Kobold KAL-D Operating Instructions Manual Download Page 10

KAL-D 

page 10 

 

KAL-D K03/0516 

b)  Measuring range (span) adjustment 

 

The flow monitor is set at the factory for the greatest possible range of flow 
speed (2 m/s). At lower flow speeds, not all 8 LEDs will illuminate. To achieve 
finer monitoring resolution, the measuring range can be adjusted to better fit the 
actual flow speed. 
 

  Rotate the potentiometer clockwise as far as it will go (to the right-hand stop). 

The extreme right-hand LED in the LED bargraph will blink. Set the desired 
maximum system flowrate. 

  Now press the SET button. The DUAL LED blinks green.  

  Do not make any changes (potentiometer setting, etc.) while the DUAL LED 

is blinking. This adjustment phase will last approx. 5-15 sec. 

  The span adjustment procedure is now complete. The device now switches 

automatically to the monitoring mode. This adjustment has set the device 
measuring range so that it now extends across the entire LED bargraph at 
the maximum system flow. 

  The adjustment procedure is now complete. It may be repeated as often as 

necessary. 

 

c) Measuring mode 

 

After adjustment, the flow monitor is once again in measuring mode. 
The flow is constantly monitored and the actual value of the flow speed is 
displayed on the LED bargraph. 
 
 

Switching point setting 

The potentiometer is now used to set the switching point (threshold) of the flow 
switch. The switching point is displayed as a blinking LED on the bargraph. If the 
flow rate increases to the point that illuminated LEDs on the bargraph (actual flow 
value) reaches the position of the blinking LED (setpoint), the flow monitor 
switches over from ALARM to FLOW. This can be seen at the display: the DUAL 
LED that was showing a steady red light now switches to a steady green light. 
The output is also switched at the same time. 
 
 Slowly 

blinking 

switching point LED (setpoint) 

actual flow < setpoint (no flow)

 

 

 

 

 

 

 

 

 

 

Alarm status 

 DUAL LED illuminated red 

no LEDs lit = no flow 

 
 Slowly 

blinking 

switching point LED (setpoint)

 

actual flow < flow below set-point

 

 

 

 



 

 

 

 

 

Alarm status 

light strip actual value 

Actual flow below setpoint 

 DUAL LED illuminated red 

 

Summary of Contents for KAL-D

Page 1: ...Operating Instructions for Compact Calorimetric Flow Monitor Model KAL D...

Page 2: ...dicators and Controls 7 9 Signal Output 8 9 1 Output function 8 10 Commissioning 9 11 Error Messages 11 12 Maintenance 11 13 Technical Information 12 14 Order Codes 12 15 Dimensions 13 16 EU Declarati...

Page 3: ...e in machines the measuring unit should be used only when the machines fulfil the EC machine guidelines 3 Instrument Inspection Instruments are checked before dispatch and should arrive in perfect con...

Page 4: ...bargraph by the individually blinking LED Sensor The model KAL D flow switch consists of a sensor with an evaluating electronic circuit The unit should only used for water like liquids for which the...

Page 5: ...flowing the heat generated in the sensor is transferred to the liquid i e the sensor is cooled The cooling time is an accurate measure of the flow speed The sensor signal is compared with the referen...

Page 6: ...lowing mounting position is recommended see figure below 7 Electrical Connection Caution Make sure that the electrical supply lines are de energized when connection the device Make sure the the supply...

Page 7: ...e switching point LED starts to blink more rapidly DUAL LED 2 The DUAL LED display indicates the following The switching point Red ALAM actual flow below setpoint Green FLOW actual flow above setpoint...

Page 8: ...nd GND GROUND 0 VDC NPN output type of contact N or M The NPN transistor output either grounds the output pin GROUND 0 VDC or is high resistance open circuit The maximum output current is 400 mA The l...

Page 9: ...complies with this directive First install the sensor complete the Mechanical connection then connect the electrical lines complete the Electrical connection After these steps are completed the zero...

Page 10: ...low The adjustment procedure is now complete It may be repeated as often as necessary c Measuring mode After adjustment the flow monitor is once again in measuring mode The flow is constantly monitore...

Page 11: ...r the settings are completed screw the cover tightly back on the housing make sure that the window for viewing the LED bargraph is aligned with the bargraph 11 Error Messages The sensor element itself...

Page 12: ...indicator on LED strip display blinking LED Output status indicator 1 dual LED Switching output Semiconductor PNP or NPN max 400 mA short circuit proof N O or N C contact set at the factory Electrical...

Page 13: ...KAL D KAL D K03 0516 page 13 15 Dimensions D C mm AF mm L M 12x1 23 19 40 5 G 1 4 26 19 40 5 G 1 2 43 27 55 5 1 4 NPT 26 19 40 5 1 2 NPT 43 27 55 5...

Page 14: ...onformity with the standards noted below EN 61000 6 4 2011 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission standard for industrial environments EN 61000 6 2 2005 Electromagnetic...

Reviews: