KNX Module SAS-04.16 Quick Manual Download Page 2

page 2

SPECIFICATIONS 

Device model

SAS-04.16

Outputs (control channels)

Number of outputs

4

Output type / Disconnection type

Potential-free outputs-bistable relay with tungsten pre-make 

contact / Micro-disconnection

Rated current per output

16A/230V AC, 16A/24V DC

Capacitive load  

140

µF

Maximum switching voltage

400V AC, 300V DC

Maximum load 
(resistive / inductive)

4000W / 1500W

Maximum inrush current

165A/20ms

 800А/200

µs

Maximum relay response time

10ms

Maximum load per output

Incandescent lamps             

2500W

Halogen lamp 230V

2500W

Halogen lamp, electronic tramsformer

1500W

Fluorescent lamp not compensated

2300W

Fluorescent lamp parallel compensated

1500W

Maximum number of electronic tranformers

 20

Cross-section of the connected wire to the screw terminals       

1 x (0,5-4mm²) 

2 x (0,5-2,5mm²)

Mechanical lifetime of the relay (cycles, minimum)

3.000.000

KNX interface

Specification

TP-256

Available application so ware

ETS 5

KNX connector

4-wire EIB connector (PUSH WIRE spring clips) for standard 

cable TP1 0,8мм Ø 

Power supply

via KNX bus

Consumption on the KNX bus (29V DC)

< 5mA

< 150mW 

Operation temperature

0°C  ..  + 45°C

Operation humidity

5 .. 95% (no condensation)

Degree of protection

IP 20, clean environment

Mounting type

DIN rail 35mm

Dimensions

71,3 х 90,5 х 62mm (4TE)

Weight

185g