KAL-K K03/0516
Connect wires to terminal connector block according to the drawing.
Tighten cable gland.
After connection, apply supply voltage of 24 VDC ± 20%. (see 12. Technical
Information)
Check function of electronic (set point LED must flash)
Calibrate flow switch (see 10. Commissioning)
24 V
DC
-Version (plug or plug with cable)
Connect wires to terminal connector block according to drawing below.
After connection apply supply voltage of 24 VDC ± 10 %. (see 12. Technical
Information)
Check function of electronic (set point LED must flash)
Calibrate flow switch (see 10. Commissioning)
110 V
DC
, 110 V
AC
or 230 V
AC
-version
Remove electronic cover.
(The fixing screws are secured against falling out)
The devices are supplied either with coded cables or a plug connection.
Connect single wires or plug according to drawings below.
After connection apply supply voltage according to label on the device and
technical data (for tolerances see section 12. Technical Information).
Check function of electronic (set point LED must flash).
Calibrate Flow Monitor (see 10. Commissioning).