![Kohler 100EFOZC Installation Instructions Manual Download Page 2](http://html1.mh-extra.com/html/kohler/100efozc/100efozc_installation-instructions-manual_1988161002.webp)
2
TT-1501
9/12
Note:
Depending upon the location, the Full Feature
Panel kits may require a Y connector and/or
harness kit. To ensure accuracy of the gauges
and meters, do not exceed 22.9 m (75 ft.) of
extension harnesses. See Figure 3.
Type
Length
Kit No.
Refer to
Y connector —
PA-344417
Figure 8
Pigtail
30.48 cm (12 in.) PA-344414
Figure 9
Extension
harness
4.6 m (15 ft.)
PA-344415
Figure 10
7.6 m (25 ft.)
PA-344416
Figure 10
Figure 3
Connector/Harness Kit Selection
Safety Precautions
Observe the following safety precautions while installing
the kit.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
the
generator
set.
Remove the negative (--) lead first
when
disconnecting
the
battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set.
Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
WARNING
The fuel system. Explosive fuel vapors can cause severe
injury or death.
Vaporized fuels are highly explosive. Use
extreme care when handling and storing fuels. Store fuels in a
well-ventilated area away from spark-producing equipment
and out of the reach of children. Never add fuel to the tank
while the engine is running because spilled fuel may ignite on
contact with hot parts or from sparks. Do not smoke or permit
flames or sparks to occur near sources of spilled fuel or fuel
vapors. Keep the fuel lines and connections tight and in good
condition. Do not replace flexible fuel lines with rigid lines. Use
flexible sections to avoid fuel line breakage caused by
vibration. Do not operate the generator set in the presence of
fuel leaks, fuel accumulation, or sparks. Repair fuel systems
before resuming generator set operation.
Installation Procedure
1.
Remove the generator set from service.
1.1
Place the generator set master switch in the OFF
position.
1.2
Disconnect the power to the battery charger, if
equipped.
1.3
Disconnect the generator set engine starting
battery(ies), negative (--) lead first.
2.
Install the panel kit.
2.1
Determine where in the wheelhouse or bridge to
mount the panel. The length of the wiring harness
and the panel size (including the mounting depth)
limits this decision. See Figure 4 for dimensions.
Allow 70 mm (2 3/4 in.) minimum mounting
clearance beyond the back of the panel.
See
Figure 5 for the panel assembly wiring.
Notes:
Dimensions are in mm (in.)
Panel thickness is 4.8 mm (0.19 in.).
279.4 (11.0)
295.4 (11.63)
231.9
(9.13)
215.9
(8.5)
4 countersunk holes 4.4 (0.172) diameter
A-344404-T
Figure 4
Meter Panel Dimensions