3
Installation and commissioning
Thermo-Hygrometer KNX TH65-AP
• Date of issue: 29.03.2012 • Technical changes reserved. Errors reserved.
The following standards have been considered for the evaluation of the product in
terms of electro magnetic compatibility:
Transient emissions:
•
EN 60730-1:2000 Section EMV (23, 26, H23, H26) (threshold category: B)
•
EN 50090-2-2:1996-11 + A1:2002-01 (threshold category: B)
•
EN 61000-6-3:2001 (threshold category: B)
Interference resistance:
•
EN 60730-1:2000 Section EMV (23, 26, H23, H26)
•
EN 50090-2-2:1996-11 + A1:2002-01
•
EN 61000-6-1:2004
The product has been tested for the above mentioned standards by an accredited EMV
laboratory.
2. Installation and commissioning
2.1. Notes on installation
Installation, inspection, commissioning and troubleshooting of
the device must only be carried out by a competent electrician.
Disconnect all lines to be assembled, and take safety precautions against accidental
switch-on.
The device is exclusively intended for appropriate use. With each inappropriate change
or non-observance of the instructions for use, any warranty or guarantee claim will be
void.
BCU type
Own micro controller
PEI type
0
Group addresses
max. 184
Allocations
max. 184
Communication objects
110
Measurement range
temperature
-40...+80°C
Resolution (temperature)
0,1°C
Accuracy (temperature)
±1°C at -10...+85°C
±1,5°C at -25...+150°C
Measurement range
humidity
0...100%
Resolution (humidity)
0,1%
Accuracy (humidity)
0...20% = ±5%R. H.
20...80% = ±3%R. H.
80...100% = ±5%R. H.
Drift (humidity)
±0,5%R. H. per year in normal air