Kohler GM87026-KP1-WHT Installation Instructions Manual Download Page 4

4

TT-1622

9/16

5.

Restore the generator set to service.

5.1 Check that the generator set is OFF.

5.2 Reconnect the generator set engine starting

battery, negative (--) lead last.

5.3 Reconnect power to the battery charger, if

equipped.

6.

Program the low oil level shutdown.

6.1 Check the dipstick to verify the oil level as full.

With the engine running and warm, adjust the high

and low oil level indicators to approx. 12.7 mm

(0.50 in.) from the full level. See Figure 2 for

adjustment locations.

6.2 Using SiteTech

t

, under the

Programmable

Digital Input 110

parameter, change the settings

to the following:

Digital Input Enabled:

On

Digital Input Logic:

Active Close

Digital Input Event:

Engine Oil Level

Low Shutdown*

Digital Input Delay:

5 s

Digital Input Inhibit Delay:

30 s

* Engine Oil Level Low Shutdown will be displayed for either low or

high oil level.

Note:

For more information on SiteTech

t

, see

TP-6701

t

SiteTech Software Operation

Manual.

Figure 3

Programmable Digital Input 110 Parameter

(in SiteTech

t

)

Parts List

Oil Level Indicator Kits

Kits: GM87026-KP1-WHT and GM87026-KP1-G49

Qty. Description

Common Parts

1

Gauge, oil level

227257

4

Mount, controller

241769

1

Cover, plate

for Kit GM87026-KP1-WHT

for Kit GM87026-KP1-G49

GM47418-WHT

GM47418-G49

1

Bracket,

for Kit GM87026-KP1-WHT

for Kit GM87026-KP1-G49

GM86335-WHT

GM86335-G49

2

Nut, hex (10 mm)

M6923-10-80

2

Screw, hex cap

M933-10025-60

1

Cross, pipe (1/2 in. NPT)

X-207-7

1

Pipe (1/2 in. NPT x 1.19 in.)

X-209-2

4

Washer, lock

(0.262 in. ID x 0.743 in. OD)

X-22-12

1

Hose (0.25 in. ID x 17 in.)

X-386-74

1

Hose (0.50 in. ID x 9.25 in.)

X-422-18

2

Clamp, hose (0.69/1.25 in.)

X-426-12

2

Clamp, hose (0.25/0.70 in.)

X-426-9

1

Coupling

X-567-1

1

Connector, hose

X-582-38

2

Connector, hose

X-582-5

4

Nut

X-6210-2

1

Plug, pipe

X-75-3

1

Restrictor plug

GM98574

Summary of Contents for GM87026-KP1-WHT

Page 1: ...pare the kit parts with the parts list at the end of this publication before beginning installation Perform the steps in the order shown Safety Precautions Observethefollowingsafetyprecautionswhileinstalling the kit Accidental starting Can cause severe injury or death Disconnect the battery cables before working on the generator set Remove the negative lead first when disconnecting the battery Rec...

Page 2: ...bushing in the oil pan 2 8 Connect the pipe cross X 207 7 to the pipe 2 9 Connect the pipe plug X 75 3 to the pipe cross as shown in Figure 2 item 14 2 10 Connect the hose connector X 582 5 to the pipe cross 2 11 Secure the oil hose X 422 18 to the hose connector in the oil pan using a hose clamp X 426 12 2 12 Place the restrictor plug GM98574 in the other end of the oil hose X 422 18 and secure i...

Page 3: ...0 Oil level bracket GM86335 WHT or GM86335 G49 11 Hose X 422 18 and hose clamps X 426 12 qty 2 12 Hose connector X 582 5 13 Pipe X 209 2 Attach to oil pan on engine 14 Pipe plug X 75 3 15 Pipe cross X 207 7 16 Position existing oil drain valve in this position 17 Restrictor plug GM98574 18 Hose connector X 582 5 19 Hose X 386 74 and hose clamps X 426 9 qty 2 20 Cover plate GM47418 WHT or GM47418 G...

Page 4: ...tdown will be displayed for either low or high oil level Note For more information on SiteTecht see TP 6701t SiteTech Software Operation Manual Figure 3 Programmable Digital Input 110 Parameter in SiteTecht Parts List Oil Level Indicator Kits Kits GM87026 KP1 WHT and GM87026 KP1 G49 Qty Description Common Parts 1 Gauge oil level 227257 4 Mount controller 241769 1 Cover plate for Kit GM87026 KP1 WH...

Page 5: ...TT 1622 9 16 5 1 Oil level gauge 1 See the full wiring diagram in the operation manual GM86969B D Figure 4 Wiring for Oil Level Gauge Typical ...

Page 6: ...6 TT 1622 9 16 Notes ...

Page 7: ...TT 1622 9 16 7 Notes ...

Page 8: ...stems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever Contact your local Kohlerr generator set distributor for availability 2014 and 2016 by Kohler Co All rights reser...

Reviews: