Electrical
WARNING: Failure to comply with these regulations may cause serious injury or death
and cause damage to the machine and its surroundings.
CAUTION:
Switching the machine “off” does not de-energize all circuits. Always disconnect
power before servicing.
•
All KOLD-DRAFT models are intended to be installed with a permanent connection to the field
electrical supply. See rating plate on the back of the machine for power supply requirements.
•
Each ice maker must be connected to a separate protected circuit with no other loads.
•
Fused disconnects, installed adjacent to each ice maker, are recommended and may be
required by local codes. These components must be supplied by the installer.
•
Electrical service must fall within the voltage tolerances listed below:
Maximum Overload Protection must be no greater than specified. The minimum circuit
ampacity specified does not indicate a typical running current value. Use the minimum
ampacity value for sizing branch circuit conductorsup to 26 feet (8 meters) in length. For a
conductor length over this length, increase the wire gauge as required by code.
Ice Cube Information
Cube Type
Cube Dimensions
Cube Weight Cubes per Cycle
C (Full Cube) 1-1/4 x 1-1/4 x 1-1/4 in (32 x 32 x 32 mm) 1.15 oz (32.6 g)
45
Model
Nominal (V) No-Load Maximum Full-Load Minimum
SC201
115
126
104
SC204
208-230
250
198
SC207
230
250
210