background image

12

1367864-W2-C

Fit the inlet connectors with isolation hex facing downwards, aligning with the holes in 

the backplate.  Attach the backnuts (supplied) leaving approx. 10-15 mm float allowing 

access to the spanner flats.      

a

e

d

c

b

10 -15 mm

a

e

d

c

b

Make the plumbing connections. 

DO NOT

 use jointing paste when making plumbing 

connections. 

Summary of Contents for rada Intelligent Care MX1 60

Page 1: ...1 1367864 W2 C Please leave these instructions with the user Installation Guide Intelligent Care MX1 Wall Mounted Tap...

Page 2: ...2 1367864 W2 C...

Page 3: ...tly in accordance with the information supplied with the disinfectant and with all relevant Guidelines Approved Codes of Practice The use of the word failsafe to describe the function of any thermosta...

Page 4: ...re 1 C 1 C Maximum Humidity 95 rH 95 rH Water Supply Water connections 15 mm Compression or 1 2 BSP Minimum dynamic pressure 100 kPa 1 0 bar Maximum dynamic pressure 500 kPa 5 0 bar Maximum static pre...

Page 5: ...erface Info Field 15 Operational State Enable Enable Enable Disable 16 Tasks Apply Changes to Valve Undo Changes 1 Valve Setup 5 Outlet Setup 1 Type Info Field 2 Sub Type On Off On Off On Off Timed Bl...

Page 6: ...Changes 1 Valve Setup 7 Cold Flush Setup 1 Activation Manual Manual Manual Automatic 2 Type Disabled Disabled Disabled Standard 3 Activation Time 04 00 Hrs 04 00 Hrs Time 24 Hr Clock 4 Duration 2 Min...

Page 7: ...sable Key q 2 x Connector q 2 x Nut q 2 x Screw q 1 x Template q 1 x Adapter q 4 x Fixing Screw q 4 x Wall Plug q 1 x Power Supply q 2 x Check valve Filter Housing Assemblies q Pack Contents 1 x Flush...

Page 8: ...47 mm 220 mm 150 mm 199 mm 220 mm 80 mm 40 mm 170 mm 26 mm 30 Connection to Power Supply Unit PSU Mains Cable 2 m PSU TAP PSU 12V Cable Extension Cable Total Cable Run 1 18 m Total Cable Run with Ext...

Page 9: ...m 200 mm 47 mm 199 mm 262 mm 80 mm 40 mm 26 mm 170 mm 30 PSU Mains Cable 2 m PSU TAP PSU 12V Cable Extension Cable Total Cable Run 1 18 m Total Cable Run with Extension Cable 3 68 m Product Tail 1 0 m...

Page 10: ...Installation Installation of the Tap on the Stud wall and IPS panel Use the installation template provided level and mark the positions of the holes For Correct Height Refer to HBN00 10 Part C Drill t...

Page 11: ...Install the PSU Power Supply Unit in an area that you can access easily for servicing and maintenance purposes Secure the backplate using the supplied fixing screws DO NOT overtighten a e d c b MX1 60...

Page 12: ...g downwards aligning with the holes in the backplate Attach the backnuts supplied leaving approx 10 15 mm float allowing access to the spanner flats a e d c b 10 15 mm e d c b Make the plumbing connec...

Page 13: ...with isolation hex facing downwards aligning with the holes in the backplate Make the plumbing connections Use the adapter supplied to hold the inlet connector DO NOT use jointing paste when making p...

Page 14: ...ow The check valves filter housings are identified by a coloured dot that indicates hot and cold connections This assembly to be sited in a location that is accessible for servicing Maximum pipe lengt...

Page 15: ...and remove the filter Flush the Pipework a e d c b a e d c b Install the bleed pipe and tighten using a 10 mm hexagonal wrench a e d c b e d c b Note The procedure is similar for Panel Stud and IPS Pa...

Page 16: ...the screw to bleed the supply pipework 1 min e d After bleeding refit the components in reverse order DO NOT open the isolator on the check valve filter housing Connect the power cable to the tap and...

