Operating instructions for KME flow meter for compressed air and gases

4.1.1  Switch and pulse outputs

Switch and pulse outputs are NOT potential-free and include internal pull-down resistors (fig.10)

V+

GND

GND

10k

10k

OUT 1

OUT 2

Fig. 10 

Switch/pulse output

4.2  Bus output (projected)

4.2.1  M-Bus (Meter Bus) (projected)

The M-Bus (Meter Bus) is a field bus for recording consumption data. Transmission runs serially 

on a reverse polarity protected two-wire line. The KME flow meter as M-Bus slave requires a sep-

arate supply voltage. There is no prescribed specific topology (line or star) for the wiring. Normal 

phone cable of type J-Y(St)Y Nx2x0.8 mm can be used. The max. cable length per segment 

(primary addressed) is 250 m (3.28 ft).

The table below shows the structure of the consumption data sent by the transmitter:

Header

68

Start of the telegram

4F 4F

L-field (length)

68

Second starting signal

08

C-field (RSP_UD)

XX

A-field (address)

Start user data

72

CI-field (variable data structure)

XX XX XX XX

Identification number

A5 16

Manufacturer (0x16A5 … EUE)

01

Version

09

Medium (9 … compressed air)

XX

Access number (consecutive)

00

Status

00 00

Signature

Data record 1: Volume flow

05

DIF (32 bit real)

3E

VIF (volume flow in m³/h)

XX XX XX XX

Cur. measured value

Data record 2: temperature

05

DIF (32 bit real)

5B

VIF (temperature in °C)

XX XX XX XX

Cur. measured value

Data record 3: Mass flow

05

DIF (32 bit real)

53

VIF (mass flow in kg/h)

XX XX XX XX

Cur. measured value

Data record 4: Consumption meter status

05

DIF (32 bit real)

16

VIF (volumes in m³)

XX XX XX XX

Cur. consumption value

Data record 5: Flow velocity

05

DIF (32 bit real)

7F

VIF (manufacturer-specific in m/s)

XX XX XX XX

Cur. measured value

Data record 6: Volume flow

04

DIF (32 bit integer)

3B

VIF (volume flow in 10-³ m³/h)

XX XX XX XX

Cur. measured value

Data record 7: temperature

04

DIF (32 bit integer)

59

VIF (temperature in 10-² °C)

XX XX XX XX

Cur. measured value

Data record 8: Mass flow

04

DIF (32 bit integer)

51

VIF (mass flow in 10-² kg/h)

XX XX XX XX

Cur. measured value

Data record 9: Consumption meter status

07

DIF (64 bit integer)

13

VIF (volumes in 10-³ m³)

XX XX XX XX 

XX XX XX XX

Cur. consumption value

Data record 10: Flow velocity

04

DIF (32 bit integer)

7F

VIF (manufacturer-specific in 10-² 

m/s)

XX XX XX XX

Cur. measured value

end user data

XX

Checksum

16

End of telegram

Summary of Contents for KME

Page 1: ...BA_KME_e V1 3 Technical data subject to change 194573 Operating instructions KME Flow meter for compressed air and gases...

Page 2: ...high frequency energy If it is not installed and used in accordance with the operating instructions it may cause electromagnetic interference to radio communica tions However there is no guarantee tha...

Page 3: ...ure 10 3 3 Installation position 10 3 4 Inlet and outlet measurement path 11 3 5 Installation of the gauge mounting block 12 3 5 1 Operating the pipeline without transmitter 12 3 6 Mounting the transm...

Page 4: ...h optimal performance of the device 1 2 Safety instructions 1 2 1 Intended use The flow meter device is dedicated to the measurement of compressed air non corrosive and non flammable gases in pipeline...

Page 5: ...rized staff before putting the system into operation Do not install or start start up a device supposed to be faulty Make sure that such devices are not accidentally used by marking them clearly as fa...

Page 6: ...umption metering The KME features an integrated consumption meter The consumption volume can be shown on the display and is retained even if the supply voltage is interrupted Transmitter Display optio...

