Kohler 5EFKOD Installation Instructions Manual Download Page 5

5

TT-1583 9/13

1.10.4 GenSet Information

Displays generator set and controller information.
Displayed data is factory entered.

GenSet Information

GenSet ---->
Information

Cntrllr S/N:

##

Genset M/N:

##

GenSet S/N:

##

1.10.5 GenSet Run Time

Displays the generator set’s operating record including
total run time loaded and unloaded, number of starts,
and total energy kW hours.

GenSet Run Time

GenSet ---->
Run Time

Eng Starts:

#

Eng Runtime:

##.# h

Next Maint:

##.# h

Since Maint:

## Starts

1.10.6 GenSet System

Display shows the generator set system data including
voltage, frequency, phase connection, etc. Use the
values entered in this menu to help determine shutdown
values and time delays.

The programming user defines the data shown in the
GenSet System menu. It is NOT data measured by the
controller and associated sensing devices.

The

programming user defines these values for purposes of
calibrating the control.

Some alternators are designed to operate at limited
voltage, frequency, or phase connections and as a result
some settings may have limited parameters.

Display for Measurement System is user selectable as
English or Metric.

Contrast display is user adjustable to help improve
digital display visibility in dimly lit rooms or in direct
sunlight.

Note:

The contrast feature is a controller hardware

change and may not be available on older units

even if the firmware is updated.

To

enable editing

of “

GenSet System

” parameters:

1.11 At the “

GenSet System

” menu, press the selector

dial and rotate until “

System Freq

” appears.

1.12 Press and hold the selector dial until “

Editing

Enabled

” appears.

1.13 Scroll through the parameters and press the

selector dial at the parameter that requires

changing. The parameter blinks to indicate that it is

editable.

1.14 Press the selector dial to change the parameter.

Note:

Parameters automatically scroll and keep

blinking until the desired selection is made by

pressing the selector dial.

1.15 Select “

Return

” to return to the

“GenSet System”

menu.

Note:

After changing the CAN A communication

setting, power off and then power on the

controller.

GenSet System

GenSet ---->
System

System Freq:
60 Hz or 50 Hz

Battery V:

## V

User Selectable -->

Meas System
English or Metric

Contrast
#####

User Selectable -->

User Selectable -->

CAN A:
J1939, SmartCraft, or
NMEA 2000

User Selectable -->

Summary of Contents for 5EFKOD

Page 1: ...st set the controller parameters On the ADC IId controller the installer can use the key sequence described in these instructions Use the pushbutton rotary selector dial to navigate to the respective...

Page 2: ...rforming voltage tests 1 Remove all jewelry 2 Stand on a dry approved electrically insulated mat 3 Do not touch the enclosure or components inside the enclosure 4 Be prepared for the system to operate...

Page 3: ...item Overview Turn the rotary dial to select the desired fixed view Overview Auto Scrolling Display Overview hr Avg V L L V Active Shutdowns if present Eng Runtime h Frequency Hz Oil Pressure PSI Bat...

Page 4: ...sh and hold the pushbutton rotary selector dial until the Calibration Enabled popup appears Calibration of each display is now available The display will show the following values for three phase gene...

Page 5: ...isplay for Measurement System is user selectable as English or Metric Contrast display is user adjustable to help improve digital display visibility in dimly lit rooms or in direct sunlight Note The c...

Page 6: ...w available The user can change the individual value or can select Reset VR Yes to reset to the default value The Reset VR Settings display will only show if editing is enabled To disable calibration...

Page 7: ...manual for voltage reconnection information With the generator set stopped go to the Volt Select menu Then push and hold the pushbutton rotary selector dial until the voltage selection starts to flas...

Page 8: ...sh Knob Load Complete Skipped if Genset is Running Note Ignored until generator set stops running Note Before inserting a mass storage device USB host connector power off and then power on the control...

Page 9: ...9 TT 1583 9 13 GM79008 C Figure 6 Wiring Diagram Point to Point...

Page 10: ...10 TT 1583 9 13 Notes...

Page 11: ...11 TT 1583 9 13 Notes...

Page 12: ...stems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the desi...

Reviews: