7 Troubleshooting
37
7 Troubleshooting
7.1 Error message on the display
Error
Cause
Solution
!InvEc
&
level present
AutCal not executed, interference
superimposes medium reflection
Perform commissioning
(see Chapter 2.1 "Quick commissioning")
TrsHld setting is not suitable for the
medium
Perform advanced commissioning
(see Chapter 2.2 "Advanced commissioning")
!InvEc
&
empty tank
Probe length configured incorrectly
Check probe length and compare against
configuration in EXPRT-Config-LENGTH
Probe not available
Check probe
!ATTNT
A parameter was written outside of
the valid value range and therefore
adjusted
Write the value again inside of the valid range
Another parameter was automatically
adjusted due to a dependency (SPx,
RPx)
Check parameter again
!WRONG
Incorrect password entered
Enter correct password
!NoCal
Information: The AutCal process or
foam calibration was rejected because
the probe length, teach-in depth, or
measuring mode was changed
Perform commissioning again if necessary
!CalOk
The teach-in process was successful
!NoSig
AutCal failed
Repeat commissioning
!faild
Foam-CalEmp or FoamCalMed menu
item failed
Follow the foam commissioning instructions
!SC-Q1
!SC-Q2
!SC-Q3
!SC-Q4
!SC-Qa
Short-circuit at the output
Remove short-circuit
Load resistance at the output is too
low
Increase load resistance
!IOLOf
Supply voltage too low for IO-Link
communication
Increase supply voltage to achieve the desired
functionality
!QaOff
Supply voltage too low for analog
output
Increase supply voltage to achieve the desired
functionality
!QxOff
Supply voltage too low for switching
outputs
Increase supply voltage to achieve the desired
functionality
!QaOvf
The ohmic load at the analog current
output Qa is too high
Reduce the load at Qa
The analog current output Qa is not
wired
Connect the load to Qa