Page 7: ...r Software 2 2 Functions 2 2 1 Analogue output OUT 1 The analogue current output factory setting 4 20 mA or 0 20 mA is used for the actual flow or temperature measured values The analogue output is fr...

Page 8: ...mption is stored every minute and is retained even if the supply voltage is interrupted The totalized consumption can be shown on the display A reset of the consumption meter can be performed via disp...

Page 9: ...nting location for installing removing the transmitter unit of the E741 The ambient temperature shall not exceed the specified limits Consider also the possible heat radiation Air medium purity at the...

Page 10: ...y adjusted at 7 bar 102 psi absolute pressure For normal requirements pressure compensation is not necessary For best measure ment accuracy the actual working pressure can be set via display menu or v...

Page 11: ...complished by observing a minimum inlet and outlet path length which depends on both the nature of disturbance and the pipe diameter The flowmeter shall be located before valves or sliders With light...

Page 12: ...g 5 The sealing plug has a Tuflok coating http www bossard com and does not require any additional seal Mount the sealing plug with a torque of min 28 Nm Under normal operation with transmitter instal...

Page 13: ...ly fig 8 Fig 8 Tighten mounting screws 4 Electrical installation The electrical installation of the KME shall be performed by qualified staff only Observe all applicable national and international req...

Page 14: ...01 Version 09 Medium 9 compressed air XX Access number consecutive 00 Status 00 00 Signature Data record 1 Volume flow 05 DIF 32 bit real 3E VIF volume flow in m h XX XX XX XX Cur measured value Data...

Page 15: ...t float 30519 206 Standard volume flow Nm min 32 bit float 30521 208 Standard volume flow l min 32 bit float 30523 20A Standard volume flow l s 32 bit float 30525 20C Standard volume flow SCFM 32 bit...

Page 16: ...MAX value mass flow 16 bit integer 60008 7 Reset MAX value standard volume flow 16 bit integer 60009 8 Reset consumption meter 16 bit integer Data transmission Factory settings Adjustable values Baud...

Page 17: ...e on a personal computer 5 Display The LCD display optional shows the actual measured values and the overall consumption The complete KME setup and configuration can be performed with the control keys...

Page 18: ...dard flow Fig 16 Status display Fig 17 Measured value display Explanation of the symbols Output 1 set to analogue output Output 2 set to pulse output consumption Output 1 set to switching output statu...

Page 19: ...pe diameter Set the pipe diameter see 2 1 1 on page 7 Display Set the measuring mode and the display orientation Process parameter Set the operating pressure and the standard conditions see 2 2 4 page...

Page 20: ...LED lights up Cause The display or the communication with the display is faulty Consequence Analogue switch and pulse outputs operate normally Remedy Return the device to the manufacturer for service...

Page 21: ...or isopropanol Isopropanol is recommended for contamination with greases or oils Do not touch or rub the sensor element within the sensing head Allow the sensing head to dry free 7 3 Ordering guide f...

Page 22: ...er pulse duration 0 02 2 sec Bus interface Modbus RTU max 32 bus devices or M BUS Meter Bus Configuration interface USB General Supply voltage 18 30 V DC Current consumption max with display Imax 120...

Page 23: ...00 2500 250 Standard volume flow l s DN15 0 20 14 1 4 DN20 0 35 25 2 5 DN25 0 55 40 4 Standard volume flow SCFM DN15 0 44 30 3 0 1 0 05 DN20 0 76 53 5 3 0 15 0 07 DN25 0 117 88 8 8 0 2 0 1 Mass flow k...

Page 24: ...40 0 8300 5800 580 DN50 0 13300 10000 1000 Standard volume flow l s DN32 0 83 56 5 6 DN40 0 139 97 9 7 DN50 0 222 167 16 7 Standard volume flow SCFM DN32 0 176 117 11 7 0 55 0 25 DN40 0 294 200 20 0 9...

Page 25: ...ory use EMC requirements Part 1 General requirements eN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test configurat...

Page 26: ...26 Operating instructions for KME flow meter for compressed air and gases...

Page 27: ...27 Operating instructions for KME flow meter for compressed air and gases...

Page 28: ...www kobold com...

Reviews: