ZED-Z
ZED-Z K11/0522
page 11
GENERAL SETTINGS
Menu Item
Parameter / Function
Explanation / Values / Other
Language
Select menu language
German or English
fUnitFS *
Measuring unit for flow
measurement
mL/s, mL/m, L/s, L/m, L/h, m
3
/m, m
3
/h,
GPM, GPH, UU/s, UU/m, UU/h
fValueFS *
Maximum measuring range value
for flow measurement
Range = 0,00...99,9..._100...9999
fMinVal *
Minimum measuring range value
for flow measurement
Basis is fValueFS and fUnitFS
If the level drops below this, the flow indicator goes to 0.
fPls/rev*
Impulse per sensor wheel
revolution
Number of impulses per revolution of the sensor wheel or the like
Necessary for long-term period averaging if the readings per revolution vary.
The function is switched off when the input value is 1.
fJumpVD*
Flow switch value for attenuation
cut-off
Value in %, basis is fValueFS and fUnitFS.
Attenuation does not function if the switch value is 0%.
fOverflV *
Flow overflow value (overflow)
Value in %, basis is fValueFS and fUnitFS.
If exceeded, an M100 report is generated and faded in, alternating
with the flow indicator.
The report is saved and can be reset by briefly pressing the
PGM key.
fFactor
Select pulse ration
Selection of works calibration or user calibration.
(only for devices Model DF-...ZLxxx and Model-...ExxR)
UserUnit.
Special volume unit
Customer-specific special unit UU.
The value entered corresponds to the number of litres of the special unit, e.g.
in the case of the unit
Barrel
the factor would for example be 115.6271.
SPdirect
Activation of direct input switching
point
yes: Direct input of switching points s1SPoint and
s2SPoint is possible using the keys (default).
no: The switching points can only be set in the menu .
*) Only for ZED devices: Device-specific parameter, is only visible after activation in the
SecCode
menu item in the
SERVICE
menu group, and can be changed.
Summary of Contents for DF ZL Series
Page 1: ...Operating Instructions for Counter Electronic Model ZED Z or DF ZLxxx or Model ExxR ...
Page 10: ...ZED Z page 10 ZED Z K11 0522 7 4 General Settings ...
Page 12: ...ZED Z page 12 ZED Z K11 0522 7 5 Flow analogue output and relay 1 ...
Page 15: ...ZED Z ZED Z K11 0522 page 15 7 6 Relay 2 and volume counter ...