1.5 Ground the box.

Note:

The power relay module uses a non-conductive

resin enclosure.

Bonding between conduit

connections is not automatic and must be

provided as part of the installation.

1. Connect ground leads to the 1/4-20 post near the

bottom of the box using nut X-81-8. See Figure 7.

If metal conduit is used, use conduit hubs with

screw terminals for the ground connection.

Connect the ground leads LK-1006-1515, supplied

with the kit, to the grounding post. Connect the

other ends of the ground leads to the conduit hub

screw terminals.

2. Ground the system according to the NEC and

applicable state and local codes.

1.6 Install the module cover.

1. Check that gasket GM92009 is in place in the

groove around the edge of the box, with a gap at the

bottom as shown in Figure 7.

2. Place the cover on the box and reinstall the four

cover screws.

1.7 Return the system to automatic

operation.

1. Check that the generator set is OFF.
2. Reconnect the generator set engine starting

battery, negative (--) lead last.

3. Reconnect utility power to the generator set.
4. Press the AUTO button on the generator set

controller.

5. Reconnect power to the transfer switch.

2 Operation

The power relay module operation is controlled by the

load management device, which is either a load shed kit

or the RXT combined interface/load management

board.

The relay is normally closed so that the

connected load is powered when the normal source is

available.

When the transfer switch is in the emergency source

position and power is supplied by the generator set, the

load management device signals the relay to open or

close. When the relay is open, the load is not powered.

When the relay closes, the load is powered by the

generator set. The loads are prioritized according to the

relay connections to the load management device. See

TT-1609 for the load shed kit or TP-6807, RXT ATS

Operation/Installation Manual, for information about

operation of the load management device.

Note:

The power relay modules are

not

RBUS

modules.

3 Dimension Drawings

The dimension drawings for the power relay module are

shown in Figure 7 and Figure 8.

Summary of Contents for RDT ATS

Page 1: ...AC relays require a customer supplied voltage source Check the electrical requirements of the customer provided equipment prior to installation to determine the wire size and circuit protection required Verify that customer provided equipment complies with applicable local and national electrical codes Read the entire installation procedure and compare the kit parts with the parts list at the end ...

Page 2: ... kit or TP 6807 RXT Operation and Installation Manual for load priority and load management operation information 1 1 Prevent the generator set from starting 1 Place the generator set master switch in the OFF position 2 Disconnect the utility power to the generator set 3 Disconnect the generator set engine starting battery ies negative lead first 1 2 Install the power relay modules 1 Identify a co...

Page 3: ...on the relay Connect the control leads from the load shed kit to the relay coil using ring terminals X 283 2 5 See Figure 4 and Figure 8 for the source and load connections to the relay a Connect the line side of the relay to the source power circuit as shown in Figure 4 b Connect the load side of the relay to the non essential load circuits as shown in Figure 4 Two 2 120 VAC loads shed simultaneo...

Page 4: ...ews on the relay Connect the control leads from the RXT combined interface load managementboard tothe relay coil using ring terminals X 283 2 5 See Figure 6 and Figure 8 for source and load connection points on the relay a Connect the line side of the relay to the source power circuit as shown in Figure 6 b Connect the load side of the relay to the non essential load circuits as shown in Figure 6 ...

Page 5: ...e generator set engine starting battery negative lead last 3 Reconnect utility power to the generator set 4 Press the AUTO button on the generator set controller 5 Reconnect power to the transfer switch 2 Operation The power relay module operation is controlled by the load management device which is either a load shed kit or the RXT combined interface load management board The relay is normally cl...

Page 6: ...6 TT 1646 6 15 Figure 7 Power Relay Module Dimensions ADV 8742 Sheet 1 of 2 ...

Page 7: ...TT 1646 6 15 7 Figure 8 Power Relay Module Dimensions ADV 8742 Sheet 2 of 2 ...

Page 8: ...M92008 1 Enclosure Base GM91999 1 Enclosure Cover GM92000 2 Screw Thread Forming GM92003 1 Gasket 2 56 ft GM92009 1 Relay Sub Assy GM92005 1 Decal GM97546 2 Terminal ring male 16 14 AWG X 283 2 2 Lead LK 1006 1515 4 Screw Phillips pan head thread form X 6071 2 1 Nut hex 1 4 20 X 81 8 1 Installation Instructions TT 1646 Availability is subject to change without notice Kohler Co reserves the right t...