SPECIFICATIONS
Device model
SAS-04.16
Outputs (control channels)
Number of outputs
4
Output type / Disconnection type
Potential-free outputs-bistable relay with tungsten pre-make
contact / Micro-disconnection
Rated current per output
16A/230V AC, 16A/24V DC
Capacitive load
140
µF
Maximum switching voltage
400V AC, 300V DC
Maximum load
(resistive / inductive)
4000W / 1500W
Maximum inrush current
165A/20ms
800А/200
µs
Maximum relay response time
10ms
Maximum load per output
Incandescent lamps
2500W
Halogen lamp 230V
2500W
Halogen lamp, electronic tramsformer
1500W
Fluorescent lamp not compensated
2300W
Fluorescent lamp parallel compensated
1500W
Maximum number of electronic tranformers
20
Cross-section of the connected wire to the screw terminals
1 x (0,5-4mm²)
2 x (0,5-2,5mm²)
Mechanical lifetime of the relay (cycles, minimum)
3.000.000
KNX interface
Specification
TP-256
Available application so ware
ETS 5
KNX connector
4-wire EIB connector (PUSH WIRE spring clips) for standard
cable TP1 0,8мм Ø
Power supply
via KNX bus
Consumption on the KNX bus (29V DC)
< 5mA
< 150mW
Operation temperature
0°C .. + 45°C
Operation humidity
5 .. 95% (no condensation)
Degree of protection
IP 20, clean environment
Mounting type
DIN rail 35mm
Dimensions
71,3 х 90,5 х 62mm (4TE)
Weight
185g