6 Modes and Operating Conditions
6.1 Terms and Definitions
TA: Temperature of indoor ambient.
TE: Temperature of evaporator.
TS: The set temperature.
DAHT: Heater sensor.
6.2 Protection Functions
The compressor restart protection has a delay of 3 minutes.
Sensor protection against an open or short circuit.
6.3 Auto Mode
AUTO Mode is a setting that allows the unit to automatically switch between COOL and FAN in order
to achieve and maintain the desired set temperature.
In Auto mode the unit will choose cooling or fan-
only mode based on ΔT(ΔT=TA-TS)
ΔT = TA - TS
Running mode
ΔT
>
4
F
Cooling
-2
F ≤ ΔT ≤ 4
F
Fan-only
The unit will default to running mode when in auto mode under the following circumstances:
Powering on, changing mode to auto mode or adjusting temperature in auto mode will cause the
unit to default to running mode again.
A: In auto mode, if the compressor does not run for 15 minutes check condition B.
B: If ΔT<-8
℉
or ΔT
>
2
℉
, the unit will default to running mode again according to ΔT until the
compressor stops.