Page 17: ...cure the tap using the supplied screws DO NOT overtighten Open the isolator on the check valve filter housing Restore the water supplies and turn on supplies at the check valve flow regulator ON ON a...

Page 18: ...a MX1 wall mounted tap will operate to factory settings when first installed Download the RADA AP1 from the Apple APP Store and follow the on screen instructions Note Run the tap for 30 seconds in ord...

Page 19: ...nload the RADA AP1 from the Apple APP Store and follow the on screen instructions Note For Type 3 valves in UK Healthcare installations the maximum blend temperature is determined by the application r...

Page 20: ...367864 W2 C Note This tap has an over temperature limiting device should blend temperature exceed safe conditions the valve will shut down and reset automatically once temperature returns to a safe st...

Page 21: ...le the digital mixer turn off and on again Inlet water supply isolators not fully turned on Check and remedy Inlet water supply failure Check and remedy Inlet filters or check valves blocked Check and...

Page 22: ...failure Contact Rada Flow rate too high Inlet water pressures too high Check specification Inlet check valves flow regulators not fitted Check and remedy Digital Mixing valve failure Contact Rada Outl...

Page 23: ...repeat commissioning procedure and rearrange pipework to avoid airlock forming Digital Mixing valve failure Contact Rada Inlet pressures and or temperatures are unstable or spiking Check and remedy re...

Page 24: ...ck valves blocked Check and remedy Outlet spout hose or handset blocked Check and remedy Reversed inlet supplies Check and remedy Fluctuating supply pressures and or temperatures Check and remedy Inle...

Page 25: ...he appliance is fixed to will affect the perceived noise level solid walls will provide a quieter operation Digital Mixing valve failure Contact Rada False triggering Protective film not removed from...

Page 26: ...n unsafe blend temperature and has gone in to a thermal shutdown to protect the user Valve will self clear fault Inlet filters or check valves blocked Check and remedy Obstruction in inlet water suppl...

Page 27: ...30 seconds then re apply power Open circuit error Software failure Re set the product by turning electrical supply off for 30 seconds then re apply power Loose internal wiring connections Thermistor...

Page 28: ...Interface CGF error IO expander error Software failure Re set the product by turning electrical supply off for 30 seconds then re apply power Loose internal wiring connections Interface and PCB Ensur...

Page 29: ...shes should be cleaned using a mild washing up detergent or soap solution rinsed and then wiped dry with a soft clean cloth Cleaning Replace the new flow insert Remove the flow insert using 8 mm hexag...

Page 30: ...30 1367864 W2 C Turn the screw fully clockwise to isolate the water supply Refit the components in reverse order Clean the Filter Unscrew and remove the filter Clean the filter under running water...

Page 31: ...the screw fully clockwise to isolate the water supply Relieve the pressure by operating the tap Unscrew and remove the filter Using a suitable spanner remove the check valve housing Note Filter must...

Page 32: ...ply Blue Indices Hot Supply Red Indices Note For approvals requirements ensure the red indicated check valve filter housing is connected to the hot supply Remove the flow regulator and check valve Mak...

Page 33: ...6 CP 76670 CP 1264109 76670 CP 76676 CP 1264111 1264132 76670 CP 76676 CP 97390 CP 72946 CP A A A A A B B 1264113 97390 CP 72946 CP 1264114 76670 CP 76676 CP 1315132 1264124 72946 CP 766760 CP 76676 C...

Page 34: ...min HOT 1370884 4L min COLD 1370885 1372501 1372500 1372499 C C C C 1264134 x2 1264135 x20 1372502 4L min 2L min 1395070 1395069 1264122 Spare Parts 1372505 Seal Pack Components Identified C 76705 NA...

Page 35: ...35 1367864 W2 C...

Page 36: ...l guarantee terms and conditions or visit www radacontrols com for further information For UK only Customer Service Post Installation enquiries including details of the Rada Commissioning Responsive a...

Reviews: