Kohler RDT ATS Installation Instructions Manual Download Page 3

TT-1646 6/15

3

1.3 Relay Connections to a Load Shed Kit

This section applies to models RDT ATS and RXT ATS

equipped with load shed kit GM88281-KA1 or

GM88281-KP1-QS.

For the RXT with combined

interface/load management board, go to Section 1.4.

See Figure 2 for cable specifications.

Note:

See the instructions provided with the load shed

kit for load priority and load management

operation information.

Load management priorities are determined by the

control relay output connections to the load shed kit.

Typically, Load A is added first and shed last.

1. Disconnect power to the transfer switch.
2. If the load shed kit is not already installed, follow the

instructions provided with the load shed kit to install

the load shed kit into the transfer switch enclosure

and connect it to the generator set controller and

current transformer.

3. Connect customer-supplied leads to the control

relay output terminals on the load shed kit terminal

block. See Figure 3 and Figure 4.

4. See Figure 7 for the coil connection screws on the

relay. Connect the control leads from the load shed

kit to the relay coil using ring terminals X-283-2.

5. See Figure 4 and Figure 8 for the source and load

connections to the relay.

a. Connect the line side of the relay to the source

power circuit as shown in Figure 4.

b. Connect the load side of the relay to the

non-essential load circuits as shown in

Figure 4.

Two (2) 120 VAC loads (shed

simultaneously) or a single 240 VAC load can

be wired to each relay.

6. Connect the 120 VAC power circuit to the the load

shed kit terminal block as shown in Figure 4.

Note:

The AC power supply circuit must be

protected by an appropriately sized fuse or

circuit breaker.

7. For all other load shed kit installation and

connection instructions, see the installation

instructions provided with the load shed kit.

8. Go to Section 1.5.

Relay *

Load Shed Kit TB10 Connection

Load A

TB10-1 and TB10-2

Load B

TB10-3 and TB10-4

Load C

TB10-5 and TB10-6

Load D

TB10-7 and TB10-8

* Load add/shed priority is based on the order of connection to

the terminal block.

Figure 3

Relay Coil Control Connections to Load

Shed Kit

GM88804

LOAD SHED KIT

TERMINAL BLOCK

FACTORY CONNECTIONS

RBUS

CONNECTIONS

Figure 4

Relay Connections to Load Shed Kit

Summary of Contents for RDT ATS

Page 1: ...AC relays require a customer supplied voltage source Check the electrical requirements of the customer provided equipment prior to installation to determine the wire size and circuit protection required Verify that customer provided equipment complies with applicable local and national electrical codes Read the entire installation procedure and compare the kit parts with the parts list at the end ...

Page 2: ... kit or TP 6807 RXT Operation and Installation Manual for load priority and load management operation information 1 1 Prevent the generator set from starting 1 Place the generator set master switch in the OFF position 2 Disconnect the utility power to the generator set 3 Disconnect the generator set engine starting battery ies negative lead first 1 2 Install the power relay modules 1 Identify a co...

Page 3: ...on the relay Connect the control leads from the load shed kit to the relay coil using ring terminals X 283 2 5 See Figure 4 and Figure 8 for the source and load connections to the relay a Connect the line side of the relay to the source power circuit as shown in Figure 4 b Connect the load side of the relay to the non essential load circuits as shown in Figure 4 Two 2 120 VAC loads shed simultaneo...

Page 4: ...ews on the relay Connect the control leads from the RXT combined interface load managementboard tothe relay coil using ring terminals X 283 2 5 See Figure 6 and Figure 8 for source and load connection points on the relay a Connect the line side of the relay to the source power circuit as shown in Figure 6 b Connect the load side of the relay to the non essential load circuits as shown in Figure 6 ...

Page 5: ...e generator set engine starting battery negative lead last 3 Reconnect utility power to the generator set 4 Press the AUTO button on the generator set controller 5 Reconnect power to the transfer switch 2 Operation The power relay module operation is controlled by the load management device which is either a load shed kit or the RXT combined interface load management board The relay is normally cl...

Page 6: ...6 TT 1646 6 15 Figure 7 Power Relay Module Dimensions ADV 8742 Sheet 1 of 2 ...

Page 7: ...TT 1646 6 15 7 Figure 8 Power Relay Module Dimensions ADV 8742 Sheet 2 of 2 ...

Page 8: ...M92008 1 Enclosure Base GM91999 1 Enclosure Cover GM92000 2 Screw Thread Forming GM92003 1 Gasket 2 56 ft GM92009 1 Relay Sub Assy GM92005 1 Decal GM97546 2 Terminal ring male 16 14 AWG X 283 2 2 Lead LK 1006 1515 4 Screw Phillips pan head thread form X 6071 2 1 Nut hex 1 4 20 X 81 8 1 Installation Instructions TT 1646 Availability is subject to change without notice Kohler Co reserves the right t...

Reviews: