5. Install the Steam Generators
WARNING: Risk of property damage.
Allow a minimum of 12
″
(30.5 cm) of air space around the
steam generators at all times. This provides an area for the heat generated by the units to dissipate.
NOTICE:
For optimum performance, install the steam generators as close as possible to the steam heads.
The steam generators must be installed within 25’ (7.62 m) of the steam head.
Install the desired drain pan at the steam generator location.
IMPORTANT!
The support blocks should be constructed of heat resistant material.
Position support blocks so the steam generators will have 3/4
″
(1.9 cm) of clearance from the drain
pan.
Position the steam generator on the drain pan.
Steam Outlet
Inlet
Maintain a 12" (30.5 cm) minimum
space around the units.
12"
(30.5 cm)
Pressure Relief Valve
Drain Pan
Control Cable
Input
1053777-2-D
8