TP-6880 10/14
55
Section 4 DC2 Controller Operation
4.2.3
LCD Display
The controller is equipped with a two-line x 16 character
backlit digital display with adjustable contrast. When the
generator set is running, the messages shown in
Figure 4-5 are displayed. When the system is in AUTO,
the LCD display steps through the status messages
shown in Figure 4-6.
When a fault or warning condition exists, the controller
will show the corresponding message. See Section 2.5
for more information on fault and warning messages.
The display backlight turns off after about a minute of no
activity. The backlight turns on when a button is pressed
or when the generator set starts.
Running
ATS: Normal *
Voltage: 240V
Freq:
60.0Hz
Engine: 123F
Oil Pressure: OK
Battery
12.3V
Runtime: 12345.6 h
Next Exercise:
7d 6h 42m
Sample data shown.
Active Alert
(if any)
OnCue Status:
Disconnected
[
* Model RXT ATS required
[
OnCue status is displayed only if OnCue password has
been reset.
Figure 4-5
Status Displays, Generator Running
Genset State
Standby
Battery
12.3V
Runtime: 12345.6 h
Next Exercise:
7d 6h 42m
Sample data shown.
Active Alert
(if any)
Next Maint:
123h or 12months
OnCue Status:
Disconnected
[
OnCue status is displayed only if OnCue password has
been reset.
Figure 4-6
Status Displays, Generator in Standby
4.3 Controller Power
The DC2 controller is powered by the generator set
engine starting battery.
Note:
To disconnect controller power, disconnect the
utility power to the generator set and disconnect
the battery (negative lead first).
4.4 Battery Charging
The controller includes a built-in battery charger to
maintain the engine starting battery. The DC2 controller
monitors the battery voltage and provides a constant
14
±
2% VDC voltage and maximum 2.5 amps to
charge the battery.
The installer must connect 120 VAC/60Hz utility power
provided from the building on a breaker-protected circuit
for the built-in battery charger. See the Installation
Manual for instructions to connect power.
Summary of Contents for 10RESV
Page 12: ...TP 6880 10 14 12 Service Assistance Notes...
Page 28: ...TP 6880 10 14 28 Section 2 Generator Set Operation Notes...
Page 52: ...TP 6880 10 14 52 Section 3 RDC2 Controller Operation Notes...
Page 58: ...TP 6880 10 14 58 Section 4 DC2 Controller Operation Notes...
Page 70: ...TP 6880 10 14 70 Section 5 Scheduled Maintenance Notes...
Page 75: ......