 and 4x for indoor use only Caution The enclosure provides a degree of protection of at least IP20 but when installed...

Page 7: ... front cover with a soft cloth and mild detergent Replacing the battery incorrectly may result in explosion Only use batteries recommended by the supplier During the warranty period the battery needs to be replaced by an authorized Kollmorgen service center 2 6 Dismantling andScrapping The HMI panel or parts thereof shall be recycled according to local regulations The following components contain ...

Page 8: ...ace Requirements Maximum installation plate thickness 11 mm Space requirements in millimeters when installing the operator panel 143 204 50 mm 100 mm 100 mm 50 mm 100 mm Note The dimensions onthedrawing are not proportional ky Kollmorgen October 2014 8 ...

Page 9: ...table surface during installation Dropping the HMI panel or letting it fallmay cause damage 2 To cut a correct opening for the HMI panel use the cut out dimensions in the outline drawing For more information see sections Operator Panel Drawings and Technical Data 3 Secure the HMI panel in position using all the fastening holes and the provided brackets and screws x 4 0 5 1 0 Nm ky Kollmorgen Octob...

Page 10: ...S422 RS485 24V DC A D Controller Power B Ethernet C Connect cable A Connect cable B using an M5 screw and a grounding conductor as short as possible that is sized correctly according to local electrical codes Connect cable C Connect cable D The recommended cross section of the cable is 1 5 mm2 5 Carefully remove the laminated film over the HMI panel display to avoid static electricity that could d...

Page 11: ...oated aluminum Weight 1 010 kg Serialport for COM1 RS232 and COM2 RS422 RS485 9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40UNC Serialport for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40UNC Ethernet 1 x 10 100 1000 Base T shielded RJ45 USB 3 USB Host 2 0 max output c...

Page 12: ...EC 61558 2 4 UL and cUL The power supply must conform with the requirements for class II power supplies Display TFT LCD with LED backlight 800 480pixels 262 k colors Activearea of display W H 152 4 91 4 mm Operating temperature 10 C to 50 C Storage temperature 20 C to 70 C Relative humidity in operation 5 85 non condensed UL approval Yes UL 508 ky Kollmorgen October 2014 12 ...

Page 13: ... to the following chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Sodium hypochlorite 10 Turpentine Note If exposure to any of the above chemicals is demanded it is recommended to first test the chemical in a hidden spot of the metal casing The powder paint shows little or no resistance to the following chemicals at room t...

Page 14: ...etchup Caustic soda 40 1 Methanol Trichloroacetic acid 50 Cutting oil Nitric acid 10 White Spirit Cyclohexanol Paraffin oil Windex 1 Diacetone alcohol Persil powder in solution 1 Wisk Diesel Petroleum spirit 1 Acetonitrile 1 Extremely faint glossing of the texture was noted Autoflex EBA 180L withstands DIN 42 115 Part 2 exposure of up to 1 hour duration to glacial acetic acid without visible chang...

Page 15: ...flex EBA 180L Outdoor Use In common with all polyester based films Autoflex EBA 180L is not suitable for use in conditions of long term exposure to direct sunlight Note The layer structure of the touch screen contains air and inrare cases appearance of bubbles can arise This is purely cosmetic and does not affect any functionality of the panel The appearance can occur under certain environmental c...

Page 16: ...A 5 Headphone Headphone Connector 6 LAN Port 1 1 x 10 100 1000 Base T shielded RJ45 7 COM 3 4 Communication Ports 6 2 Communication Ports Serial port 9 pin female Serial port 9 pin female Pin COM1 COM2 COM3 COM4 1 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx 2 RS232 RxD RS232 RxD 3 RS232 TxD RS232 TxD 4 RS422 Rx RS422 Rx 5 GND GND GND GND 6 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx 7 RS232 RTS RS422 ...

Page 17: ...AKI CDB MOD 07T OPERATOR PANEL DRAWINGS 6 3 AKI CDB MOD 07TOutline 126 9 9 43 max 11 mm 7 143 187 204 9 9 ky Kollmorgen October 2014 17 ...

Page 18: ...according to local electrical codes between the operator panel s chassis and the closest grounding point on the door see 3 in drawing above 3 Connect a strong but short grounding braid between the door and the device cabinet see 4 in drawing above 4 Twist the cables onto the 24 V DC feed see 5 in drawing above 2 turns around the ferrite core provide 4 times the suppression of 1 turn 3 turns around...

Page 19: ...Ethernet unit has its shield directly grounded or grounded via a capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at bothends is inappropriate Hum or grounding loops can occur Unshielded cabling may even result in fewer communication errors A good solution may be to use a shielded Ethernet cable but to connect the shield at one end only One option is to break th...

Page 20: ... end of the shield to the ground via a 0 1 µF 250 V plastic capacitor Both ends are then connected to the ground in terms of HF but only connected to the ground at one end in terms of LF thus avoiding the 50 60 Hz grounding loops Metal cabinet Metal cabinet Terminal or connector Terminal or connector EMC cable gland Plastic cable gland Shielded cable Short distance Cable clamp in steel Shielded ca...

Page 21: ...sitive to heat The lifespan of an electrolytic capacitor is cut in half with an 8 10 C increase in temperature A 15 20 C temperature increase results in a quarter of the lifespan etc Rittal has a good program for estimating the anticipated average temperature in the cabinet as well as a large program for controlling the temperature in the device cabinet An enamel coated steel cabinet has a radiant...

Page 22: ... example SELV according to EN 60950 protection against electric shock and UL 950 Note Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller controller Check that the clearances and creepage distances between 24V DC and 230 V AC fulfillEN 60950 or UL 950 If not input a separate 24 V unit into the operator pan...

Page 23: ...r example a USB memory stick keyboard or similar device is plugged in If a number of units are connected that have a 0 V and a ground connection and these are connected to various grounding points there is a substantial risk of problems Grounding currents go through communication cables the rear plate of the controller and internally in the operator panel and can cause errors Use external units to...

Page 24: ...shield must be grounded at one end The other end is usually grounded but with longer distances or when there is a difference in the ground potential the shield should be connected to the ground via 0 1 µF 250 V plastic capacitor to prevent ground current in the braided shield A number of manufacturers recommend that the shield be grounded at each node Various manufacturers have different systems f...

Page 25: ...AKI CDB MOD 07T ADDITIONAL INSTALLATION TIPS ky Kollmorgen October 2014 25 ...

Page 26: ... Tap anywhere on screen or touch calibrate will start in 10 seconds 5 Press finger on screen again to enter the service menu The Service Menu displays Note Additional information about the Service Menu options are available in the Kollmorgen Visualization Builder KVB online help HMI Panel System Software Service Menu 8 2 HMI to PDMM Connection and Programming Modbus TCP is used to communicate from...

Page 27: ...by right clicking on the System option in the Project Explorer and select Add HMI Device to display a list of HMI panels that Kollmorgen has available Double click on the project to launch KVB and automatically import tags and the target IP address for the KAS controller 8 3 HMI to PAC Connection The same Ethernet service port of the AKI panel can be used to connect and interface with a PAC Using ...

Page 28: ...marketplace advantage For assistance with your application needs visit www kollmorgen com or contact us at North America Europe Asia KOLLMORGEN KOLLMORGEN Europe GmbH KOLLMORGEN 203A West Rock Road Pempelfurtstraße 1 Rm 2205 Scitech Tower China Radford VA 24141 USA 40880 Ratingen Germany 22 Jianguomen Wai Street Web www kollmorgen com Web www kollmorgen com Web www kollmorgen com Mail support koll...